T P --- P R H --- A , T P --- N R H --- APerformancetSeriesEdger Thermidistatt ControlInstallation InstructionsA07049 A07048Programmable Control Non--
10S Exposed to direct light or heat from a lamp, sun, fireplace, or othertemperature--radiating objects which could cause a false reading.S Close to o
11UNIT DAMAGE HAZARDFailure to follow this caution may result in equipment damageor improper operation.Improper wiring or installation may damage Ther
12ENVIRONMENTAL HAZARDFailure to follow this caution may result in environmentaldamage.Mercury is a hazardous waste. Federal regulations require thatM
13A07225Fig. 4 -- Press Tabs to Remove BackplateA07226Fig. 5 -- Take Apart
142. Route wires through large hole in mounting base. Level mounting baseagainst wall (for aesthetic value only—Display Module need not be lev-eled fo
156. Match and connect equipment wires to proper terminals of each connectorblock, being careful not to over tighten the screws. Correct polarity must
16A07166Fig. 8 -- Secure Wires to Terminal StripA07167Fig. 9 -- Connect Pigtail Wires to Display Module
17NOTE: The 2 --wire pigtail is not intended to support the weight of the UserInterface. Do not hang the User Interface from the Equipment Control Mod
1810. Find suitable indoor mounting location for Equipment Control Module,either near or on equipment. See Fig. 11.IMPORTANT NOTE: Equipment Control M
19A07227Fig. 12 -- StandoffNOTE: Standoffs are provided as an aid when installing Equipment ControlModule on inside equipment or a solid wall.12. Matc
2TABLE OF CONTENTSPAGESAFETY CONSIDERATIONS 2...INTRODUCTION 3...INSTALLAT
20A07218Fig. 13 -- Cover on Equipment Control Module14. Turn on power to equipment. On power up, all display segments willlight for 5 sec. For the nex
21Single--Piece InstallationThe following steps should be followed for the installation of the single-- piececonfiguration.1. Remove cover from Equipm
22A07219Fig. 14 -- Equipment Control Module5. Match and connect equipment wires to proper terminals of each connectorblock.6. Push any excess wire int
23A07220Fig. 15 -- Reattach Display Module9. Turn on power to equipment. On power up, all display segments willlight for 5 sec. For the next 5 sec a 2
24Set Thermidistat Control ConfigurationConfiguration options enable the installer to configure the Thermidistat Controlfor a particular installation.
25Option 11 — Adjustable Setpoint Deadband (not available onheat only and cool only systems)Option 12 — Smart Recovery (programmable models only)Optio
26Option 31* — Daylight Savings Time Configuration(programmable models only)Option 32 — Furnace Heat StagingOption 33 — Single or Two--Piece Installat
27saved at the time of selection and will be saved in the event of the 3 minutetime--out or when installer exits from configuration menu.Configuration
28Option 03 — Fahrenheit/CentigradeSelect between Fahrenheit (F) and Centigrade (C) operation. Factory default isFahrenheit (F).Option 04 — Fan (G) On
29time guard and cycle timers. The minimum On time is still controlled by theThermidistat Control.Default is OF (off).Option 08 — Auxiliary Heat Locko
3INTRODUCTIONCarrier’s 7--day, 5/2-- day, 1--day programmable and non --programmablePerformance Series Thermidistat Control is a wall--mounted, low--
30on heat pump operation. “O” is used to describe a heat pump system thatenergizes its reversing valve in cooling. “B” is used to describe a heat pump
31Option 14 — Humidity Display Offset AdjustThe percentage to be added to the displayed humidity to calibrate or deliberatelymiscalibrate the measured
32Option 17 — Time Between Equipment StagesThis selection is only available for heat pump systems. This determines theminimum number of minutes of equ
33the period or minutes and then use the UP/DOWN buttons to change to thedesired value.2 — The dry contact will operate as a DH relay. This relay is r
34Option 20 — Outdoor Air Temperatur e Offset AdjustmentThis selection allows the calibration, or deliberate miscalibration of the outdoorair temperat
351 — The user has access to modify Home, Sleep, Away, and UP/DOWNsetpoints.2 — The entire keypad is locked. When a button is pressed, the backlight w
36On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy allcooling demands.Default is OF (off).Option 23 — High Heat Latch Temperature
37four periods is more common for residential. This selection is not available ifOption 24 has been set to nP to configure the Thermidistat Control fo
386--48 — The number of months after which the UV Light reminder will bedisplayed, “CHECK UV LIGHT”.Default is OF (off).Option 29 — Humidifier Pad Rem
39Option 31 — Daylight Savings Time Configuration (programmable modelsonly)This selection allows the installer to set the Thermidistat Control to auto
4INSTALLATION CONSIDERATIONSPowerThis control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and Cterminals) of the low--voltage transforme
40Option 33 — Single or Two-- Piece InstallationThis configuration allows the Thermidistat Control to compensate for theamount of heat generated by th
41On -- The system has a variable speed blower.Factory default is OF (Off)Option 42 — Variable Speed Super DehumidificationThis option will only be av
42Option 44 — Super Comfort HeatThis option is only available on heat pump units HP (HP, H2, hh, and h2) whenOption 41 (Variable Speed Blower) is set
43Option 99 — Reset to Factory DefaultsUse this capability to reset the Thermidistat Control to “out of the box”conditions. BEWARE! All configuration
44Heat -- The first stage of heating will be energized for three minutes, then the firstand second stages (if a second stage exists) will turn on for
45pressed for fan to turn On and off. On some fan coils, fan continues to operatefor 90 sec after G signal is removed.Final SettingsBe sure to press D
46The FAN button may be used to select between AUTO (fan on only withequipment) and On (fan on continuously) fan modes. For further information ontemp
47Humidity Control FeaturesThe various humidity control features of the Thermidistat Control are explainedbelow. They are grouped into 2 sections, hum
48See Fig. 16 for outdoor temperature/indoor humidity relationship in autohumidify mode.3. Humidify OffThe humidify function can be turned off complet
49than setpoint, a dehumidification demand exists. The Thermidistat Controlresponds by activating the dry contact (when enabled in Option 19). It may
5A07052Fig. 1 -- PCB Breakout JumperModelsThere are programmable and non-- programmable models for all applications.They can be configured for AC or H
50A06599Fig. 16 -- Auto Humidity3. Dehumidify OffDehumidification can be turned off completely. This can be done withoutchanging existing setpoints.To
51system is in AUTO mode, dehumidify options are available if the last systemoperation was a call for cooling.To Select Dehumidification (non--program
52Carrier FK and FV series variable--speed fan coils, all variable--speed furnaces,and select single and multi--stage furnaces with the dehumidify con
53Vacation SetpointsA special set of temperature and humidity setpoints exist which are active invacation mode. They are adjustable by the homeowner,
54OPERAT IONAL INFORMATIONTimersFive-- Minute Compressor TimeguardThis timer prevents compressor from starting unless it has been off for at least 5mi
55signal shall be considered valid if the compressor output is energized and thedefrost signal has been active for less than 15 consecutive minutes. A
56Humidify and Dehumidify IndicatorsWhen the Display Module door is closed, the humidify icon will be displayedwhen humidification is active and the d
57power to energize the dehumidify terminal on the cooling equipment when thedry contact is closed.If it is desired to operate a ventilator or other d
58seconds. The control will operate from the temperature sensed by the workingsensor.E1 -- If the Display Module and the Equipment Control Module cann
59Table 4 – Equipment Configuration OutputsEQUIPCONFIGOPTION 01FACTORYCONFIGCOOLSTG 1COOLSTG 2HEATSTG 1HEATSTG 2HEATSTG 3HEATSTG 4EMHEATSTG 1EMHEATSTG
6ELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personal injuryor death.DO NOT connect furnace HUM terminal directly toTher
60Table 4 -- Equipment Configuration Outputs (cont)EQUIPCONFIGOPTION 01FACTORYCONFIGCOOLSTG 1COOLSTG 2HEATSTG 1HEATSTG 2HEATSTG 3HEATSTG 4EMHEATSTG 1E
61WIRING DIAGRAMSDisplay moduleDisplay modulewall mountEquipment Control Module Fan Coil Heat PumpV+ V+Vg Vg O OV+ RVS/Heat Stage 2 O/B W2 W3 W2Vg Hea
62Equipment Control Module Fan Coil Heat PumpOORVS Cooling O/B W2 W1 W1Heat Stage 3 W/W1 W2Heat/Cool Stage 1 Y1 / W2 Y1 Y1Heat/Cool Stage 2 Y/Y2 Y/Y2
63Typical Single-StageEquipment Control Module Fan Coil Heat PumpORVS Cooling O/B W2 E W2Heat Stage 2 W/W1 W2Heat Stage 3 Y1 / W2 W3Heat/Cool Stage 1
64Equipment Control ModuleRVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Low Y1 / W2Compressor High Y/Y2Fan G G24VAC Hot Heating Rh R24VAC H
65Equipment Control Module Fan Coil Air ConditionerORemove J2Jumper forheat staging Heat Stage 2 O/B W2 W2Heat Stage 1 W/W1 W1Cool Stage 1 Y1 / W2 Y1
66Typical Single-StageEquipment Control Module Fan Coil Air ConditionerOHeat Stage 2 O/B W2 EHeat Stage 1 W/W1 W3N/A Y1 / W2 W2Cool Stage 1 Y/Y2 Y YFa
67Equipment Control Module Fan CoilRVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Low Y1 / W2Compressor High Y/Y2Fan G G24VAC Hot Heating Rh
68Equipment Control Module Fan Coil Heat PumpOORVS Cooling O/B W2 W2Heat Stage 2 W/W1 W1Remove J2Jumper forheat stagingHeat Stage 3 Y1 / W2 W2Heat/Coo
69TypicalEquipment Control Module Fan CoilRVS/Heat Stage 2 O/B W2 EHeat Stage 1 W/W1 W2Compressor Low Y1 / W2Compressor High Y/Y2Fan G G24VAC Hot Heat
7Remote Indoor Temperature SensorA remote temperature sensor may be used with the programmable model, whereit is desirable to install the Thermidistat
70Equipment Control ModuleRVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1Compressor Low Y1 / W2Compressor High Y/Y2Fan G G24VAC Hot Heating Rh R24VAC Hot Coo
71Equipment Control Module Fan Coil Air ConditionerOHeat Stage 2 O/B W2 W2Remove J2Jumper forheat stagingHeat Stage 1 W/W1 W1N/A Y1 / W2 Y1Heat/Cool S
72Typical Single-StageEquipment Control Module Fan Coil Air ConditionerRVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1Compressor Low Y1 / W2Compressor High Y
73Variable Speed/Multi-StageEquipment Control Module Furnace Heat PumpORVS Cooling O/B W2 W2Heat Stage 3 (furnace)W/W1 W/W1 W2 *Heat/Cool Stage 1 Y1
74Single-Stage Single-StageEquipment Control Module Furnace Heat PumpORVS Cooling O/B W2Heat Stage 2 (furnace)W/W1 W W2 *N/A Y1 / W2Heat/Cool Stage 1
75Variable Speed/Multi-StageEquipment Control Module Furnace Air ConditionerHeat Stage 2 O/B W2 W2Heat Stage 1 W/W1 W1Cool Stage 1 Y1 / W2 Y1Cool Stag
76Single-Stage Single-StageEquipment Control Module Furnace Air ConditionerN/A O/B W2Heat Stage 1 W/W1 WN/A Y1 / W2Cool Stage 1 Y/Y2 Y YFan G G24VAC H
77Variable Speed/Multi-StageEquipment Control Module Furnace Heat PumpORVS Cooling O/B W2 W2 W2Heat Stage 3 (furnace)Y1 / W2 W1Heat Stage 2 (furnace)W
78Single-StageEquipment Control Module FurnaceN/A O/B W2Heat Stage 1 W/W1 WN/A Y1 / W2N/A Y/Y2Fan G G24VAC Hot Heating Rh R24VAC Hot Cooling RcDry Con
79Variable Speed/Multi-StageEquipment Control Module Furnace Air ConditionerHeat Stage 2 O/B W2 W2Heat Stage 1 W/W1 W1N/A Y1 / W2 Y1Cool Stage 1 Y/Y2
8INSTALLATIONCarton contains the following components. See Fig. 2 for TP--PRH --A or Fig. 3for TP--NRH--A.A07685Fig. 2 -- TP--PRH--A Carton Contents1.
80Single-StageEquipment Control ModuleFurnace Air ConditionerHeat Stage 2 O/B W2Heat Stage 1 W/W1 W1N/A Y1 / W2 Y1Cool Stage 1 Y/Y2 Y/Y2 YFan G G24VAC
81THERMIDISTAT CONTROL CONFIGURATIONRECORDInstaller_________________________Model Number______________________________Date_________________________A.
82E Configuration OptionsOption 01_____Equipment TypeOption 02_____Clean Filter Timer AdjustmentOption 03*_____Fahrenheit/Centigrade SelectionOption 0
83E Configuration Options (cont)Option 19_____Dry Contact (programmable models only)Option 20_____Outdoor Air Temperature Offset AdjustmentOption 21*_
84E Configuration Options (cont)Option 40_____Fan HumidityOption 41_____V ariable Speed BlowerOption 42_____V ariable Speed Super DehumidificationOpti
9A07686Fig. 3 -- TP--NRH--A Carton Contents1. Display Module2. Stand-- off for Equipment Control Module3. Outside Air Temperature Sensor, screws and p
Commentaires sur ces manuels