Controls
Microprocessor controls
Microprocessor controls provide the safety, interlock, ca-
pacitycontrol, andindications necessaryto operatethechiller
in a safe and efficient manner.
Control system
The microprocessor control on each 16JB double-effect
chiller isfactory mounted, wired,and tested to ensurechiller
protection and efficient capacity control. In addition, the
program logic ensures proper starting, stopping, and recy-
cling of the chiller and provides a communication link to
the Carrier Comfort Network (CCN).
Features
Control system
Component Test and Diagnostic Check
Menu-Driven Keypad Interface for Status Display,
Set Point Control, and System Configuration
CCN Compatible
Primary and Secondary Status Messages
Individual Start/Stop Schedules for Local and
CCN Operation Modes
Recall of Up to 25 Alarm/Alert Messages with
Diagnostic Help
Extensive Diagnostic and Service Capabilities
Advanced Crystallization Protection
Safety cutouts
Solution Pump Motor Overload/High Temperature
Refrigerant Pump Motor Overload/High Temperature
Low Chilled Water Temperature Cutout
Generator Solution Temperature Cutout
Generator Pressure Cutout
Evaporator and Condenser Water Flow
Intermittent Power Loss
Generator High Level
Protective limits
Low Chilled and Cooling Water Flow
Solution Pump Overload/High Temperature
Refrigerant Pump Overload/High Temperature
Transducer Reference Voltage
Generator High Temperature
Solution Pump Pressure
Entering and Leaving Chilled Water Temperature
Cooling Water Temperature Entering and
Leaving Absorber
Cooling Water Temperature Leaving Condenser
Weak Solution Temperature Leaving Absorber
Strong Solution Temperature Entering Heat Exchanger
Strong Solution Temperature Leaving Generator
Solution Temperature Entering Spray Header
Low Refrigerant Temperature
Condenser Vapor Condensate Temperature
Overrides
Refrigerant Low Temperature
Generator High Saturation Temperature
Generator High Solution Temperature
Generator High Solution Level
Recycle Control
Solution Concentration Control
Desolidification Mode
Capacity control
Leaving Chilled Water Control
Entering Chilled Water Control
Ramp Loading
Steam Demand Limit
Chilled Water Reset
Indications
Chiller Operating Status Message
Absorption Cycle State Points
Dilution Cycle
Power-On
Pre-Alarm Alert
Alarm
Safety Shutdown Messages
Elapsed Time (Hours of Operation)
Control Valve Position
16JB MICROPROCESSOR CONTROL CENTER
(EXTERNAL VIEW)
LID
WINDOW
SOLUTION
PUMP
REFRIGERANT
PUMP
DILUTION
VALV E
EXHAUST
PURGE
LLC
VALV E
DILUTION CYCLE
MANUAL/AUTO
GG
W
R
W
19