Carrier XRV Spécifications Page 52

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 190
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 51
52
If the entering chilled water control option (ECW CON-
TROL OPTION) is enabled (configured in TEMP_CTL
screen) and a common point sensor is desired (COMMON
SENSOR OPTION in LEADLAG screen selected as 1) then
the sensor is wired in Spare Temp #2 position on the CCM
(terminals J4-27 and J4-28).
When installing chillers in series, either a common point
sensor should be used (preferred), or the LEAVING CHILLED
WATER sensor of the upstream chiller must be moved into the
leaving chilled water pipe of the downstream chiller. In this
application the COMMON SENSOR OPTION should only be
enabled for the upstream chiller if that chiller is configured as
the Lead.
If ENTERING CHILLED WATER control is required on
chillers piped in series, either the common point return chilled
water sensor should be used (preferred), or the LEAVING
CHILLED WATER sensor of the downstream chiller must be
relocated to the LEAVING CHILLED WATER pipe of the
upstream chiller. In this application, the COMMON SENSOR
OPTION should only be enabled for the downstream chiller if
that chiller is configured as the lead. Note that ENTERING
CHILLED WATER control is not recommended for chillers
installed in series due to potential control stability problems.
To properly control the LEAVING CHILLED WATER
TEMPERATURE when chillers are piped in parallel, the water
flow through the shutdown chiller(s) should be isolated so that
no water bypass around the operating chiller occurs. However,
if water bypass around the operating chiller is unavoidable, a
common point sensor in the mixed LEAVING CHILLED
WATER piping should be provided and enabled for the Lead
chiller.
CHILLER COMMUNICATION WIRING Refer to the
chillers Installation Instructions, Carrier Comfort Network
®
Interface section for information on chiller communication
wiring.
LEAD/LAG OPERATION The PIC III not only has the
ability to operate 2 chillers in lead/lag, but it can also start a
designated standby chiller when either the lead or lag chiller is
faulted and capacity requirements are not met. The lead/lag
option only operates when the chillers are in CCN mode. If any
other chiller configured for lead/lag is set to the LOCAL or
OFF modes, it will be unavailable for lead/lag operation.
Lead/Lag Chiller Configuration and Operation
A chiller is designated the lead chiller when its LEADLAG:
CONFIGURATION value on the LEADLAG screen is set
to “1.”
A chiller is designated the lag chiller when its LEADLAG:
CONFIGURATION value is set to “2.”
A chiller is designated as a standby chiller when its LEAD-
LAG: CONFIGURATION value is set to “3.”
A value of “0” disables the lead/lag designation of a chiller.
This setting should also be used when “normal” operation
without regard to lead/lag rules is desired (in LOCAL or
CCN mode).
When configuring the LAG ADDRESS value on the
LEADLAG screen of chiller “A” enter the address of the
chiller on the system which will serve as lag when/if chiller
“A” is configured as lead. For example, if you are configuring
chiller A, enter the address for chiller B as the lag address. If
you are configuring chiller B, enter the address for chiller A as
the lag address. This makes it easier to rotate the lead and lag
chillers. Note that only the lag and standby chiller addresses
specified in the configured lead chiller's table are relevant at a
given time.
If the address assignments in the LAG ADDRESS
and STANDBY ADDRESS parameters conflict, the lead/lag
function is disabled and an alert (!) message displays. For
example, if the LAG ADDRESS matches the lead chiller’s
address, the lead/lag will be disabled and an alert (!) message
displayed. The lead/lag maintenance screen (LL_MAINT) dis-
plays the message ‘INVALID CONFIG’ in the LEADLAG:
CONFIGURATION and CURRENT MODE fields.
The lead chiller responds to normal start/stop controls such
as the occupancy schedule, a forced start or stop, and remote
start contact inputs. After completing start-up and ramp
loading, the PIC III evaluates the need for additional capacity.
If additional capacity is needed, the PIC III initiates the start-up
of the chiller configured at the LAG ADDRESS. If the lag
chiller is faulted (in alarm) or is in the OFF or LOCAL modes,
the chiller at the STANDBY ADDRESS (if configured) is
requested to start. After the second chiller is started and is
running, the lead chiller monitors conditions and evaluates
whether the capacity has been reduced enough for the lead
chiller to sustain the system alone. If the capacity is reduced
enough for the lead chiller to sustain the CONTROL POINT
temperatures alone, then the operating lag chiller is stopped.
If the lead chiller is stopped in CCN mode for any reason
other than an alarm (*) condition, the lag and standby chillers
are also stopped. If the configured lead chiller stops for an
alarm condition, the configured lag chiller takes the lead
chillers place as the lead chiller, and the standby chiller serves
as the lag chiller.
The PRESTART FAULT TIMER provides a timeout if
there is a prestart alert condition that prevents a chiller from
starting in a timely manner. If the configured lead chiller does
not complete its start-up before the PRESTART FAULT
TIMER (a user-configured value) elapses, then the lag chiller
starts, and the lead chiller shuts down. The lead chiller then
monitors the lag, acting as the lead, for a start request. The
PRESTART FAULT TIMER parameter is on the LEADLAG
screen, which is accessed from the EQUIPMENT SERVICE
table of the SERVICE menu.
If the lag chiller does not achieve start-up before the
PRESTART FAULT TIMER elapses, the lag chiller stops, and
the standby chiller is requested to start, if configured and ready.
Standby Chiller Configuration and Operation
— A chiller is
designated as a standby chiller when its LEADLAG: CONFIG-
URATION value on the LEADLAG screen is set to “3.” The
standby chiller can operate as a replacement for the lag chiller
only if one of the other two chillers is in an alarm (*) condition
(as shown on the ICVC panel). If both lead and lag chillers
are in an alarm (*) condition, the standby chiller defaults to
operate in CCN mode and will operate based on its configured
CCN occupancy schedule and remote contacts input.
Lag Chiller Start-Up Requirements
— Before the lag chiller
can be started, the following conditions must be met:
1. The lag chiller status indicates it is in CCN mode and is
not in an alarm condition. If the current lag chiller is in an
alarm condition, the standby chiller becomes the active
lag chiller, if it is configured and available.
2. Lead chiller ramp loading must be complete.
3. The configured LAG STOP TIMER entry has elapsed.
The LAG STOP TIMER starts when the lead chiller ramp
loading is completed or when a lag chiller stops. The
LAG STOP TIMER entry is on the LEADLAG screen.
4. Lead chiller ACTIVE DEMAND LIMIT (see the MAIN-
STAT screen) value must be greater than 95% of full load
amps.
5. Lead chilled water temperature must be greater than the
CONTROL POINT temperature (see the MAINSTAT
screen) plus 1/2 the CHILLED WATER DEADBAND
temperature (see the SETUP1 screen).
NOTE: The chilled water temperature sensor may be the
leaving chilled water sensor, the return water sensor, the
common supply water sensor, or the common return wa-
ter sensor, depending on which options are configured
and enabled.
Vue de la page 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 189 190

Commentaires sur ces manuels

Pas de commentaire