SET GAS INPUT RATE
UNIT DAMAGE HAZARD
Failure to follow this caution may result in gas valve
damage.
Do not force the rotary adjustment switch on the
modulating gas valve. Do not turn the rotary adjustment
switch faster than one click per second when adjusting
manifold pressure. Gas valve will be damaged if excessive
force is used on the rotary switch.
/_r ner Flame
__ _ Burnel
Al1461
Fig. 16 - Burner Flame
For proper operation and long term reliability, the manifold
pressure must be adjusted as specified on the conversion kit rating
plate.
The modulating furnace manifold pressure is set at two points.
The first point is Maximum Heat. The second point is Mininmm
Heat. Do not adjust Intermediate Heat manifold pressure.
Intermediate Heat manifold pressure can be checked as part of the
temperature rise, but is not adjustable. Always adjust Maximum
Heat first, then Minimum Heat.
NOTE: DO NOT set Maximum Heat manifold pressure less than
10.5-in. W.C. or more than 11-in. W.C. for propane gas.
NOTE: Use care when perfornfing adjustments. Gas valve
adjustment is performed by turning a rotary adjustment switch
inside the gas valve with a small straight blade screwdriver.
Excessive force can break or bend the rotary adjustment switch
making it non-adjustable.
To adjust manifold pressure to obtain input rate for Maximum
Heat:
1. Make sure the gas supply is turned off to the furnace and
at the electric switch on the gas valve.
2. Remove the 1/8 inch NPT plug from the outlet pressure
tap on the gas valve.
3. Connect a manometer to the outlet pressure tap on gas
valve.
4. Turn on furnace power supply.
5. Turn gas supply manual shutoff valve to ON position.
6. Turn furnace gas valve switch to ON position.
7. Turn Setup switch SW 1-2 to ON.
8. Verify Set-up switch SW 4-2 is turned OFF.
9. Jumper the R to W/W1 and W2 thermostat connections at
the furnace control board.
10. After the main burners ignite and the blower starts, con-
firm Maximum Heat manifold pressure is correct, based
on the manifold pressure table on the Conversion Kit Rat-
ing Plate.
11. To adjust the Maxinmm Heat manifold pressure, Slowly
turn the rotary adjustment switch counterclockwise to de-
crease manifold pressure or clockwise to increase manifold
pressure.
12. Turn rotary adjustment switch no more than one click per
second until you obtain the required manifold pressure.
>
A11451
Fig. 17 - Modulating Gas Valve Adjustment
Main burner flame should be clear blue, almost transparent.
To adjust manifold pressure to obtain input rate for Minimum
Heat:
1. Remove the jumper from W2 at the thermostat connec-
tions at the furnace control board control.
2. Wait until the burners and the blower transitions to Minim-
um Heat.
3. Verify the Minimum Heat manifold pressure is correct,
based on the manifold pressure table on Conversion Kit
Rating Plate.
4. To adjust the Minimum Heat manifold pressure, Slowly
turn the rotary adjustment switch counterclockwise to de-
crease manifold pressure or clockwise to increase manifold
pressure.
5. Turn rotary adjustment switch no more than one click per
second until you obtain the required manifold pressure.
This adjustment will not affect the previous Maximum
Heat adjustment.
After adjusting the manifold pressure, allow the furnace to
operate an additional 5 nfinutes before checking Minimum Heat
Temperature rise.
Furnace must operate within ranges of temperature rise specified
on the furnace rating plate. Deternfine air temperature rise as
follows:
1. Place thermometers in return and supply ducts as near fur-
nace as possible. Be sure thermometers do not see heat ex-
changer so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to deternfine air
temperature rise.
3. Allow the furnace to run for at least 10 minutes before
checking Temperature Rise.
If the temperature rise is too high or too low in Minimum Heat:
1. Remove jumpers from R and W/W1.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of Heat Rise Adjustment Switch
SW1-3. When set to ON, airflow is raised 18% higher for
Minimum Heat and Intermediate Heat. Factory default po-
sition is OFF.
5. Turn 115 VAC power on.
6. Jumper R to W/W1 and W2.