Installation InstructionsPart No. 50DJ-902---801, 50DJ-902---811CONTENTSPageGENERAL ... 1INSTALLATION ...
NOTE: Dimensions shown in ( ) are in millimeters.UNITSIZEDIMENSIONSAB C D E Fin. mm in. mm in. mm in. mm in. mm in. mm034 and 038 10 254 59 1500 44 11
MOTORMASTERT I CONTROLLER MOUNTING TEMPLATENOTE: Dimensions in ( ) are in millimeters.CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE---------------------
Copyright 1999 Carrier CorporationManufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and w
074 AND 078 UNITS 088 AND 104 UNITSLEGENDOFM — Outdoor (Condenser) Fan MotorNOTE: All views are from the top of the unit.Fig. 1 — Location of OFM1034
5. Replace the existing motor mount spacer (see Fig. 2)with motor mount spacer provided in the accessorypackage.6. Install speed control motor in plac
12. Mount the Motormaster I controller on the partition nextto the capacitor. The controller must be mounted verti-cally with the leads coming out the
19. 460-volt units only — A stepdown transformer is sup-plied with the 50DJ-902---811 package and must be in-stalled as described below:Transformer is
Fig. 9 — MotormasterT I Control Sensor Location,Size 044 and 048 Units074 ONLY CONTROL BOXCIRCUIT NO. 1 COILSENSORLOCATION COILHEADER ENDFig. 10
CONTROL BOXCIRCUIT NO. 1 COILSENSORLOCATIONCOIL HEADER END COILHEADER ENDFig. 11 — MotormasterT I Control Sensor Location,Size 088 and 104 Units
SIZE 034, 038 SIZE 044, 048Fig. 13 — Circuit 1 Evaporator Suction Headers forFreeze Protection Thermostat Location, Size 034-048 UnitsFig. 14 — Circui
WIND BAFFLEFor low-ambient duty, a baffle should be installed in frontof the condenser coil to prevent cross currents from causingabnormal operation.