Carrier AQUASNAP 30RB060-390 Spécifications Page 19

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 72
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 18
19
7169.08
282.25[]
2806.54
110.49[]
800.00
31.50[]
CG
x
930.95
36.652[]
1885.22
74.221[]
PIPING ENTRANCE AREA3222.17
126.86[]
1348.58
53.09[]
1256.59
49.47[]
2690.32
105.92[]
2236.08
88.03[]
760.39
29.94[]
1447.8
[57.0]
400.00
15.75[]
240.00
9.45[]
CG
y
200.00
7.87[]
100.00
3.94[]
RIGGING HOLE
38.00
1.50[]
864.00
34.02[]
408.89
16.10[]
UNIT MOUNTING
1981.65
78.02[]
UNIT MOUNTING
2794.35
110.01[]
UNIT MOUNTING
1575.30
62.02[]
408.89
16.10[]
2281.37
89.82[]
437.86
17.24[]
437.86
17.24[]
200.00
7.87[]
200.00
7.87[]
1990.54
78.37[]
UNIT MOUNTING
2156.30
84.89[]
39.89
1.57
[]
800.00
31.50[]
2016.54
79.39[]
759.89
29.92[]
2438.40
[96.00]
938.35
36.94[]
215.73
8.49[]
WEIGHT
CU/AL
lb/kg
WEIGHT
CU/CU
lb/kg
WEIGHT
MCHX
lb/kg
CENTER OF GRAVITY
CGx
MM [INCH]
CGy
MM [INCH]
30RB-210
13734
6243
15181
6901
12772
5793
3528
[138.90]
917
[36.10]
30RB-225
14067
6394
15514
7052
13093
5937
3588
[141.26]
906
[35.67]
CIRCUIT C
COMPRESSORS
POWER BOX 2
230V ONLY
CKT C
POWER BOX 1 & 2
(PEB)
ALL VOLTAGES
LEAVING WATER
6" VICTAULIC
ENTERING WATER
6" VICTAULIC
COOLER VENT
1/4" NPT
COOLER DRAIN
3/4" NPT
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
A
A
CIRCUIT A
COMPRESSORS
CIRCUIT B
COMPRESSORS
POWER BOX 1
230V CKT B
380V,460V,575V
CKT A,B,C
COIL SERVICE AREA
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
PEB1 230V DUAL POINT
380V,460V,575V DUAL & SINGLE POINT
PEB2 230V DUAL POINT
380V,460V,575V DUAL POINT
SEE DETAIL
B
VIEW-A-A
DETAIL B
SCALE 1:4
22.2[.87]
MOUNTING HOLE
POWER BOX
230V ONLY (CKT A)
SCROLLING MARQUEE
DISPLAY
FIELD CONTROL WIRING
FAN ELECTRICAL BOX
(FEB)
ALL VOLTAGES
AIR FLOW
COIL SERVICE AREA
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(DUAL POINT 230V ONLY)
(DUAL POWER NFD
CIRCUIT B 380,460,
575V ONLY)
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 from solid surface.
2. Temperature relief devices located on suction line, liquid line
and filter drier of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of unit for
condenser coil removal.
a30-4716
MCHX — Microchannel Condenser Coil
Fig. 17 — 30RB210, 225 Air-Cooled Chiller Dimensions