Carrier XRV Spécifications Page 42

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 190
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 41
42
DIFFUSER CONTROL On all units with Frame 5 com-
pressors and those Frame 4 compressors with the variable (split
ring) diffuser option, the PIC III adjusts the diffuser actuator
position (DIFFUSER ACTUATOR on the COMPRESS screen)
based on the ACTUAL GUIDE VANE POSITION. This is
done in accordance with a compressor build-specific “schedule”
entered in the SETUP2 screen. The schedule consists of guide
vane and diffuser positions for three points (designated as the
25%, 50%, and 75% Load Points). In order for the schedule to
be valid, the guide vane values must be ascending and the dif-
fuser values must be descending for the three points. Diffuser
actuator output is controlled by a 4 to 20 mA output from CCM
terminals J8-3(+) and J8-4(–). Figure 22 shows the relationship
between diffuser-related parameters for a typical build.
Diffuser control output is enabled whenever the DIFFUSER
OPTION is enabled, whether the machine is running or not. As
shown in Fig. 22, 0% output corresponds to a full open diffuser.
The minimum closed position (25% Load Point value) will be
at less than 100% for most diffusers (depending upon the
model). This coordinated guide vane-diffuser operation may be
tested in the Control Test selection “IGV & SRD Actuator.”
Note that the diffuser actuator should NOT be forced to a great-
er percent than the configured 25% Load Point (maximum)
value. The diffuser opening can be incremented from fully open
to completely closed. A 0% setting is fully open; a 100% setting
is completely closed. To obtain the proper settings for Diffuser
Control, contact a Carrier Engineering representative.
DEMAND LIMITING The PIC III controls provide a
feature for limiting AVERAGE LINE CURRENT or LINE
KILOWATTS (demand) by limiting capacity via guide vane
control. The limit applied is called ACTIVE DEMAND
LIMIT, which is equal to a BASE DEMAND LIMIT value
(set in the SETPOINTS Screen, page 26, default value 100%),
or that determined by AUTO DEMAND LIMIT INPUT (an
optional 4 to 20 mA input, described below). ACTIVE
DEMAND LIMIT may also be forced to be different from
BASE DEMAND LIMIT by manually overriding the value
(forcing) from the MAINSTAT screen or writing a value via a
CCN network device, or controlled by another chiller in Lead
Lag operation (see page 51).
The demand limit may be based on either line current or
kW, as indicated by DEMAND LIMIT SOURCE in the
EQUIPMENT SERVICE/RAMP_DEM table. The default is 0,
for demand limiting based on AVERAGE LINE CURRENT
(percent of RATED LINE AMPS, as displayed on the default
screen). Setting DEMAND LIMIT SOURCE to 1 makes
demand limiting based on PERCENT LINE KILOWATTS
(displayed in the MAINSTAT screen). LINE KILOWATTS is
measured by the VFD, and the MOTOR RATED LOAD kW
value (100% rated kW) is set in the VFD_CONF table.
If the DEMAND LIMIT SOURCE (percent line current)
exceeds the ACTIVE DEMAND LIMIT by 5% or less, in-
creases in guide vane opening will be prevented. If the DE-
MAND LIMIT SOURCE (percent line current) exceeds the
ACTIVE DEMAND LIMIT by more than 5%, the guide vanes
will be forced to close. Also, as the DEMAND LIMIT
SOURCE approaches the ACTIVE DEMAND LIMIT from a
lower value, allowable capacity increases become increasingly
more limited, beginning when the DEMAND LIMIT
SOURCE is within the DEMAND LIMIT PROP BAND (con-
figurable in the RAMP_DEM table).
Demand Limit Control Option
— The demand limit control
option (20 mA DEMAND LIMIT OPT) is externally
controlled by a 4 to 20 mA signal from an energy management
system (EMS). The option is set up on the RAMP_DEM
screen. When enabled, 4 mA will set ACTIVE DEMAND
LIMIT to 100% of the DEMAND LIMIT SOURCE (regard-
less of the value of BASE DEMAND LIMIT), and 20 mA will
set ACTIVE DEMAND LIMIT to the value configured as
“20MA DEMAND LIMIT OPT” in the RAMP_DEM table.
Wire the auto demand limit input to terminals J5-1 (–) and
J5-2 (+) on the CCM. In order to use a 1 to 5 vdc input instead
of 4 to 20 mA, install a 25-ohm resistor in series with the + lead
at terminal J5-2.
A DEMAND KILOWATTS monitoring feature is also
available. This feature provides a display of average demand
(power) in kilowatts (in the POWER screen). This value is
continuously updated and averaged over the preceding time
interval specified as DEMAND WATTS INTERVAL in the SER-
VICE / EQUIPMENT SERVICE/RAMP_DEM screen.
CHILLER TIMERS AND STARTS COUNTER — The
PIC III maintains two run time clocks: COMPRESSOR
ONTIME and SERVICE ONTIME. COMPRESSOR
ONTIME indicates the total lifetime compressor run hours.
SERVICE ONTIME is a resettable timer that can be used to
indicate the hours since the last service visit or any other event.
A separate counter tallies compressor starts as TOTAL COM-
PRESSOR STARTS. All of these can be viewed on the
MAINSTAT screen on the ICVC. Both ontime counters roll
over to 0 at 500,000 hours. Manual changes to SERVICE
ONTIME from the ICVC are permitted at any time. If the con-
troller is replaced, one opportunity, before the first startup with
the new controller, is provided to set COMPRESSOR
ONTIME and TOTAL COMPRESSOR STARTS to the last
readings retained with the prior controller. The SERVICE
ONTIME timer can register up to 32,767 hours before it rolls
over to zero.
The chiller also maintains a start-to-start timer and a
stop-to-start timer. These timers limit how soon the chiller
can be started. START INHIBIT TIMER is displayed on
the MAINSTAT screen. See the Start-Up/Shutdown/Recycle
Sequence section, page 57, for more information on this topic.
OCCUPANCY SCHEDULE The chiller schedule, de-
scribed in the Time Schedule Operation section (page 25), deter-
mines when the chiller can run. Each schedule consists of from
1 to 8 occupied or unoccupied time periods, set by the operator.
The chiller can be started and run during an occupied time peri-
od (when OCCUPIED? is set to YES on the MAINSTAT dis-
play screen). It cannot be started or run during an unoccupied
time period (when OCCUPIED? is set to NO on the MAIN-
STAT display screen). These time periods can be set for each
day of the week and for holidays. The day begins with 0000
hours and ends with 2400 hours. The default setting for OCCU-
PIED? is YES, unless an unoccupied time period is in effect.
25 % Load Point
50 %0 %
78 %
50 % Load Point
rotating stall
less likely
surge more likely
75 % Load Point
surge less likely
2 mA
(0%)
4 mA
(0.2%)
Full
Open
Full
Closed
approx.
20 mA*
(100%)
Pinion Shaft Clockwise Rotation
DIFFUSER POSITION
Control Output
(Actuator Position)
GUIDE VANE OPENING (%)
* Diffuser full Span mA.
Fig. 22 — Diffuser Control
a19-1620
312
Vue de la page 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 189 190

Commentaires sur ces manuels

Pas de commentaire