7. After burners ignite and blower starts allow the furnace to
run for at least 10 minutes before checking Temperature
Rise.
Maximum Heat Temperature Rise
If the temperature rise is too high or too low in Maximum Heat:
1. Remove jumpers from R, Wl and W2.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of the Efficiency/Comfort Adjustment
switch SWl-4. When set to OFF (Efficiency Mode), air-
flow is 10% higher for Minimum, 7.5% for Intermediate
Heat, and 17.5% for Maximum Heat. Factory default posi-
tion is ON (Comfort Mode).
5. Turn 115 VAC power on.
6. Re-check Minimum Heat Temperature Rise.
7. Remove jumpers across thermostat connections to termin-
ate the call for heat. Wait until the blower off delay is com-
pleted.
8. Turn gas supply manual shutoff valve to OFF position.
9. Turn off furnace power supply.
10. Remove manometer from the outlet pressure tap of the gas
valve.
11. Apply pipe dope sparingly to 1/8-in. NPT plug and re-in-
stall outlet pressure tap on the gas valve.
12. Re-install plastic cap over rotary adjustment switch on the
top of the gas valve.
CHECK LOW GAS PRESSURE SWITCH
The newly installed low gas pressure switch is a safety device
used to guard against adverse burner operating characteristics that
can result from low gas supply pressure. Switch opens at not less
than 6.5 in. W.C. and closes at not greater than 10.2 in. W.C.
This switch also prevents operation when the propane tank level
is low which can result in gas with a high concentration of
impurities, additives, and residues that have settled to the bottom
of the tank. Operation under these conditions can cause harm to
the heat exchanger system. This normally open switch closes
when gas is supplied to gas valve under normal operating
pressure. The closed switch completes control circuit. Should an
interruption or reduction in gas supply occur, the gas pressure at
switch drops below low gas pressure switch setting, and switch
opens. Any interruption in control circuit (in which low gas
pressure switch is wired) quickly closes gas valve and stops gas
flow to burners. When normal gas pressure is restored, the system
must be electrically reset to re-establish normal heating operation.
Before leaving installation, observe unit operation through 2
complete heating cycles. During this time, turn gas supply to gas
valve off just long enough to completely extinguish burner flame,
then instantly restore full gas supply. To ensure proper low gas
pressure switch operation, observe that there is no gas supply to
burners until after hot surface igniter begins glowing.
LABEL APPLICATION
1. Fill in Conversion Responsibility Label 337704-205 and
apply to Blower Access Door of furnace as shown. (See
Fig. 18. Date, name, and address of organization making
this conversion are required.
2. Attach Conversion Rating Plate Label 337704-201 to out-
er door of furnace., see Fig. 5.
3. Attach Gas Control Conversion Label 337704-202 to gas
valve. Do not use 337704-203, which is similar.
THiSFURNACEWAS CONVERTED
ON TO PROPANEGAS
(DAY-MONTH-YEAR)
KiT NO.: KGANP5201VSP
BY:
(Name and address of organization making this conversion),
which accepts the responsibility that this conversion has
been properly made.
CE GENC:RATEUR D'NR CHAUD A €:TI_
CONVERTiLE POUR
(JOUR-MOIS-ANNI_E)
DE L'ENSEMBLE N°.: KGANP5201VSP
PAR:
(Nora et adresse de I'organisme qui a effectu6 [a conversion),
qui accepte |' entrii.=re responsabilit6 de [a conversion,
337704-205 REV.B
Fig. 18 - Conversion Responsibility Label
Al1296
10
Vue de la page 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 25 26

Commentaires sur ces manuels

Pas de commentaire