Fig. 17 -- Remote Room Sensor -- Parallel Wiring
This selection determines which sensor the control will use for measuring room air
temperature. Room air temperature can be sensed in one of three ways; the local
sensor (L) located on the Display Module, the remote room air sensor (r), or the
average of local and remote sensors (Lr). Settings are L, r, Lr.
Default is L.
Option 06 — Cooling Lockout Below 55_F/13_C
This selection disables cooling when outdoor temperature is below 55_F/13_C. It
requires an outdoor temperature sensor. Setting is not available if valid outdoor
sensor is not connected. Set to OF (off) to allow cooling below 55_F/13_C. Set to
On to prevent cooling below 55_F/13_C.
Factory default is OF (off).