Carrier XRV Spécifications Page 48

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 190
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 47
48
Kilowatt Output — An output is available on the CCM
module [Terminal J8-1 (+) and J8-2 (–)] to represent the power
consumption of the chiller. The 4 to 20 mA signal generated by
the CCM module can be wired to the building automation or
energy management system to monitor the chiller’s energy
consumption. Output is 2 mA with the chiller off, and it
varies linearly from 4 mA (representing 0% rated kilowatt
consumption) to 20 mA (representing 100% RATED LINE
KILOWATTS). The rated peak kilowatt consumption is
configured by the user in the VFD_CONF display screen by
setting the RATED LINE KILOWATTS from the machine elec-
trical data nameplate.
Remote Reset of Alarms — A standard feature of the
PIC III controls is the ability to reset a chiller in a shutdown
alarm state from a remote location. If the condition which
caused the alarm has cleared the chiller, the chiller can be
placed back into a normal CCN operating mode when the
REMOTE RESET OPTION (ICVC_PWD menu) is set to
ENABLE. A variety of Carrier Comfort Network
®
software
systems including ComfortVIEW™ or Network Service
Tool™ can access the PIC III controls and reset the displayed
alarm. Third party software from building automation systems
(BAS) or energy management systems (EMS) can also access
the PIC III controls through a Carrier DataLINK™ module and
reset the fault displayed. Both methods would access the
ICVC_PWD screen and force the RESET ALARM? point to
YES to reset the fault condition. If the PIC III controls have de-
termined that it is safe to start the chiller, the CCN MODE?
point (ICVC_PWD screen) can be forced to YES to place the
chiller back into normal CCN operating mode. The only excep-
tions are the following alarms that cannot be reset from a
remote location: Alarm/Alert STATE 100, 200, 201, 204, 206,
217-220, 233, 234, 247, and 259. To view alarm codes, refer to
Troubleshooting Guide, Checking Display Messages, page 89.
After the alarm has been reset, the PIC III control will incre-
ment the STARTS IN 12 HOURS counter by one upon restart. If
the limit of 8 starts in a 12-hour period is reached (Prestart/
Alert state 100), this must be reset at the local chiller control
panel (ICVC).
Condenser Pump Control — The chiller will moni-
tor the CONDENSER PRESSURE and may turn on the con-
denser pump if the condenser pressure becomes too high while
the compressor is shut down. The COND PRESS OVERRIDE
parameter is used to determine this pressure point. COND
PRESS OVERRIDE is found in the SETUP1 display screen,
which is accessed from the EQUIPMENT SERVICE table.
The default value is 125 psig (862 kPa).
If the CONDENSER PRESSURE is greater than or equal to
the COND PRESS OVERRIDE, and the ENTERING CON-
DENSER WATER temperature is less than 115 F (46 C), the
condenser pump will energize to try to decrease the pressure
and Alert 151 will be generated. The pump will turn off when
the condenser pressure is 3.5 psi (24.1 kPa) less than the
pressure override and the CONDENSER REFRIG TEMP is
within 3 F (1.7 C) of the ENTERING CONDENSER WATER
temperature.
Condenser Freeze Prevention — This control algo-
rithm helps prevent condenser tube freeze-up by energizing the
condenser pump relay. The PIC III controls the pump and, by
starting it, helps to prevent the water in the condenser from
freezing. The PIC III can perform this function whenever the
chiller is not running except when it is either actively in pump-
down or in pumpdown/lockout with the freeze prevention
disabled.
When the chiller is off and CONDENSER REFRIG TEMP
is less than the CONDENSER FREEZE POINT, the
CONDENSER WATER PUMP will be energized (Alert State
154) However, if the chiller is in pump down, and when it
entered pump down mode, the CONDENSING REFRIG
TEMP was more than 5 F (2.7 C) above the CONDENSER
FREEZE POINT, the same low temperature condition will
generate Alarm State 244 and the CONDENSER WATER
PUMP will be energized. In either case, the fault state will clear
and the pump will turn off when the CONDENSER REFRIG
TEMP is more than 5 F (2.7 C) above the CONDENSER
FREEZE POINT and the entering condenser water temperature
is greater than the CONDENSER FREEZE POINT. If the chill-
er is in Recycle Shutdown Mode when the condition occurs,
the controls will transition to a non-recycle shutdown.
Evaporator Freeze Protection — When the EVAP-
ORATOR REFRIG TEMP is less than the EVAP REFRIG
TRIPPOINT plus the REFRIG OVERRIDE DELTA T (configu-
rable from 2 to 5 F or 1.1 to 2.8 C), Alert State 122 will be dis-
played, and a capacity override will occur. (See Table 7.)
When the unit is running or in recycle, if the EVAPORATOR
REFRIG TEMP is equal to or less than the EVAP REFRIG
TRIPPOINT (33 F or 0.6 C for water, configurable for brine),
Protective Limit Alarm State 232 will be displayed, the unit
will shut down, and the CHILLED WATER PUMP will remain
on. The alarm will be clearable when the leaving chilled water
temperature rises 5°F (2.8°C) above the CONTROL POINT.
When the unit is off, if the EVAPORATOR REFRIG TEMP
is less than the EVAP REFRIG TRIPPOINT plus 1° F (0.6 C),
Alarm State 243 will be generated and the CHILLED WATER
PUMP will be turned on. The alarm can be reset when the
EVAPORATOR REFRIG TEMP rises 5 F (2.8 C) above the
EVAP REFRIG TRIPPOINT.
Tower Fan Relay Low and High — Low condens-
er water temperature can cause the chiller to shut down when
refrigerant temperature is low. The tower fan relays, located in
the VFD, are controlled by the PIC III to energize and deener-
gize as the pressure differential between cooler and condenser
vessels changes. This prevents low condenser water tempera-
ture and maximizes chiller efficiency. The tower fan relay can
only accomplish this if the relay has been added to the cooling
tower temperature controller.
TOWER FAN RELAY LOW is turned on whenever the
condenser water pump is running, flow is verified, and the
difference between cooler and condenser pressure is more than
30 psid (207 kPad) for entering condenser water temperature
greater than 65 F (18.3 C).
TOWER FAN RELAY LOW is turned off when the condens-
er pump is off, flow is stopped, or the EVAP REFRIGERANT
TEMP is less than the EVAP REF OVERRIDE TEMP for
ENTERING CONDENSER WATER temperature less than
62 F (16.7 C), or the difference between the CONDENSER
PRESSURE and EVAPORATOR PRESSURE is less than
25 psid (172.4 kPad) for ENTERING CONDENSER water less
than 80 F (27 C).
TOWER FAN RELAY HIGH is turned on whenever
the condenser water pump is running, flow is verified and
the difference between EVAPORATOR PRESSURE and
CONDENSER PRESSURE is more than 35 psid (241.3 kPa)
for ENTERING COND WATER temperature greater than the
TOWER FAN HIGH SETPOINT (SETPOINT menu, default
75 F [23.9 C]).
The TOWER FAN RELAY HIGH is turned off when the
condenser pump is off, flow is stopped, or the EVAPORATOR
REFRIG TEMP is less than the EVAP REF OVERRIDE TEMP
and ENTERING CONDENSER WATER is less than 70 F
(21.1 C), or the difference between EVAPORATOR PRES-
SURE and CONDENSER PRESSURE is less than 28 Psid
(193 kPa), and ENTERING CONDENSER WATER tempera-
ture is less than TOWER FAN HIGH SETPOINT minus 3 F
(–16.1 C).
Vue de la page 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 189 190

Commentaires sur ces manuels

Pas de commentaire