For larger casing when Vent Pipe does not pass across casing. All Sizes
switch contacts must point toward the Cell Panel. Black Iron Street 90 can be
used at Valve Inlet instead of Brass Street 90.
Brass Street Tee
A11366
Fig. 13 - LGPS for Casing Wider Than 14-3/16 (360 mm)
and Vent Does Not Pass Between Inducer and Burner As-
sembly
INSTALL LOW GAS PRESSURE SWITCH WIRES
1. Locate the orange wire in the kit with an insulated straight
female spade terminal and an insulated straight male ter-
minal on the other end.
2. Connect the female terminal to a terminal on the Low Gas
Pressure Switch.
3. Locate the orange wire in kit with an insulated straight fe-
male spade terminal and an insulated female flag terminal
on the other end.
4. Connect both straight female terminals of the orange wires
to the ternfinals on the Low Gas Pressure Switch.
INSTALL MANIFOLD
1. Align the orifices in the manifold assembly with the sup-
port rings on the end of the burner.
2. Insert the orifices in the support rings of the burners. Man-
ifold mounting tabs should fit flush against the burner box
NOTE: If manifold does not fit flush against the burner box, the
burners are not fully seated forward. Remove the manifold and
check burner positioning in the burner box assembly.
3. Attach the green/yellow wire and ground terminal to one
of the manifold mounting screws.
4. Install the remaining manifold mounting screws.
5. Connect the wires to the flame sensor and hot surface ig-
niter.
6. Connect the connector harness to gas valve
NOTE: Use only propane-resistant pipe dope. Do not use Teflon
tape.
7. Insert the gas pipe through the grommet in the casing. Ap-
ply a thin layer of pipe dope to the threads of the pipe and
thread the pipe into the gas valve.
NOTE: Use a back-up wrench on the gas valve to prevent the
valve from rotating on the manifold or damaging the mounting to
the burner box.
8. With a back-up wrench on the inlet boss of the gas valve,
finish tightening the gas pipe to the gas valve.
9. Turn gas on at electric switch on gas valve.
MODIFY PRESSURE SWITCH WIRING
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage or
improper operation.
Label all wires prior to disconnection when servicing
controls.
D'EQUIPEMENT D'OPERATION
Toute erreur de cfiblage peut _tre une source de danger et de
panne.
Lors des op6rations d'entretien des commandes, 6tiqueter
tousles/ills avant de les d6connecter.
1. Disconnect orange wire from Low Pressure switch LPS on
inducer housing.
2. Connect the orange wire from the Low Pressure Switch to
the orange wire with the insulated male spade terminal.
3. Connect the orange wire from the Low Gas Pressure
Switch to the terminal on the Low Pressure Switch.
4. Route orange wires along wire harness. If possible, secure
with wire tie provided in kit.
CHECK INLET GAS PRESSURE
[]NIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
DO NOT operate furnace more than one minute to check
inlet gas pressure, as conversion is not complete at this time.
NOTE: This kit is to be used only when inlet gas pressure is
between ll.0-in. W.C. and 13.6-in. W.C.
1. Verify manometer is connected to inlet pressure tap on gas
valve.
2. Turn on furnace power supply.
3. Turn gas supply manual shutoff valve to ON position.
FIRE, EXPLOSION, ELECTRICAL SHOCK
HAZARD
Failure to follow this warning could result in personal
iniury, death or property damage.
Gas supply MUST be shut off before disconnecting
electrical power and proceeding with conversion.
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
iniury, death or property damage.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position and
install a lockout tag. There may be more than one
disconnect switch. Lock out and tag switch with a suitable
warning label. Verify proper operation after servicing.
4. Turn furnace gas valve switch to ON position.
5. Turn Setup Switch SWI-2 on furnace control ON (see
Fig. 14).
6. Jumper R-W/WI and R-W2 thermostat connections on
control.