Electrical data (60 Hz)
UNIT VOLTAGE
208/230-3-60*
UNIT
16JB
PUMP/MOTOR
SIZE (Hp)
RLA LRA
MCA MFA kW
SP RP SP RP SP RP
010 3 3 12.0 12.0 55.0 55.0 28.0 40.0 3.8
012 3 3 12.0 12.0 55.0 55.0 28.0 40.0 3.8
014 3 3 12.0 12.0 55.0 55.0 28.0 40.0 3.8
018 3 3 12.0 12.0 55.0 55.0 28.0 40.0 4.1
021 3 3 12.0 12.0 55.0 55.0 28.0 40.0 4.1
024 3 3 12.0 12.0 55.0 55.0 28.0 40.0 4.4
028 3 3 12.0 12.0 55.0 55.0 28.0 40.0 4.4
032 5 3 19.0 12.0 82.0 55.0 36.8 50.0 5.0
036 5 3 19.0 12.0 82.0 55.0 36.8 50.0 5.0
041 5 5 19.0 19.0 82.0 82.0 43.8 60.0 5.9
047 5 5 19.0 19.0 82.0 82.0 43.8 60.0 5.9
054 5 5 19.0 19.0 82.0 82.0 43.8 60.0 6.8
057 5 5 19.0 19.0 82.0 82.0 43.8 60.0 6.8
061 5 5 19.0 19.0 82.0 82.0 43.8 60.0 7.3
068 5 5 19.0 19.0 82.0 82.0 43.8 60.0 7.3
460-3-60*
UNIT
16JB
PUMP/MOTOR
SIZE (Hp)
RLA LRA
MCA MFA kW
SP RP SP RP SP RP
010 3 3 6.0 6.0 27.5 27.5 14.5 20.0 3.8
012 3 3 6.0 6.0 27.5 27.5 14.5 20.0 3.8
014 3 3 6.0 6.0 27.5 27.5 14.5 20.0 3.8
018 3 3 6.0 6.0 27.5 27.5 14.5 20.0 4.1
021 3 3 6.0 6.0 27.5 27.5 14.5 20.0 4.1
024 3 3 6.0 6.0 27.5 27.5 14.5 20.0 4.4
028 3 3 6.0 6.0 27.5 27.5 14.5 20.0 4.4
032 5 3 9.5 6.0 41.0 27.5 18.9 25.0 5.0
036 5 3 9.5 6.0 41.0 27.5 18.9 25.0 5.0
041 5 5 9.5 9.5 41.0 41.0 22.4 30.0 5.9
047 5 5 9.5 9.5 41.0 41.0 22.4 30.0 5.9
054 5 5 9.5 9.5 41.0 41.0 22.4 30.0 6.8
057 5 5 9.5 9.5 41.0 41.0 22.4 30.0 6.8
061 5 5 9.5 9.5 41.0 41.0 22.4 30.0 7.3
068 5 5 9.5 9.5 41.0 41.0 22.4 30.0 7.3
575-3-60
UNIT
16JB
PUMP/MOTOR
SIZE (Hp)
RLA LRA
MCA MFA kW
SP RP SP RP SP RP
010 3 3 4.8 4.8 23.0 23.0 11.8 15.0 3.8
012 3 3 4.8 4.8 23.0 23.0 11.8 15.0 3.8
014 3 3 4.8 4.8 23.0 23.0 11.8 15.0 3.8
018 3 3 4.8 4.8 23.0 23.0 11.8 15.0 4.1
021 3 3 4.8 4.8 23.0 23.0 11.8 15.0 4.1
024 3 3 4.8 4.8 23.0 23.0 11.8 15.0 4.4
028 3 3 4.8 4.8 23.0 23.0 11.8 15.0 4.4
032 5 3 7.6 4.8 33.0 23.0 15.3 20.0 5.0
036 5 3 7.6 4.8 33.0 23.0 15.3 20.0 5.0
041 5 5 7.6 7.6 33.0 33.0 18.1 25.0 5.9
047 5 5 7.6 7.6 33.0 33.0 18.1 25.0 5.9
054 5 5 7.6 7.6 33.0 33.0 18.1 25.0 6.8
057 5 5 7.6 7.6 33.0 33.0 18.1 25.0 6.8
061 5 5 7.6 7.6 33.0 33.0 18.1 25.0 7.3
068 5 5 7.6 7.6 33.0 33.0 18.1 25.0 7.3
*Refrigerant and solution pump/motor assemblies are designed for dual
voltage applications and can be applied at either 208/230-3-60 or 460-
3-60 (requiring only wiring and heater element changes).
LEGEND
LRA Locked Rotor Amps
MCA Minimum Circuit Ampacity
MFA Maximum Fuse Amps
RLA Rated Load Amps
RP Refrigerant Pump
SP Solution Pump
NOTES:
1. Standard voltages (3-Ph, 60 Hz)
VOLTAGE FOR USE ON SUPPLY VOLTAGES
208 200 to 208 Volt Systems
230 220 to 240 Volt Systems
460 440 to 480 Volt systems
575 550 to 600 Volt Systems
Motor nameplates can be stamped for any voltage within the supply volt-
age range.
2. Control circuit voltage 110-1-60.
3. Control circuit amps = 1.0.
4. MCA and MFA include refrigerant and solution pumps, and control
circuit.
5. kW includes solution and refrigerant pumps and control circuit.