38AKS028-044
Air-Cooled Condensing Units
Installation, Start-Up and
Service Instructions
CONTENTS
SAFETY CONSIDERATIONS ……………...…….1
BEFORE INSTALLATION ………..……….… 1-6
Placing Unit ……………………………………….. 1
Mounting Unit ……………………………………. 6
Compressor Mounting ………………………….. 6
INSTALLATION ……………………………... 7-10
Refrigerant Piping Connections …………….…. 7
Liquid Solenoid Drop Refrigerant Control .....7
Filter Drier and Moisture indicator …………..… 7
Receiver …………………………………………. 7
Piping Procedure ……………………………….. 7
Power Supply …………………………………….8
Power Wiring ……………………………………..9
PRE-START-UP………………………...…… 10-12
System check ………………………………...…. 10
Leak Test and Dehydration ……………………. 10
START-UP …………………………….………12-15
38AKS Units …………………………………….. 13
Sequence of operation …………………………. 14
SERVICE ……………………………………...15-16
38AKS Access for Servicing …………………… 16
TROUBLESHOOTING ………………………… 16
START-UP CHECKLIST ……………… …....18-19
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning
equipment can be hazardous due to system pressures,
electrical components, and equipment location (roofs,
elevated structures, etc).
Only trained, qualified installers and service
mechanics should install, start-up, and service this
equipment.
Untrained personnel can perform basic maintenance
functions such as cleaning coils. All other operations
should be performed by trained service personnel.
When working on the equipment, observe precautions
in the literature and on tags, stickers, and labels
attached to the equipment.
Follow all safety codes. Wear safety glasses and work
when brazing. Use care in handling, rigging and
setting bulky equipment.
WARNING
Before installing or servicing system, always turn off
main power to system and install lockout tag on
disconnect. There may be more than one disconnect
switch. Electrical shock can cause personal injury.
BEFORE INSTALLATION
Placing Unit there must be 4 ft (1200 mm) for
service and for unrestricted airflow on all sides of unit,
and a minimum of 8 ft (2440 mm) clear air space
above unit. For multiple units, allow 8 ft (2440 mm)
separation between units for airflow and service. See
Tables 1A-4B for physical data for unit dimensions.
Vue de la page 0
1 2 3 4 5 6 ... 19 20

Résumé du contenu

Page 1 - Service Instructions

1 38AKS028-044 Air-Cooled Condensing Units Installation, Start-Up and Service Instructions CONTENTS SAFETY CONSIDERATIONS ……………...…….1 BEFORE I

Page 2

10 AB = 243v BC = 236v AC = 238v Average Voltage = 243 + 236 + 238 = 239 v 3 Determine maximum deviation from average voltage: (AB)243 – 239 = 4

Page 3

11 method (through liquid service valve) on the high side. See approximate refrigerant charge in Table 1A-1B. charge according to the valves in

Page 4

12 Fig. 10 – Charging Chart, 38AKS044, 50/60 Hz (Circuits No. 1 and 2) START-UP 38AKS Units – close field disconnect. Set thermosetting.

Page 5 - UNIT 38AKS

13 COMPLETE UNIT STOPPAGE Causes – Interruption of supplied power, compressor over temperature protection, open HPS, open OPS, or open LPS causes’

Page 6

14 Fig. 11 – Timer Sequence Chart NOTE: Actual start-up and all refrigerant charge modifications should be done only under supervision of a

Page 7

15 SERVICE (Fig. 12-14) CAUTION Turn off all power to unit before proceeding. 38AKS Units Access for servicing (See Fig.13) COMPRESSOR SECTION –

Page 8

16 When additional oil or a complete charge is required, use only Carrier-approved compressor oil: Petroleum Specialties Inc ………….……… Cryol 150 Te

Page 9

17 TROUBLESHOOTING – 38AKS UNITS SYMPTOM AND PROBABLE CAUSE PROBABLE REMEDY COMPRESSPR DOES NOT RUN 1. Control circuit breaker tripped. 1. Res

Page 10

18 START-UP CHECKLIST I. PRELIMINARY INFORMATION OUTDOOR: MODEL NO. ……………………………………………. SERIAL NO. ……………………………………… INDOOR: AIR HANDLER MANUFACTURE

Page 11

19 IS THE OIL LEVEL IN EACH COMPRESSOR CRANKCASE VISIBLE IN THE COMPRESSOR SIGHT GLASSES? (Y/N) ……………………….. CHECK VOLTAGE IMBALANCE

Page 12

2 Fig. 1 UNIT MAX SHIPPING WEIGHT CENTER OF GRAVITY B C lb kg In. mm In. mm 38AKS 028 1924 872 43.0 1091 28.0 711 034 2115 960 43.0 1092 28.0 711

Page 13

20 Sanaye Sarma Afarin Iran   NO.200, W. Khorramshahr (Apadana)Ave.,T

Page 16

5 Table 1A – physical Data – 38AKS028-044 Units – 50Hz, English UNIT 38AKS 028 034 044 NOMINAL CAPACITY (tons) 23.4 26.7 35.8 OPERATING WEIGHTS (lb)

Page 17 - PROBABLE REMEDY

6 Table 1B – physical data – 38AKS028-044 Units – 50Hz,SI UNIT 38AKS 028 034 044 NOMINAL CAPACITY (kw) 82.5 94.5 127.0 OPERATING WEIGHTS (kg) Al

Page 18 - START-UP CHECKLIST

7 Fig.5 – Compressor Mounting (Typical unit Shown) INSTALLATION Refrigerant Piping Connections – Line sizes depended on length of piping

Page 19

8 Fig.7 – Liquid Line Solenoid Valve, Filter Drier(s), and Sight Glass Locations Table 2 – Refrigerant Pipe Sizes, Single suction Risers – 38AK

Page 20

9 IMPORTANT: Operating unit on improper supply voltage, or with excessive phase imbalance, constitutes abuse and may affect Carrier w