DUAL CHILLER CONTROL OPTION — If the Dual Chiller
algorithm is used and the machines are installed in parallel, an
additional chilled water sensor must be installed for each
chiller. For 30RB315-390 units, a factory-supplied thermistor
and well are shipped in the control box of each. Install the well
in the common leaving water header. See Fig 34. Do not relo-
cate the chillers leaving water thermistors. They must remain
in place for the unit to operate properly.
For the non-modular units, an accessory kit, Part No.
00EFN900044000A, is available. This kit includes all parts
necessary for dual chiller control.
The thermistor well is a
1
/
4
in. NPT fitting for securing the
well in the piping. The piping must be drilled and tapped for
the well. Select a location that will allow for removal of the
thermistor without any restrictions. See Fig. 55 and 56.
Once the well is inserted, install the thermistors. Insert the
thermistor into the well until the O-ring reaches the well body.
Use the nut on the thermistor to secure the thermistor in place.
Once the thermistor is in place, it is recommended that a
thermistor wire loop be made and secured with a wire tie to the
chilled water pipe. This will aid in thermistor retention in the
well. See Fig. 55. Attach connector (part no. HY06AM016) to
thermistor lead. Plug connector into MBB J6-CH-3.
For 30RB315-390 units, as well as all units using the dual
chiller algorithm, a Carrier Comfort Network
®
(CCN) bus
must be connected between the two modules. See the
Carrier Comfort Network Communication Bus Wiring section
on page 66 for additional information.
WIRE TIE
LOOP
THERMISTOR WIRE
AND SECURE
TO CHILLED WATER PIPE
INSERT THERMISTOR UNTIL
O-RING MEETS THE
THERMISTOR WELL BODY.
Fig. 55 — Dual Leaving Water Thermistor
(Part No. 30RB660036)
5/8 in. HEX
6" MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL
1.188 in.
2.315 in.
1/4-18 NPT
Fig. 56 — Dual Leaving Water Thermistor Well (Part No. 00PPG000008000A)