Carrier 59SP2A Manuel d'instructions

Naviguer en ligne ou télécharger Manuel d'instructions pour Pompes à chaleur Carrier 59SP2A. Carrier 59SP2A Instruction manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 88
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
1
59TP5A
Tw o --- S t a g e , 4 --- W a y M u l t i p o i s e
Co ndensing Gas Furnace
Series 100
Installation, Start---up, Operating and
Se rvice and M aintenance Ins tructions
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS 3.........................
INTRODUCTION 4...................................
CODES AND STANDARDS 4...........................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 4...
ACCESSORIES 5.....................................
LOCATION 8........................................
General 8.........................................
AIR FOR COMBUSTION AND VENTILATION 9..........
Introduction 9.....................................
CONDENSATE TRAP 12...............................
Upflow 12........................................
Downflow 12.....................................
Horizontal 12.....................................
CONDENSATE DRAIN 16.............................
INSTALLATION 19...................................
Upflow 19........................................
Downflow 19.....................................
Horizontal 20......................................
Filter Arrangement 20...............................
AIR DUCTS 29.......................................
General Requirements 29.............................
Ductwork Acoustical Treatment 29.....................
GAS PIPING 31......................................
ELECTRICAL CONNECTIONS 32.......................
115--V Wiring 32...................................
J--Box Installation 33................................
24--V Wiring 33....................................
Accessories 33.....................................
Alternate Power Supplies 34..........................
VENTING 38........................................
Special Venting Requirements for Installations in Canada 38.
General 38........................................
Materials 38.......................................
Venting Systems 39.................................
Combustion Air and Vent Piping Insulation Guidelines 42...
Installing the Termination 44..........................
Venting System Length Calculations 49.................
START--UP, ADJUSTMENT, AND SAFETY CHECK 63......
General 63.........................................
Thermostat Setup Switch 63............................
Prime Condensate Trap 63.............................
Adjustments 64......................................
SERVICE AND MAINTENANCE PROCEDURES 72........
Cleaning Heat Exchangers 77...........................
SEQUENCE OF OPERATION 81........................
PARTS REPLACEMENT GUIDE 87......................
TABLES
Loose Parts Bag 5.....................................
Minimum Clearances to Combustible Materials 5.............
Minimum Free Area Required 11.........................
Minimum Space Volumes 11.............................
Filter Size Information 23...............................
Opening Dimensions 25................................
Air Delivery CFM 30...................................
Maximum Capacity of Pipe 32...........................
Electrical Data 35......................................
Vent Termination Kit for Direct Vent (2--Pipe) Systems 40......
Combustion--Air Vent Pipe, Fitting & Cement Material.. 46.....
Maximum Allowable Exposed Vent Lengths Insulation 47......
Maximum Equivalent Vent Length 48......................
Deductions from Maximum Equivalent Vent Length 48........
Altitude Derate Multiplier for U.S.A. 69....................
Blower Off Delay Setup Switch 69........................
Gas Rate 69..........................................
Orifice Size and Manifold Pressure 70.....................
CERTIFIED
Use of the AHRI Certified
TM
Mark indicates a
manufacturers participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
Portions of the text and tables are reprinted from NFPA 54/ANSI
Z223.1--2009E, with permission of National Fire Protection
Association, Quincy, MA 02269 and American Gas Association,
Washington DC 20001. This reprinted material is not the complete
and official position of the NFPA or ANSI on the referenced
subject, which is represented only by the standard in its entirety.
Vue de la page 0
1 2 3 4 5 6 ... 87 88

Résumé du contenu

Page 1 - Series 100

159TP5ATw o --- S t a g e , 4 --- W a y M u l t i p o i s eCo ndensing Gas FurnaceSeries 100Installation, Start---up, Operating andSe rvice and M aint

Page 2 - IMPORTANT

10in. (25 mm) from the sides and back and 6 in. (150 mm) from thefront. The opening shall directly communicate with the outdoors orshall communicate t

Page 3 - SAFETY CONSIDERATIONS

11Table 3 – Minimum Free Area Required for Each Combustion Air Opening or Duct to OutdoorsFURNACEINPUT(BTUH)TWO HORIZONTAL DUCTS(1 SQ. IN./2,000 BTUH)

Page 4 - PRECAUTIONS PROCEDURE

12CONDENSATE TRAPCondensate Trap -- Upflow OrientationWhen the furnace is installed in the upflow position, it is notnecessary to relocate the condens

Page 5 - ACCESSORIES

13Remove relief tube from reliefport on condensate trap.Remove the screwthat secures the trap to the collector box andremove trap.Loosen clamp on inle

Page 6 - Fig. 1 -- Dimensional Drawing

14Remove plug fromcollector box.DO NOT DISCARD.If alternate vent positionis required, loosen clampon inlet of vent elbow.Remove the screw that secures

Page 7 - 80 / 27˚C

15If alternate vent positionis required, loosen clampon vent elbow inlet.Remove relief tubefrom port on collectorbox.Remove the screw that secures the

Page 8 - LOCATION

16CONDENSATE DRAIN CONNECTIONFROZEN AND BURST WATER PIPE HAZARDFailure to protect against the risk of freezing may result inproperty damage.Special pr

Page 9 - VENTILATION

17the other side of the casing should be facing the front of thefurnace.11. Slide a spring clamp over the end of the remaining rubberdrain elbow.12. A

Page 10 - Standard Method

18INSTALL CLAMPS ON DRAIN TUBEATTACH DRAIN TUBE TO CONDENSATE DRAIN TRAPPULL DRAIN STUB THROUGH CASINGOPEN SPRING CLAMPINSERT FACTORYïSUPPLIED 1/2ïIN.

Page 11

19INSTALLATIONThis furnace is certified to leak 2% or less of nominal airconditioning CFM delivered when pressurized to 1--in. watercolumn with all pr

Page 12 - CONDENSATE TRAP

2Required Notice for Massachusetts InstallationsIMPORTANTThe Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:5.08

Page 13 - Downflow Trap Configuration

20Return Air ConnectionsFIRE HAZARDA failure to follow this warning could cause personal injury,death and/or property damage.Never connect return--air

Page 14 - (Appearance may vary)

21There are no provisions for an internal filter rack in these furnaces.An external filter is required.The furnace is shipped with a factory-supplied

Page 15

22Table 5 – Filter Media Pressure Drop (Clean) Versus Airflow -- In. W.C. (Pa)14 x 25 Filter(356 x 635 mm)Factory-AccessoryWashableFactory-AccessoryMe

Page 16 - CONDENSATE DRAIN CONNECTION

23Table 7 – Air Filter Selection and Duct Sizing -- In. (mm)FURNACE CASING WIDTHFILTE R SIZEFILTER TYPESIDE RETURN BOTTOM RETURN14---3/16{ (360)16 x 2

Page 17 - L12F019B

2414-3/16 and 17-1/2-in.Furnace16-in. Media Cabinet21-in. Furnace4-Ton or less, ACcapacity airflow20-in. Media Cabinet4-in.Block OffPlate1/2-in.Screws

Page 18 - Formed end of

25PLENUMOPENINGCABDFLOOROPENINGDOWNFLOWSUBBASESHEET METALPLENUMFLOOROPENINGFURNACE(OR COIL CASINGWHEN USED)COMBUSTIBLEFLOORINGAPPROVEDCOIL ASSEMBLYOR

Page 19 - INSTALLATION

26UPFLOW DOWNFLOW HORIZONTALYESNONOYESYESYESNO120°MINYES120°MINYES120°MIN90°90°PERFORATEDDISCHARGE DUCTFLANGEA10493Fig. 20 -- Duct Flanges1 3 / 4 ″1

Page 20 - Horizontal Installation

27ANY COMBINATION OF 1, 2, OR 3 PERMITTED.A11036Fig. 24 -- Upflow Return Air Configurations and RestrictionsA11037Fig. 25 -- Downflow Return Air Confi

Page 21

282-IN.(51 mm)ROLLOUT PROTECTION REQUIREDInstall 12” x 22” (305 x 559 mm) sheetmetal in front of burner compartmentarea.30 IN. (762 mm)MIN. WORK AREAC

Page 22

29AIR DUCTSMany states, provinces and localities are considering or haveimplemented standards and/or restrictions on duct sizingpractices, ductwork le

Page 23

3SAFETY CONSIDERATIONSFIRE, EXPLOSION, ELECTRICAL SHOCK, ANDCARBON MONOXIDE POISONING HAZARDFailure to follow this warning could result in dangerousop

Page 24 - Fig. 18 -- Media Filter

30Table 9 – Air Delivery -- CFM (With Filter)UNITSIZERETURN-AIRCONNECTIONSPEEDTAPS2, 3EXTERNAL STATIC PRESSURE (IN.W.C.)0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.

Page 25

31GAS PIPINGFIRE OR EXPLOSION HAZARDFailure to follow this warning could result in personalinjury, death, and/or property damage.Never purge a gas lin

Page 26 - UPFLOW DOWNFLOW HORIZONTAL

32Table 10 – Maximum Capacity of PipeNOMINALIRON PIPESIZEIN. (MM)LENGTH OF PIPE --- FT. (M)10(3.0)20(6.0)30(9.1)40(12.1)50(15.2)1/2 (13) 175 120 97 82

Page 27 - ANY MODEL

33J--Box InstallationFIRE OR ELECTRICAL SHOCK HAZARDFailure to follow this warning could result in personalinjury, death, or property damage.If field-

Page 28 - (SEE VENTING SECTION)

34Connect an accessory 24 VAC, 0.5 amp. maximum humidifier (ifused) to the ¼--in. male quick--connect HUM terminal andCOM--24V screw terminal on the c

Page 29 - AIR DUCTS

35Table 11 – Electrical DataUNIT SIZEV O LT S ---H E R T Z ---PHASEOPERATING VOLTAGERANGE*MAXIMUMUNITAMPSUNITAMPACITY#MINIMUMWIRESIZEAWGMAXIMUMWIRELEN

Page 30

36W/W1W2COMY/Y2RGA11401Fig. 34 -- Typical Two--Stage Field Wiring DiagramTEST / TWINHUMPLTSEC-2 SEC-1COM 24VACPL1W2 Y DHUM G COM

Page 31 - GAS PIPING

37Modulating and 2-Stage Furnace with Single-Speed Air ConditionerModulating and 2-Stage Furnace with Two-Speed Air ConditionerModulating and 2-Stage

Page 32 - ELECTRICAL CONNECTIONS

38NOTES FOR THERMOSTAT WIRING DIAGRAMS1. Heat pump MUST have a high pressure switch for dual fuel applications.2. Refer to outdoor equipment Installat

Page 33 - 24--V Wiring

39CARBON MONOXIDE POISONING HAZARDFailure to follow the steps outlined below for each applianceconnected to the venting system being placed into opera

Page 34 - Alternate Power Supplies

412. Maintain a 1--in. (25 mm) clearance from combustible ma-terials to supply air ductwork for a distance of 36 in. (914mm) horizontally from the fur

Page 35 - Table 11 – Electrical Data

40Table 12 – Vent Termination Kit for Direct Vent (2--pipe)SystemsDIRECT VENT(2 --- PIPE)TERMINATION KITTERMINATIONSYSTEMDIAMETER OFCOMBUSTION AIRAND

Page 36 - L1 BL-1 PR-1

41RECOMMENDED SUPPORT FORVENT TERMINATIONSIt is recommended that sidewall vent terminations in excess of24 inches (0.6 M) or rooftop terminations in e

Page 37

42Optional Combustion Air Inlet Moisture TrapAs an option to prevent moisture from trickling into the furnacevestibule, a trap can be installed in the

Page 38

43NOTE: Pipe length (ft. / M) specified for maximum pipe lengthslocated in unconditioned spaces cannot exceed total allowable pipelength as calculated

Page 39 - Venting Systems

4412. After pipes have been cut and pre--assembled, apply gener-ous layer of cement primer to pipe fitting socket and end ofpipe to insertion mark. Qu

Page 40 - Locating the Vent Termination

45Loosely assemble concentric vent/combustion air terminationcomponents together using instructions in kit.Slide assembled kit with rain shield REMOVE

Page 41 - Ventilated Combustion Air

46Table 13 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials (U.S.A. Installations)ASTM SPECIFICATION(MARKED ON MATERIAL)MATERIAL

Page 42 - Guidelines

47Table 14 – Maximum Allowable Exposed Vent Lengths Insulation Table -- Ft. / MTwo Stag eFurnace HighHeat InputWinter DesignTe m p ° F ( ° C )PipeLeng

Page 43 - Configure the Furnace

48NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.Use Table 16 - Deductions

Page 44 - Roof Terminations

49Venting System Length CalculationsThe Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting syst

Page 45

5NOT move or shuffle your feet, do not touch ungroundedobjects, etc.).4. If you touch ungrounded objects (and recharge your bodywith static electricit

Page 46

50NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.Use Table 16 - Deductions

Page 47

51Attach gaskets to vent pipe andcombustion air adapters.Vent Coupling and AdapterA11314Fig. 37 -- Vent Coupling and Adapter with GasketsPSC INDUCER A

Page 48

5212346755Rotate vent elbow torequired position.Any other unusedknockout may be usedfor combustion airconnection.&A1130912345675Rotate vent elbow

Page 49 - Example 2

53Attach vent pipe adapter with gasket to furnace casing.Align notches in rubber coupling over standoffs on adapter. Slide clamps over the coupling.S

Page 50

54HORIZONTAL LEFT - RIGHT VENT CONFIGURATION**Requires Accessory Internal Vent Kit See Product Data for Current Kit Number HORIZONTAL LEFT -VERTICAL V

Page 51 - Vent Coupling and Adapter

55HORIZONTAL RIGHT - VERTICAL VENT CONFIGURATIONHORIZONTAL RIGHT - LEFT VENT CONFIGURATION**Requires Internal Vent Kit See Product Data for Current Ki

Page 52

56VENT PIPE FLUSH SHOWING COUPLINGVENT PIPE FLUSH WITH ADAPTERVENT PIPE ADAPTER WITH GASKETINSTALLED ON FURNACE VENTPIPE IS CUT FLUSH WITH TOP OFADAPT

Page 53 - Downflow Vertical

57VVA12326NOTE: The following is based upon National codes for gas appliances and is provided as a reference.Refer to local codes which may supersede

Page 54 - RIGHT VENT CONFIGURATION*

58VVA12325NOTE: The following is based upon National codes for gas appliances and is provided as a reference.Refer to local codes which may supersede

Page 55

59AA090AVertical separation betweencombustion air and vent8 ¾ in. (222mm) or 3 in.(76mm)6¾ in. (172mm) or 2in. (51mm)Maintain 12 in. (305mm)min. Clear

Page 56 - VENT PIPE FLUSH WITH ADAPTER

66 15/16[176.1] 3[76.2]3[76.2]6 11/16[170.1]23 5/16[592.9]25 1/8[638.7]26 3/8[670.0] 26 11/16[678.1]21[534.0]26 5/16[668.8]17 5/16[439.2]16 9/16[420.9

Page 57

60OPTIONAL TERMINATIONBRACKET FOR 2-PIPETERMINATIONS12-IN. (305 MM)ABOVE ANTICIPATED SNOW LEVEL12-IN.(305 MM)12 IN. (305 MM) SEPARATIONBETWEEN BOTTOM

Page 58

613” (76 mm)12” (305 mm) Pipe hangarVentilated Combustion Airintake termination in crawlspaceVentilated CombustionAir intake pipeCRAWL SPACEATTIChighe

Page 59 - Roof Termination (Preferred)

62EXAMPLE FORUPFLOW INSTALLATIONS.MAY BE APPLIED TOOTHER CONFIGURATIONS.A12220Fig. 51 -- Sample Inlet Air Pipe Connection forPolypropylene Venting Sys

Page 60 - (ELBOW PARALLEL TO WALL)

63START--UP, ADJUSTMENT, AND SAFETYCHECKGeneral1. Furnace must have a 115-v power supply properly connec-ted and grounded.NOTE: Proper polarity must b

Page 61

64AdjustmentsFIRE HAZARDFailure to follow this warning could result in personalinjury, death and/or property damage.DO NOT bottom out gas valve regula

Page 62 - Polypropylene Venting Systems

65j. Reinstall manifold pressure tap plug from gas valve.k. Move setup switch SW--1 (LHT) to off position after com-pleting low--heat adjustment.l. Le

Page 63 - Purge Gas Lines

66ELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personal injuryor death.Disconnect 115vac electrical power before changing

Page 64 - Adjustments

67Checklist1. Put away tools and instruments. Clean up debris.2. Verify that the jumper is removed from the TEST/TWINterminal. Verify that there is no

Page 65 - Adjust Temperature Rise

68338314-201 Rev. DA11598Fig. 56 -- Service Label Information59TP5A

Page 66 - Check Safety Controls

69Table 18 – Altitude Derate Multiplier for U.S.A.*ALTITUDEPERCENTOFDERATEDERATEMULTIPLIERFACTOR*FT. M0–2000 0 --- 6 1 0 0 1.002001–3000 610---914 4 -

Page 67

7THE BLOWER IS LOCATEDTO THE RIGHT OF THEBURNER SECTION, ANDCONDITIONED AIR ISDISCHARGED TO THE LEFT.THE BLOWER ISLOCATED BELOW THEBURNER SECTION, AND

Page 68 - 338314-201 Rev. D

70Table 21 – Orifice Size and Manifold Pressure (in. w.c.) for Gas Input RateSAGLARUTANFOYTIVARGCIFICEPSSAG.GVAHEATVALUE0.580.600.620.64AT ALTITUDE Or

Page 69

71Table 21 -- Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate (Cont.)SAGLARUTANFOYTIVARGCIFICEPSSAG.GVAHEATVALUE0.580.600.620.64AT AL

Page 70 - TWO-STAGE FURNACE

72SERVICE AND MAINTENANCEPROCEDURESFIRE, INJURY OR DEATH HAZARDFailure to follow this warning could result in personalinjury, death and/or property da

Page 71

73Component Self--TestNOTE: The furnace control component test allows allcomponents to run for a short time; except the gas valve andhumidifier termin

Page 72 - PROCEDURES

74CUT HAZARDFailure to follow this caution may result in personal injury.Sheet metal parts may have sharp edges or burrs. Use careand wear appropriate

Page 73 - Care and Maintenance

75g. Clean wheel per instructions on degreaser cleaner. Do notget degreaser in motor.8. Reassemble motor and blower wheel by reversing items 7bthrough

Page 74

767. Install the remaining manifold mounting screws.8. Check the igniter alignment. See Fig. 57, 59 and 63.9. Attach the wires to the roll-out switche

Page 75

772. Install gasket on collector box3. Align the condensate trap with the drain opening on the col-lector box and secure the trap with the screw4. Att

Page 76 - Servicing Hot Surface Igniter

78WINTERIZATIONUNIT AND PROPERTY DAMAGE HAZARDFailure to follow this caution may result in unit component orproperty damage.If the furnace is installe

Page 77 - Cleaning Heat Exchangers

79SET SCREWMOTOR WHEEL HUBMOTOR SHAFT FLATSCREWMOTOR ARMGROMMETSCREW LOCATIONBLOWER HSG ASSYBRACKETBRACKETENGAGEMENTSEE DETAIL ACAPACITOROR POWER CHOK

Page 78 - WINTERIZATION

8LOCATIONPERSONAL INJURY AND/OR PROPERTYDAMAGE HAZARDImproper use or installation of this furnace may result inpremature furnace component failure. Th

Page 79 - Fig. 62 -- Blower Assembly

80FLAME SENSOR(BELOW BURNER)FLAME ROLLOUTSWITCHBRACKET, IGNITERIGNITERBURNER SUPT. ASSYBURNER ASSYA11403Fig. 63 -- Burner Assembly59TP5A

Page 80 - Fig. 63 -- Burner Assembly

81SEQUENCE OF OPERATIONNOTE: Furnace control must be grounded for proper operation orcontrol will lockout. Control is grounded through green wireconne

Page 81 - SEQUENCE OF OPERATION

82control CPU is factory--set for a 120--sec blower--OFFdelay.2. Two--Stage Thermostat and Two--Stage Heating SeeFig. 35 and 36 for thermostat connect

Page 82

83ated. If the DHUM input is low for more than 48 hours, thefurnace control reverts back to non--Thermidistat mode.The cooling operation described in

Page 83

84Is LED status light on? Is there 24V at SEC-1 and SEC-2? Is there 115V at L1 and L2? Replace furnace control. Is door switch closed? Replace tr

Page 84 - Troubleshooting Guide

85 11 NO PREVIOUS CODE – Stored codes are erased after 72 hours. Run system through a low-heat, high-heat, or cooling cycle to check system. 12 BLOW

Page 85 - Troubleshooting Guide (Cont)

86338314-2 Rev. EA12249Fig. 65 -- Wiring Diagram59TP5A

Page 86 - Fig. 65 -- Wiring Diagram

87PARTS REPLACEMENT INFORMATION GUIDECasing GroupBlower doorBottom plateControl doorDoor knob assemblyTop filler plateElectrical Group3--Amp fuseCircu

Page 87

88Copyright 2012 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 06/12Manufacturer reserves the right to c

Page 88 - Replaces: 59TP5A---05SI

9FIRE HAZARDFailure to follow this warning could result in personalinjury, death and/or property damage.Do not install the furnace on its back or hang

Commentaires sur ces manuels

Pas de commentaire