Carrier PERFORMANCETSERIES EDGER THERMIDISTATT CONTROL TP-NRH-A Manuel d'instructions

Naviguer en ligne ou télécharger Manuel d'instructions pour Thermostats Carrier PERFORMANCETSERIES EDGER THERMIDISTATT CONTROL TP-NRH-A. Carrier PERFORMANCETSERIES EDGER THERMIDISTATT CONTROL TP-NRH-A Instruction manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - Installation Instructions

T P --- P R H --- A , T P --- N R H --- APerformancetSeriesEdger Thermidistatt ControlInstallation InstructionsA07049 A07048Programmable Control Non--

Page 2 - SAFETY CONSIDERATIONS

10S Exposed to direct light or heat from a lamp, sun, fireplace, or othertemperature--radiating objects which could cause a false reading.S Close to o

Page 3 - INTRODUCTION

11UNIT DAMAGE HAZARDFailure to follow this caution may result in equipment damageor improper operation.Improper wiring or installation may damage Ther

Page 4 - INSTALLATION CONSIDERATIONS

12ENVIRONMENTAL HAZARDFailure to follow this caution may result in environmentaldamage.Mercury is a hazardous waste. Federal regulations require thatM

Page 5

13A07225Fig. 4 -- Press Tabs to Remove BackplateA07226Fig. 5 -- Take Apart

Page 6 - Outdoor Temperature Sensor

142. Route wires through large hole in mounting base. Level mounting baseagainst wall (for aesthetic value only—Display Module need not be lev-eled fo

Page 7

156. Match and connect equipment wires to proper terminals of each connectorblock, being careful not to over tighten the screws. Correct polarity must

Page 8 - INSTALLATION

16A07166Fig. 8 -- Secure Wires to Terminal StripA07167Fig. 9 -- Connect Pigtail Wires to Display Module

Page 9 - Thermidistat Control Location

17NOTE: The 2 --wire pigtail is not intended to support the weight of the UserInterface. Do not hang the User Interface from the Equipment Control Mod

Page 10 - Install Thermidistat Control

1810. Find suitable indoor mounting location for Equipment Control Module,either near or on equipment. See Fig. 11.IMPORTANT NOTE: Equipment Control M

Page 11

19A07227Fig. 12 -- StandoffNOTE: Standoffs are provided as an aid when installing Equipment ControlModule on inside equipment or a solid wall.12. Matc

Page 12 - Two--Piece Installation

2TABLE OF CONTENTSPAGESAFETY CONSIDERATIONS 2...INTRODUCTION 3...INSTALLAT

Page 13 - Fig. 5 -- Take Apart

20A07218Fig. 13 -- Cover on Equipment Control Module14. Turn on power to equipment. On power up, all display segments willlight for 5 sec. For the nex

Page 14

21Single--Piece InstallationThe following steps should be followed for the installation of the single-- piececonfiguration.1. Remove cover from Equipm

Page 15

22A07219Fig. 14 -- Equipment Control Module5. Match and connect equipment wires to proper terminals of each connectorblock.6. Push any excess wire int

Page 16

23A07220Fig. 15 -- Reattach Display Module9. Turn on power to equipment. On power up, all display segments willlight for 5 sec. For the next 5 sec a 2

Page 17

24Set Thermidistat Control ConfigurationConfiguration options enable the installer to configure the Thermidistat Controlfor a particular installation.

Page 18

25Option 11 — Adjustable Setpoint Deadband (not available onheat only and cool only systems)Option 12 — Smart Recovery (programmable models only)Optio

Page 19

26Option 31* — Daylight Savings Time Configuration(programmable models only)Option 32 — Furnace Heat StagingOption 33 — Single or Two--Piece Installat

Page 20

27saved at the time of selection and will be saved in the event of the 3 minutetime--out or when installer exits from configuration menu.Configuration

Page 21 - Single--Piece Installation

28Option 03 — Fahrenheit/CentigradeSelect between Fahrenheit (F) and Centigrade (C) operation. Factory default isFahrenheit (F).Option 04 — Fan (G) On

Page 22

29time guard and cycle timers. The minimum On time is still controlled by theThermidistat Control.Default is OF (off).Option 08 — Auxiliary Heat Locko

Page 23

3INTRODUCTIONCarrier’s 7--day, 5/2-- day, 1--day programmable and non --programmablePerformance Series Thermidistat Control is a wall--mounted, low--

Page 24

30on heat pump operation. “O” is used to describe a heat pump system thatenergizes its reversing valve in cooling. “B” is used to describe a heat pump

Page 25

31Option 14 — Humidity Display Offset AdjustThe percentage to be added to the displayed humidity to calibrate or deliberatelymiscalibrate the measured

Page 26

32Option 17 — Time Between Equipment StagesThis selection is only available for heat pump systems. This determines theminimum number of minutes of equ

Page 27

33the period or minutes and then use the UP/DOWN buttons to change to thedesired value.2 — The dry contact will operate as a DH relay. This relay is r

Page 28

34Option 20 — Outdoor Air Temperatur e Offset AdjustmentThis selection allows the calibration, or deliberate miscalibration of the outdoorair temperat

Page 29

351 — The user has access to modify Home, Sleep, Away, and UP/DOWNsetpoints.2 — The entire keypad is locked. When a button is pressed, the backlight w

Page 30

36On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy allcooling demands.Default is OF (off).Option 23 — High Heat Latch Temperature

Page 31

37four periods is more common for residential. This selection is not available ifOption 24 has been set to nP to configure the Thermidistat Control fo

Page 32

386--48 — The number of months after which the UV Light reminder will bedisplayed, “CHECK UV LIGHT”.Default is OF (off).Option 29 — Humidifier Pad Rem

Page 33

39Option 31 — Daylight Savings Time Configuration (programmable modelsonly)This selection allows the installer to set the Thermidistat Control to auto

Page 34 - Adjustment

4INSTALLATION CONSIDERATIONSPowerThis control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and Cterminals) of the low--voltage transforme

Page 35

40Option 33 — Single or Two-- Piece InstallationThis configuration allows the Thermidistat Control to compensate for theamount of heat generated by th

Page 36

41On -- The system has a variable speed blower.Factory default is OF (Off)Option 42 — Variable Speed Super DehumidificationThis option will only be av

Page 37

42Option 44 — Super Comfort HeatThis option is only available on heat pump units HP (HP, H2, hh, and h2) whenOption 41 (Variable Speed Blower) is set

Page 38

43Option 99 — Reset to Factory DefaultsUse this capability to reset the Thermidistat Control to “out of the box”conditions. BEWARE! All configuration

Page 39

44Heat -- The first stage of heating will be energized for three minutes, then the firstand second stages (if a second stage exists) will turn on for

Page 40

45pressed for fan to turn On and off. On some fan coils, fan continues to operatefor 90 sec after G signal is removed.Final SettingsBe sure to press D

Page 41

46The FAN button may be used to select between AUTO (fan on only withequipment) and On (fan on continuously) fan modes. For further information ontemp

Page 42

47Humidity Control FeaturesThe various humidity control features of the Thermidistat Control are explainedbelow. They are grouped into 2 sections, hum

Page 43 - SYSTEM START--UP AND CHECKOUT

48See Fig. 16 for outdoor temperature/indoor humidity relationship in autohumidify mode.3. Humidify OffThe humidify function can be turned off complet

Page 44

49than setpoint, a dehumidification demand exists. The Thermidistat Controlresponds by activating the dry contact (when enabled in Option 19). It may

Page 45 - Final Settings

5A07052Fig. 1 -- PCB Breakout JumperModelsThere are programmable and non-- programmable models for all applications.They can be configured for AC or H

Page 46

50A06599Fig. 16 -- Auto Humidity3. Dehumidify OffDehumidification can be turned off completely. This can be done withoutchanging existing setpoints.To

Page 47 - Humidification

51system is in AUTO mode, dehumidify options are available if the last systemoperation was a call for cooling.To Select Dehumidification (non--program

Page 48 - Dehumidification

52Carrier FK and FV series variable--speed fan coils, all variable--speed furnaces,and select single and multi--stage furnaces with the dehumidify con

Page 49

53Vacation SetpointsA special set of temperature and humidity setpoints exist which are active invacation mode. They are adjustable by the homeowner,

Page 50

54OPERAT IONAL INFORMATIONTimersFive-- Minute Compressor TimeguardThis timer prevents compressor from starting unless it has been off for at least 5mi

Page 51

55signal shall be considered valid if the compressor output is energized and thedefrost signal has been active for less than 15 consecutive minutes. A

Page 52

56Humidify and Dehumidify IndicatorsWhen the Display Module door is closed, the humidify icon will be displayedwhen humidification is active and the d

Page 53

57power to energize the dehumidify terminal on the cooling equipment when thedry contact is closed.If it is desired to operate a ventilator or other d

Page 54 - OPERAT IONAL INFORMATION

58seconds. The control will operate from the temperature sensed by the workingsensor.E1 -- If the Display Module and the Equipment Control Module cann

Page 55 - Equipment On Indicators

59Table 4 – Equipment Configuration OutputsEQUIPCONFIGOPTION 01FACTORYCONFIGCOOLSTG 1COOLSTG 2HEATSTG 1HEATSTG 2HEATSTG 3HEATSTG 4EMHEATSTG 1EMHEATSTG

Page 56

6ELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personal injuryor death.DO NOT connect furnace HUM terminal directly toTher

Page 57 - TROUBLESHOOTING

60Table 4 -- Equipment Configuration Outputs (cont)EQUIPCONFIGOPTION 01FACTORYCONFIGCOOLSTG 1COOLSTG 2HEATSTG 1HEATSTG 2HEATSTG 3HEATSTG 4EMHEATSTG 1E

Page 58

61WIRING DIAGRAMSDisplay moduleDisplay modulewall mountEquipment Control Module Fan Coil Heat PumpV+ V+Vg Vg O OV+ RVS/Heat Stage 2 O/B W2 W3 W2Vg Hea

Page 59

62Equipment Control Module Fan Coil Heat PumpOORVS Cooling O/B W2 W1 W1Heat Stage 3 W/W1 W2Heat/Cool Stage 1 Y1 / W2 Y1 Y1Heat/Cool Stage 2 Y/Y2 Y/Y2

Page 60

63Typical Single-StageEquipment Control Module Fan Coil Heat PumpORVS Cooling O/B W2 E W2Heat Stage 2 W/W1 W2Heat Stage 3 Y1 / W2 W3Heat/Cool Stage 1

Page 61 - WIRING DIAGRAMS

64Equipment Control ModuleRVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Low Y1 / W2Compressor High Y/Y2Fan G G24VAC Hot Heating Rh R24VAC H

Page 62

65Equipment Control Module Fan Coil Air ConditionerORemove J2Jumper forheat staging Heat Stage 2 O/B W2 W2Heat Stage 1 W/W1 W1Cool Stage 1 Y1 / W2 Y1

Page 63

66Typical Single-StageEquipment Control Module Fan Coil Air ConditionerOHeat Stage 2 O/B W2 EHeat Stage 1 W/W1 W3N/A Y1 / W2 W2Cool Stage 1 Y/Y2 Y YFa

Page 64

67Equipment Control Module Fan CoilRVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Low Y1 / W2Compressor High Y/Y2Fan G G24VAC Hot Heating Rh

Page 65

68Equipment Control Module Fan Coil Heat PumpOORVS Cooling O/B W2 W2Heat Stage 2 W/W1 W1Remove J2Jumper forheat stagingHeat Stage 3 Y1 / W2 W2Heat/Coo

Page 66

69TypicalEquipment Control Module Fan CoilRVS/Heat Stage 2 O/B W2 EHeat Stage 1 W/W1 W2Compressor Low Y1 / W2Compressor High Y/Y2Fan G G24VAC Hot Heat

Page 67

7Remote Indoor Temperature SensorA remote temperature sensor may be used with the programmable model, whereit is desirable to install the Thermidistat

Page 68

70Equipment Control ModuleRVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1Compressor Low Y1 / W2Compressor High Y/Y2Fan G G24VAC Hot Heating Rh R24VAC Hot Coo

Page 69

71Equipment Control Module Fan Coil Air ConditionerOHeat Stage 2 O/B W2 W2Remove J2Jumper forheat stagingHeat Stage 1 W/W1 W1N/A Y1 / W2 Y1Heat/Cool S

Page 70

72Typical Single-StageEquipment Control Module Fan Coil Air ConditionerRVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1Compressor Low Y1 / W2Compressor High Y

Page 71

73Variable Speed/Multi-StageEquipment Control Module Furnace Heat PumpORVS Cooling O/B W2 W2Heat Stage 3 (furnace)W/W1 W/W1 W2 *Heat/Cool Stage 1 Y1

Page 72

74Single-Stage Single-StageEquipment Control Module Furnace Heat PumpORVS Cooling O/B W2Heat Stage 2 (furnace)W/W1 W W2 *N/A Y1 / W2Heat/Cool Stage 1

Page 73 - (furnace)

75Variable Speed/Multi-StageEquipment Control Module Furnace Air ConditionerHeat Stage 2 O/B W2 W2Heat Stage 1 W/W1 W1Cool Stage 1 Y1 / W2 Y1Cool Stag

Page 74 - (Hybrid Heat)

76Single-Stage Single-StageEquipment Control Module Furnace Air ConditionerN/A O/B W2Heat Stage 1 W/W1 WN/A Y1 / W2Cool Stage 1 Y/Y2 Y YFan G G24VAC H

Page 75

77Variable Speed/Multi-StageEquipment Control Module Furnace Heat PumpORVS Cooling O/B W2 W2 W2Heat Stage 3 (furnace)Y1 / W2 W1Heat Stage 2 (furnace)W

Page 76

78Single-StageEquipment Control Module FurnaceN/A O/B W2Heat Stage 1 W/W1 WN/A Y1 / W2N/A Y/Y2Fan G G24VAC Hot Heating Rh R24VAC Hot Cooling RcDry Con

Page 77

79Variable Speed/Multi-StageEquipment Control Module Furnace Air ConditionerHeat Stage 2 O/B W2 W2Heat Stage 1 W/W1 W1N/A Y1 / W2 Y1Cool Stage 1 Y/Y2

Page 78

8INSTALLATIONCarton contains the following components. See Fig. 2 for TP--PRH --A or Fig. 3for TP--NRH--A.A07685Fig. 2 -- TP--PRH--A Carton Contents1.

Page 79 - Air Conditioner

80Single-StageEquipment Control ModuleFurnace Air ConditionerHeat Stage 2 O/B W2Heat Stage 1 W/W1 W1N/A Y1 / W2 Y1Cool Stage 1 Y/Y2 Y/Y2 YFan G G24VAC

Page 80 - Equipment Control Module

81THERMIDISTAT CONTROL CONFIGURATIONRECORDInstaller_________________________Model Number______________________________Date_________________________A.

Page 81

82E Configuration OptionsOption 01_____Equipment TypeOption 02_____Clean Filter Timer AdjustmentOption 03*_____Fahrenheit/Centigrade SelectionOption 0

Page 82

83E Configuration Options (cont)Option 19_____Dry Contact (programmable models only)Option 20_____Outdoor Air Temperature Offset AdjustmentOption 21*_

Page 83

84E Configuration Options (cont)Option 40_____Fan HumidityOption 41_____V ariable Speed BlowerOption 42_____V ariable Speed Super DehumidificationOpti

Page 84

9A07686Fig. 3 -- TP--NRH--A Carton Contents1. Display Module2. Stand-- off for Equipment Control Module3. Outside Air Temperature Sensor, screws and p

Commentaires sur ces manuels

Pas de commentaire