Carrier 16JB Manuel d'utilisateur Page 27

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 26
2. Safeties:
a. Unit shall automatically shut down when any
of the following conditions occur: (Each of
these protective limits shall require manual
reset and cause an alarm message to be dis-
played on the LCD screen, informing the
operator of the shutdown cause.)
solution pump motor overload/high
temperature
refrigerant pump motor overload/high
temperature
low chilled water temperature
low evaporator refrigerant temperature
generator high solution temperature
loss of evaporator water flow
loss of cooling water flow
prolonged warm-up period
b. The control system shall detect conditions
which approach protective limits and take
self-corrective action prior to an alarm
occurring. The system shall automatically re-
duce chiller capacity when any of the
following parameters are outside their
normal operating range:
low evaporator refrigerant temperature.
generator high saturation temperature
generator high solution temperature
high solution concentration
During the capacity override period, a pre-
alarm (alert) message shall be displayed
informing the operator which condition is
causing the capacity override. Once the con-
dition is again within acceptable limits, the
override condition shall terminate and the
chiller shall revert to normal chilled water
control. If during either condition the protec-
tive limit is reached, the chiller shall shut
down, an alarm shall be generated, and a
text message shall be displayed informing
the operator which condition caused the
shut down and alarm.
3. Diagnostics and Service:
a. The control system shall execute a series of
pre-start checks whenever a start command
is received to determine if pressures,
temperatures, and timers are within prestart
limits, thereby allowing start-up to proceed.
If any of the limits are exceeded a text alert
message will be displayed informing the op-
erator of the cause of the pre-start alert.
b. The control system shall provide a manual
test which permits selection and test of indi-
vidual control components and inputs. A
thermistor test and transducer test shall
allow display on the LCD screen of the ac-
tual reading of each transducer and each
thermistor installed on the chiller.
A pump test shall automatically energize the
chilled water and condenser water pumps,
and the control system shall confirm water
flows have been established and require op-
erator confirmation prior to proceeding to
the next test.
A steam control valve test shall allow the op-
erator to test the control valve travel range
by manually increasing or decreasing valve
travel limit. Upon completion of the steam
control valve test the control valve shall re-
vert to the closed position.
c. All sensors shall have quick disconnects to
allow replacement of the sensor without re-
placement of the entire sensor wire.
4. Building Control System Interface:
The chiller control system shall have the ability to
interface and communicate directly to the build-
ing control system without the use of additional
field installed hardware and software. The build-
ing control system and the absorption chiller must
be supplied by the same manufacturer. If different
building control and chiller suppliers are chosen
the chiller shall be supplied with a dataport mod-
ule which shall translate the information in the
chiller microprocessor to an ASCII stream of data
which can be read by any manufacturer’s building
management control system.
G. Electrical Requirements:
1. Power supply to the unit shall be 3-ph, 60 Hz
with voltages of 208, 230, 460, or 575 and
3-ph, 50 Hz with 400 v as specified on the equip-
ment schedule. A multitap transformer shall pro-
vide 110 v single-phase secondary power for the
control panel.
2. Contractor shall supply and install the electrical
power line and all auxiliary electrical protection
devices per local code requirements and as indi-
cated necessary by the chiller manufacturer.
3. Contractor shall supply and install electrical
wiring and devices required to interface the chiller
controls with the building controls system if
applicable.
H. Piping Requirements:
1. Piping and instrumentation for the chilled water,
cooling water, steam, and condensate piping (or
hot water supply and return piping) shall be sup-
plied and installed by the contractor/owner.
2. Absorber-condenser crossover piping shall be fur-
nished by the contractor/owner or the chiller
manufacturer as specified on the equipment
schedule.
3. Chilled water and condenser water flow switch
shall be field installed and supplied by either the
chiller manufacturer or the contractor/owner.
4. Piping from the rupture disk shall be provided
and installed by the contractor/owner and piped
in accordance with the chiller manufacturer’s
written instructions and any local jurisdictional
requirements.
27
Vue de la page 26
1 2 ... 22 23 24 25 26 27 28

Commentaires sur ces manuels

Pas de commentaire