Table 11 — 30RB Electrical Data — Dual Point Units (cont)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Control power is derived from main power. No separate control power connection is
required.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is #4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
30RB
UNIT SIZE
UNIT VOLTAGE NO HYDRONIC PACKAGE 3 HP PUMP, 1750 RPM 5 HP PUMP, 1750 RPM
V-Hz (3 Ph)
Supplied
MCA MOCP ICF
Rec
Fuse
Size
MCA MOCP ICF
Rec
Fuse
Size
MCA MOCP ICF
Rec
Fuse
Size
Min Max
XL XL XL XL XL XL XL XL XL
315
A
208/230-60 187 253 519.8/243.8 600/300 962.0/635.0 600/300
380-60 342 418 274.9/124.8 300/150 528.3/336.8 300/150
460-60 414 506 230.8/106.3 250/125 438.8/280.4 250/125
575-60 518 633 187.3/ 85.2 200/110 354.9/227.4 200/100
B
208/230-60 187 253 519.8/243.8 600/300 962.0/635.0 600/300
460-60 414 506 230.8/106.3 250/125 438.8/280.4 250/125
575-60 518 633 187.3/ 85.2 200/110 354.9/227.4 200/100
380-60 342 418 274.9/124.8 300/150 528.3/336.8 300/150
330
A
208/230-60 187 253 519.8/306.2 600/400 962.0/748.4 600/350
380-60 342 418 274.9/160.2 300/200 528.3/413.6 300/175
460-60 414 506 230.8/135.2 250/175 438.8/343.2 250/150
575-60 518 633 187.3/110.2 200/125 354.9/277.8 200/125
B
208/230-60 187 253 519.8/243.8 600/300 962.0/635.0 600/300
380-60 342 418 274.9/124.8 300/150 528.3/336.8 300/150
460-60 414 506 230.8/106.3 250/125 438.8/280.4 250/125
575-60 518 633 187.3/ 85.2 200/110 354.9/227.4 200/100
345
A
208/230-60 187 253 519.8/306.2 600/400 962.0/748.4 600/350
380-60 342 418 274.9/160.2 300/200 528.3/413.6 300/175
460-60 414 506 230.8/135.2 250/175 438.8/343.2 250/150
575-60 518 633 187.3/110.2 200/125 354.9/277.8 200/125
B
208/230-60 187 253 519.8/306.2 600/400 962.0/748.4 600/350
380-60 342 418 274.9/160.2 300/200 528.3/413.6 300/175
460-60 414 506 230.8/135.2 250/175 438.8/343.2 250/150
575-60 518 633 187.3/110.2 200/125 354.9/277.8 200/125
360
A
208/230-60 187 253 543.7/400.4 600/450 985.9/842.6 600/450
380-60 342 418 288.0/209.5 300/250 541.3/462.9 300/225
460-60 414 506 241.6/176.8 250/200 449.6/384.8 250/200
575-60 518 633 195.9/144.1 225/175 363.5/311.7 225/175
B
208/230-60 187 253 519.8/306.2 600/400 962.0/748.4 600/350
380-60 342 418 274.9/160.2 300/200 528.3/413.6 300/175
460-60 414 506 230.8/135.2 250/175 438.8/343.2 250/150
575-60 518 633 187.3/110.2 200/125 354.9/277.8 200/125
390
A
208/230-60 187 253 543.7/400.4 600/450 985.9/842.6 600/450
380-60 342 418 288.0/209.5 300/250 541.3/462.9 300/225
460-60 414 506 241.6/176.8 250/200 449.6/384.8 250/200
575-60 518 633 195.9/144.1 225/175 363.5/311.7 225/175
B
208/230-60 187 253 543.7/400.4 600/450 985.9/842.6 600/450
380-60 342 418 288.0/209.5 300/250 541.3/462.9 300/225
460-60 414 506 241.6/176.8 250/200 449.6/384.8 250/200
575-60 518 633 195.9/144.1 225/175 363.5/311.7 225/175
AWG American Wire Gage
ICF Instantaneous Current Flow (Ckt1/Ckt2)
MCA Minimum Circuit Amps (Ckt1/Ckt2)
MOCP Maximum Overcurrent Protection (Ckt1/Ckt2)
XL Across-the-Line Start
208/230
460
575 v only