Performance data
ENGLISH
UNIT 16JB 010 012 014 018 021 024 028 032
COOLING CAPACITY (ton) 108 122 137 186 211 245 279 326
CHILLED WATER
Flow Rate (gpm) 259 292 328 446 506 587 669 781
Pressure Drop (ft) 15.9 16.0 16.4 15.6 15.7 15.9 16.2 15.6
COOLING WATER
Flow Rate (gpm) 389 439 493 670 760 882 1004 1174
Pressure Drop (ft) 20.0 20.2 19.2 22.4 23.2 20.8 20.9 21.3
STEAM (lb/hr-ton) 1915 2178 2448 3319 3784 4373 5004 5826
(lb/hr) 17.7 17.9 17.9 17.8 17.9 17.9 17.9 17.9
UNIT 16JB 036 041 047 054 057 061 068
COOLING CAPACITY (ton) 362 413 479 539 574 618 680
CHILLED WATER
Flow Rate (gpm) 868 990 1148 1292 1376 1481 1630
Pressure Drop (ft) 15.7 15.9 16.1 33.3 32.9 32.7 32.9
COOLING WATER
Flow Rate (gpm) 1303 1487 1724 1940 2066 2225 2448
Pressure Drop (ft) 22.0 20.9 21.6 35.9 36.2 36.5 36.3
STEAM (lb/hr-ton) 6492 7387 8585 9706 10,440 11,231 12,456
(lb/hr) 17.9 17.9 17.9 18.0 18.2 18.2 18.3
LEGEND
ARI Air Conditioning and Refrigeration Institute
NOTE: Ratings are based on ARI 560, latest edition, 54/44 F (2.4 gpm/ton) chilled water; 85 F cooling water (3.6 gpm/ton);
fouling factor .00025 ft
2
-hr F/Btu.
SI
UNIT 16JB 010 012 014 018 021 024 028 032
COOLING CAPACITY (kW) 380 429 482 654 742 862 981 1147
CHILLED WATER
Flow Rate (L/s) 16.3 18.5 20.7 38.1 31.9 37.1 42.2 49.3
Pressure Drop (kPa) 47.6 47.9 49.0 46.7 46.9 47.6 48.3 46.7
COOLING WATER
Flow Rate (L/s) 24.5 27.7 31.1 42.3 47.9 55.6 63.3 74.1
Pressure Drop (kPa) 59.8 60.5 57.3 67.0 69.4 62.2 62.4 63.7
STEAM (kg/hr-kW) 2.29 2.30 2.30 2.30 2.31 2.30 2.31 2.30
(kg/hr) 867 988 1110 1505 1716 1983 2269 2642
UNIT 16JB 036 041 047 054 057 061 068
COOLING CAPACITY (kW) 1273 1453 1685 1896 2019 2173 2392
CHILLED WATER
Flow Rate (L/s) 54.7 62.5 72.4 81.5 86.8 93.5 102.8
Pressure Drop (kPa) 46.9 47.4 48.2 99.4 98.4 97.7 98.4
COOLING WATER
Flow Rate (L/s) 82.2 93.8 108.8 122.4 130.3 140.4 154.4
Pressure Drop (kPa) 65.9 62.3 64.6 107.4 108.3 109.2 108.4
STEAM (kg/hr-kW) 2.31 2.31 2.31 2.32 2.35 2.34 2.36
(kg/hr) 2944 3350 3893 4402 4735 5093 5649
LEGEND
ARI Air Conditioning and Refrigeration Institute
NOTE: Ratings are based on ARI 560, latest edition, 12.2/6.7 C (.043 L/s-kW) chilled water; 29.4 C (.081 L/s-kW) cooling
water; fouling factor .000044 m
2
-hr C/w.
Part-load performance
Throughthe useof Carrier’sElectronic Catalog(E-CAT)com-
puter program,part-load performanceenergy requirements
ranging from 10% to 100% of full load can be provided in
accurate detail. These programs are rated in accordance
with ARI 560, latest edition.
ARI560, latest edition,defines IntegratedPart LoadValue
(IPLV) as a measure of part-load efficiency representing the
weighted average of overall chiller performance calculated
by the following equation:
IPLV = .17A + .39B + .33C + .11D
where A = COP at 100%
B = COP at 75%
C = COP at 50%
D = COP at 25% or minimum load
NOTE: COP = Coefficient of Performance
14