DRIVE STATUS INDICATOR — The DRIVE status indica-
tor is on the right side of the Gateway. See Table 19.
Table 19 — DRIVE Status Indicator
MS STATUS INDICATOR — The MS status indicator is the
seco
nd LED from the right of the Gateway. See Table 20.
Table 20 — MS Status Indicator: State Definitions
NET A STATUS INDICATOR — The NET A status indica-
tor is the third LED from the right of the Gateway. See
T
able 21.
Table 21 — NET A Status Indicator:
St
ate Definitions
NET B STATUS INDICATOR — The NETB status indicator
is the left LED on
the Gateway. See Table 22.
Table 22 — NET B Status Indicator:
St
ate Definitions
Physical Data — Tables 23A-30 and Fig. 52-62 provide
additional information on component weights, compressor fits
and clearances, physical and electrical data, and wiring sche-
matics for the operators convenience during troubleshooting.
NOTE: This publication provides start-up and service informa-
tion for the LiquiFlo™ 2.0 (LF2) VFDs. For information on
S
td Tier VFDs, refer to associated Start-Up and Service
Instructions for the Rockwell PowerFlex 755 VFD or the
Eaton LCX 9000 VFD.
STATE CAUSE CORRECTIVE ACTION
Off
The Gateway is not
po
wered or is not con-
nected properly to the
dr
ive.
Securely connect the
Gate
way to the drive using
the DPI ribbon cable.
Apply power to the drive.
Flashing
Red
The Gateway is not
receiving a ping mes-
sage from the drive.
Verify that cables are
securely connected.
Cycle power to the drive.
Solid
Red
The drive has refused
an I/O connection from
the Gate
way.
IMPORTANT: Cycle power
after making the f
ollowing
correction:
Verify that all DPI cables
on the dr
ive are securely
connected and not dam-
aged. Replace cables if
necessar
y.
Orange
The Gateway is con-
nected to a product that
does not suppor
t Rock-
well Automation DPI
co
mmunications.
Check wires leading to the
A32 ter
minal block.
Check that A32 terminal
b
lock is fully engaged.
Flashing
Green
The Gateway is estab-
lishing an I/O connec-
tion to the drive or the
I/O has been disabled.
Normal behavior.
Solid
Green
The Gateway is prop-
erly connected and is
co
mmunicating with the
drive.
No action required.
DPI RIBBON
CABLE CONNECTOR
A32
TERMINAL BLOCK
NODE ADDRESS
TENS DIGIT = 0
(DO NOT
CHANGE)
DATA
RATE = PGM
(DO NOT
CHANGE)
NODE ADDRESS
ONES DIGIT = 1
(DO NOT CHANGE)
NOTE: If all status indicators are off, the Gateway is not receiving
power.
Fig. 51 — Gateway Status LEDs
NUMBER
STATUS
INDICATOR
DESCRIPTION
1 DRIVE DPI Connection Status
2 MS Module Status
3 NET A Serial Communication Status
4 NET B Serial Communication Traffic Status
a23-1618
STATE CAUSE CORRECTIVE ACTION
Off
The Gateway is not
po
wered.
Securely connect the
Gate
way to the drive using
the ribbon cable.
Apply power to the drive.
Flashing
Red
Recoverable Fault
Condition
Cycle power to the drive. If
cycling po
wer does not cor-
rect the problem, the firm-
ware may need to be flashed
into the modu
le.
Solid
Red
The module has failed
the hardw
are test.
Cycle power to the drive
Replace the Gateway
Flashing
Green
The Gateway is opera-
tional. No I/O data is
being tr
ansferred.
Normal behavior during SIO
configur
ation initialization
process.
Solid
Green
The Gateway is opera-
tional and transferring
I/O data.
No action required.
STATE CAUSE CORRECTIVE ACTION
Off
The module is not pow-
ered or is not properly
connected to the
network.
First incoming network
command not y
et
recognized.
Securely connect the
Gate
way ribbon cable to
the drive DPI board.
Attach the RS485 cable in
Gate
way to the connector.
Apply power to the drive.
Flashing
Red
Network has timed out. Cycle power to the drive.
Solid
Red
The Gateway has
detected an e
rror that
has made it incapable
of communication on
the network.
Check node address and
data r
ate switch positions on
the front of the Gateway.
Cycle power to the drive.
Flashing
Green
Online to network, but
not producing o
r con-
suming I/O information.
No action required. The LED
will turn solid green when
communication resumes.
Solid
Green
The module is properly
connected and comm
u-
nicating on the network.
No action required.
STATE CAUSE CORRECTIVE ACTION
Off
Gateway not receiving
data o
ver the network.
Check wires leading to
A32 ter
minal block.
Check that A32 terminal
b
lock is fully engaged.
Solid or
Blin
king
Green
Gateway is transmit-
ting data.
No action required.