124
Table 27A — 19XRV Waterbox Cover Weights — English (lb) (cont)
LEGEND
NOTE: Weight for NIH 2-pass cover, 150 psig, is included in the heat exchanger weights shown in Tables 23A and 23B.
FRAMES 4, 5, and 6 — COOLER
WATERBOX DESCRIPTION
Frame 4 Frame 5 Frame 6
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
NIH, 1 Pass Cover, 150 psig 148 185 168 229 187 223
NIH, 2 Pass Cover, 150 psig 202 256 224 298 257 330
NIH, 3 Pass Cover, 150 psig 473 489 629 655 817 843
NIH Plain End Cover, 150 psig 138 138 154 154 172 172
MWB End Cover, 150 psig 317 317 393 393 503 503
MWB Return Cover, 150 psig 138 138 154 154 172 172
NIH, 1 Pass Cover, 300 psig 593 668 764 839 959 1035
NIH, 2 Pass Cover, 300 psig 594 700 761 878 923 1074
NIH, 3 Pass Cover, 300 psig 621 656 795 838 980 1031
NIH/MWB End Cover, 300 psig 569 569 713 713 913 913
FRAMES 4, 5, and 6 — CONDENSER
WATERBOX DESCRIPTION
Frame 4 Frame 5 Frame 6
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
NIH, 1 Pass Cover, 150 psig 148 185 168 229 187 223
NIH, 2 Pass Cover, 150 psig 202 256 224 298 257 330
NIH, 3 Pass Cover, 150 psig 473 489 629 655 817 843
NIH Plain End Cover, 150 psig 138 138 154 154 172 172
MWB End Cover, 150 psig 317 317 393 393 503 503
MWB Return Cover, 150 psig 138 138 154 154 172 172
NIH, 1 Pass Cover, 300 psig 593 668 764 839 959 1035
NIH, 2 Pass Cover, 300 psig 594 700 761 878 923 1074
NIH, 3 Pass Cover, 300 psig 621 656 795 838 980 1031
NIH/MWB End Cover, 300 psig 569 569 713 713 913 913
NIH — Nozzle-in-Head
MWB — Marine Waterbox