Carrier 19XL Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Réfrigérateurs Carrier 19XL. Carrier 19XL User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 100
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Start-Up, Operation, and Maintenance Instructions
SAFETY CONSIDERATIONS
Centrifugal liquid chillers are designed to provide
safe and reliable service when operated within design
specifications. When operating this equipment, use good
judgment and safety precautions to avoid damage to
equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions
as well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in
accordance with the latest edition of ANSI/ASHRAE 15
(American National Standards Institute/American Society of Heat-
ing, Refrigeration, and Air Conditioning Engineers). The accumu-
lation of refrigerant in an enclosed space can displace oxygen and
cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/ASHRAE
15, especially for enclosed and low overhead spaces. Inhalation
of high concentrations of vapor is harmful and may cause heart
irregularities, unconsciousness, or death. Misuse can be fatal.
Vapor is heavier than air and reduces the amount of oxygen avail-
able for breathing. Product causes eye and skin irritation. Decom-
position products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any chiller.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel
until all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and
the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or
the entire assembly.
DO NOT work on high-voltage equipment unless you are a quali-
fied electrician.
DO NOT WORK ON electrical components, including control pan-
els, switches, starters, or oil heater until you are sure ALL POWER
IS OFF and no residual voltage can leak from capacitors or solid-
state components.
LOCK OPENAND TAG electrical circuits during servicing. IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized be-
fore resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
with soap and water. If liquid refrigerant enters the eyes, IMME-
DIATELY FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant
cylinder. Dangerous over pressure can result. When it is necessary
to heat refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLEGAL. When
cylinder is emptied, evacuate remaining gas pressure, loosen
the collar and unscrew and discard the valve stem. DO NOT
INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the chiller. The introduction of the wrong refrigerant can cause dam-
age or malfunction to this chiller.
Operation of this equipment with refrigerants other than those
cited herein should comply with ANSI/ASHRAE-15 (latest edi-
tion). Contact Carrier for further information on use of this chiller
with other refrigerants.
DO NOTATTEMPT TO REMOVE fittings, covers, etc., while chiller
is under pressure or while chiller is running. Be sure pressure is at
0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace
the device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to
act as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about
and release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if com-
ponents are light, use mechanical equipment when there is a risk of
slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN EN-
GAGE THE STARTER, TOWER FAN, OR PUMPS. Open the
disconnect ahead of the starter, tower fans, or pumps.
USE only repair or replacement parts that meet the code require-
ments of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process
control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has
been completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for cor-
rosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pres-
sure relief device to prevent a build-up of condensate or rain
water.
19XL
Hermetic Centrifugal Liquid Chillers
50/60 Hz
With HCFC-22 and HFC-134a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5a
PC 211 Catalog No. 531-971 Printed in U.S.A. Form 19XL-4SS Pg 1 7-96 Replaces: 19XL-3SS
Vue de la page 0
1 2 3 4 5 6 ... 99 100

Résumé du contenu

Page 1 - 50/60 Hz

Start-Up, Operation, and Maintenance InstructionsSAFETY CONSIDERATIONSCentrifugal liquid chillers are designed to providesafe and reliable service whe

Page 2 - CONTENTS

STARTING EQUIPMENTThe 19XL requires a motor starter to operate the centrif-ugal hermetic compressor motor, the oil pump, and variousauxiliary equipmen

Page 3 - CONTENTS (cont)

Copyright 1996 Carrier CorporationManufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and w

Page 4 - INTRODUCTION

• overtemperature• ground fault• current unbalance• run stateThese LEDs are further explained in the Check Starter andTroubleshooting Guide section, p

Page 5

Fig. 8 — 19XL Controls and Sensor LocationsFig. 9 — Control Sensors(Temperature)Fig. 10 — Control Sensors(Pressure Transducer, Typical)LEGEND1—LID2—PS

Page 6 - 19XL REAR VIEW

PROCESSOR MODULE (PSIO) — The PSIO is the brainof the PIC (Fig. 11). This module contains all the operatingsoftware needed to control the chiller. The

Page 7

LID Operation and Menus (Fig. 13-19)GENERAL• The LID display will automatically revert to the defaultscreen after 15 minutes if no softkey activity ta

Page 8 - Summary —

• Press EXIT to return to the previous screen level.• Press INCREASE or DECREASE to change the high-lighted point value.TO VIEW POINT STATUS (Fig. 15)

Page 9

3. Press RELEASE to remove the override and return thepoint to the PIC’s automatic control.Override Indication— An override value is indicated by‘‘SUP

Page 10 - STARTING EQUIPMENT

*Only available on PSIO Software Version 09 and higher.†Available on PSIO Software Versions 07 and 08.Fig. 17 — 19XL Menu Structure17

Page 11 - Definitions

Fig. 18 — 19XL Service Menu Structure18

Page 12

*Only available on PSIO Software Version 09 and higher.†Available on PSIO Software Versions 07 and 08.Fig. 18 — 19XL Service Menu Structure (cont)19

Page 13

CONTENTSPageSAFETY CONSIDERATIONS ...1INTRODUCTION ...4ABBREVIATIONS AND EXPLANATIONS ...4CHILLER FAMIL

Page 14

TO VIEW AND CHANGE SET POINTS (Fig. 19)1. To view the Set Point table, at the Menu screen pressSETPOINT.2. There are 4 set points on this screen: Base

Page 15

Table 2 — LID ScreensNOTES:1. Only 12 lines of information appear on the LID screen at any given time. Press NEXT or PREVIOUS to highlight a point or

Page 16

Table 2 — LID Screens (cont)EXAMPLE2—STATUS02 DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press STATUS.3. Scroll

Page 17 - Fig. 17 — 19XL Menu Structure

Table 2 — LID Screens (cont)EXAMPLE 5 — CONFIGURATION (CONFIG) DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press

Page 18

Table 2 — LID Screens (cont)EXAMPLE 7 — SERVICE1 DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press SERVICE.3. Sc

Page 19

Table 2 — LID Screens (cont)EXAMPLE 8 — SERVICE2 DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press SERVICE.3. Sc

Page 20

Table 2 — LID Screens (cont)EXAMPLE 10 — MAINTENANCE (MAINT01) DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press

Page 21 - Table 2 — LID Screens

Table 2 — LID Screens (cont)EXAMPLE 12 — MAINTENANCE (MAINT03) DISPLAY SCREENTo access this display from the LID default screen:1. Press MENU.2. Press

Page 22 - Table 2 — LID Screens (cont)

PIC System FunctionsNOTE: Throughout this manual, words printed in capital let-ters and italics represent values that may be viewed on theLID. See Tab

Page 23

Safety Controls — The PIC monitors all safety controlinputs, and if required, shuts down the chiller or limits theguide vanes to protect the chiller f

Page 24

CONTENTS (cont)PageCheck Optional Pumpout CompressorWater Piping ...47Check Relief Devices ...47Inspe

Page 25

Table 3 — Protective Safety Limits and Control SettingsMONITORED PARAMETER LIMIT APPLICABLE COMMENTSTEMPERATURE SENSORSOUT OF RANGE–40 to 245 F (–40 t

Page 26

Ramp Loading Control — The ramp loading controlslows down the rate at which the compressor loads up. Thiscontrol can prevent the compressor from loadi

Page 27

High Discharge Temperature Control — If thedischarge temperature increases above 160 F (71.1 C)(PSIO Software Version 09 and higher) or 180 F (82 C) (

Page 28 - PIC System Functions

Tower Fan Relay — Low condenser water tempera-ture can cause the chiller to shut down on low refrigeranttemperature. The tower fan relay, located in t

Page 29

The algorithm first determines if corrective action is nec-essary. This is done by checking 2 sets of operator con-figured data points, which are the MI

Page 30 - ADJUSTMENT

Operation Features:• 2 chiller lead/lag• addition of a third chiller for backup• manual rotation of lead chiller• load balancing if configured• stagger

Page 31

4. Lead chiller temperature pulldown rate of the CHILLEDWATER temperature is less than 0.5° F (0.27° C) perminute.5. The lag chiller status indicates

Page 32

START-UP/RECYCLE OPERATION — If the chiller is notrunning when ice build activates, then the PIC checks thefollowing parameters, based on the ICE BUIL

Page 33

ATTACHING TO OTHER CCN MODULES — If the chillerPSIO has been connected to a CCN Network or other PICcontrolled chillers through CCN wiring, the LID ca

Page 34 - Lead/Lag Control

6. Press NEXT to highlight the holiday table that youwish to view or change. Each table is one holiday pe-riod, starting on a specific date, and lastin

Page 35

CONTENTS (cont)PageWater Leaks ...64Water Treatment ...65Inspect the Starting Equipment ...

Page 36 - Ice Build Control

and go into a RECYCLE mode. If the water/brine tempera-ture is high enough, the start-up sequence continues on tocheck the guide vane position. If the

Page 37

Safety Shutdown — A safety shutdown is identical toa manual shutdown with the exception that the LID will dis-play the reason for the shutdown, the al

Page 38

Fig. 26 — 19XL Leak Test Procedures42

Page 39 - Local Start-Up —

procedures in the Transfer Refrigerant from StorageTank to Chiller section, Steps 1a-e, page 59.Never charge liquid refrigerant into the chiller ifthe

Page 40

Table 5A — HCFC-22 Pressure — Temperature (F)TEMPERATURE(F)PRESSURE (psi)Absolute Gage−50 11.67 6.154*−48 12.34 4.829*−46 13.00 3.445*−44 13.71 2.002*

Page 41

Table 5C — HFC-134a Pressure — Temperature (F)TEMPERATURE(F)PRESSURE(psig)0 6.502 7.524 8.606 9.668 10.7910 11.9612 13.1714 14.4216 15.7218 17.0620 18

Page 42

Fig. 27 — Typical Optional Pumpout System Piping Schematicwith Storage TankFig. 28 — Typical Optional Pumpout System Piping Schematicwithout Storage T

Page 43

Chiller Dehydration — Dehydration is recommendedif the chiller has been open for a considerable period of time,if the chiller is known to contain mois

Page 44

6. Be sure that fused disconnects or circuit breakers havebeen supplied for the oil pump, power panel, andpumpout unit.7. Check that all electrical eq

Page 45

3. Some dashpot-type magnetic overload relays must be filledwith oil on the jobsite. If the starter is equipped with de-vices of this type, remove the

Page 46

CHILLER FAMILIARIZATION(Fig. 1, 2A, and 2B)Chiller Information Plate —The information plateis located on the right side of the chiller control centerp

Page 47

Oil Charge — The 19XL compressor holds approxi-mately 8 gal. (30 L) of oil. The chiller will be shipped withoil in the compressor. When the sump is fu

Page 48 - Check Starter

MODIFY CONTROLLER IDENTIFICATION IF NECES-SARY — The controller identification screen is used to changethe PSIO module address. Change this address for

Page 49

Table 6 — Amps Correction Factorsfor 19XL MotorsVOLT/HzMOTOR CODECB CC CD CE CL CM CN CP CQ CR200/60 4536323222208/60 5558424222220/60 3422231111230/6

Page 50

Loosen the compressor holddown bolts to allow free springtravel. Open the compressor suction and discharge servicevalves. Check that oil is visible in

Page 51

19XL CHILLER EQUALIZATION WITH PUMPOUTUNIT — The following procedure describes how to equal-ize refrigerant pressure on an isolated 19XL chiller using

Page 52 - Compressor —

INITIAL START-UPPreparation —Before starting the chiller, check that the:1. Power is on to the main starter, oil pump relay, tower fanstarter, oil hea

Page 53

2. Observe that all 6-gate LEDs are lit on the starter SCRcontrol board.3. The factory setting should bring the motor to full voltagein 15 to 30 secon

Page 54

2. The bearing oil temperature accessed on the Status01 tableshould be 120 to 165 F (49 to 74 C). If the bearingtemperature reads more than 180 F (83

Page 55 - Check Rotation

DateREFRIGERATION LOG CARRIER 19XT HERMETIC CENTRIFUGAL REFRIGERATION MACHINEPlantCHILLER MODEL NO. CHILLER SERIAL NO. REFRIGERANT TYPEDATE COOLER CON

Page 56

PUMPOUT AND REFRIGERANT TRANSFERPROCEDURESPreparation —The 19XL may come equipped withan optional storage tank or pumpout system, or a pump-out compre

Page 57

19XL FRONT VIEW19XL REAR VIEWFig. 2A — Typical 19XL Components — Design ILEGEND1—Unit-Mounted Starter2—Refrigerant Filter Drier3—Rigging Guide Bolt4—R

Page 58 - Fig. 33 — Refrigeration Log

2. Transfer remaining refrigerant.a. Close valve 5 and open valve 4.VALVE 1a1b23456781011121314CONDITION CCCb. Turn off the chiller water pumps throug

Page 59 - PROCEDURES

TRANSFER ALL REFRIGERANT TO CHILLERCOOLER/COMPRESSOR VESSEL1. Push refrigerant into the chiller cooler vessel.a. Valve positions:VALVE 1a 1b 2 3 4 5 8

Page 60

HCFC-22 and HFC-134a should not be mixed withair or oxygen and pressurized for leak testing. In gen-eral, neither refrigerant should not be allowed to

Page 61

SCHEDULED MAINTENANCEEstablish a regular maintenance schedule based on theactual chiller requirements such as chiller load, run hours,and water qualit

Page 62

Inspect Refrigerant Float System — Performinspection every 5 years or when the condenser is openedfor service. Transfer the refrigerant into the coole

Page 63

Water Treatment — Untreated or improperly treated wa-ter may result in corrosion, scaling, erosion, or algae. Theservices of a qualified water treatmen

Page 64

TROUBLESHOOTING GUIDEOverview —The PIC has many features to aid theoperator and the technician in troubleshooting a 19XLchiller.• By using the LID dis

Page 65

If the transducer value is not within the calibration range,the transducer will return to the original reading. Ifthe LID pressure value is within the

Page 66 - Overview —

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting GuidesA. SHUTDOWN WITH ON/OFF/RESET-OFFPRIMARY MESSAG

Page 67

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)C. IN RECYCLE SHUTDOWNPRIMARY MESSAGE SE

Page 68 - B. TIMING OUT OR TIMED OUT

45678910111213141516171819202122232419XL FRONT VIEW31302928272625414039383736 35 34 3332154219XL REAR VIEWFig. 2B — Typical 19XL Components — Design I

Page 69 - E. NORMAL OR AUTO.-RESTART

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)F. START-UP FAILURES: This is an alarm c

Page 70

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)G. COMPRESSOR JUMPSTART AND REFRIGERANT

Page 71

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)I. NORMAL RUN OVERRIDES ACTIVE (ALERTS)P

Page 72

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)K. CHILLER PROTECT LIMIT FAULTSExcessive

Page 73

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)L. CHILLER ALERTSPRIMARY MESSAGE SECONDA

Page 74 - L. CHILLER ALERTS

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messageswith Troubleshooting Guides (cont)N. OTHER PROBLEMS/MALFUNCTIONSDESCRIPTIO

Page 75

Table 10A — Thermistor Temperature (F) vs Resistance/Voltage DropTEMPERATURE VOLTAGE RESISTANCE(F) DROP (V) (Ohms)−25 4.821 98,010−24 4.818 94,707−23

Page 76

Table 10B — Thermistor Temperature (C) vs Resistance/Voltage DropTEMPERATURE VOLTAGE RESISTANCE(C) DROP (V) (Ohms)−40 4.896 168 230−39 4.889 157 440−3

Page 77

Control ModulesTurn controller power off before servicing controls. Thisensures safety and prevents damage to controller.The Processor module (PSIO),

Page 78 - Notes on Module Operation

Processor Module (PSIO) (Fig. 41)INPUTS — Each input channel has 3 terminals; only 2 ofthe terminals are used.Application of chiller determines whicht

Page 79

Refrigerant that flows to the oil cooling system is reg-ulated by a thermostatic expansion valve. There is alwaysa minimum flow bypassing the TXV, which

Page 80

Terminal block connections are provided on the optionsmodules. All sensor inputs are field wired and installed.Options module number 1 can be factory o

Page 81

Solid-State Starters — Troubleshooting guides and in-formation pertaining to the operation of the solid-state startermay be found in Fig. 44-46 and Ta

Page 82

LEGENDSCR — Silicon Control Rectifier*See test procedure described in Testing SCRs in Solid-State Starters section on page 81.Fig. 45 — Solid-State Sta

Page 83

Fig. 46 — Solid-State Starter, Starter Fault (Motor Will Not Start)Troubleshooting Guide (Typical)83

Page 84

Table 11 — Benshaw, Inc. Solid-State Starter Troubleshooting GuidePROBLEM PROBABLE CAUSES AREA OF CORRECTIONAK board phase correct noton.1. L1 and L3

Page 85 - CONDENSER

Physical Data — Tables 12-17 and Fig. 47-51 pro-vide additional information regarding compressor fits andclearances, physical and electrical data, and

Page 86 - ENGLISH (lb)

Table 14 — Waterbox Cover Weights*ENGLISH (lb)HEATEXCHANGERWATERBOXDESCRIPTIONFRAME 4,STANDARDNOZZLESFRAME 4,FLANGEDFRAME 5,STANDARDNOZZLESFRAME 5,FLA

Page 87 - Electrical Data

Table 15 — Compressor/Motor WeightsMOTORSIZEENGLISH SICompressorWeight(lb)Stator Weight(lb)Rotor Weight(lb)End BellCover(lb)CompressorWeight(kg)Stator

Page 88

NOTES:1. Dimensions are in inches with rotor in the thrust position.2. All clearances listed are new chiller tolerances.3. All radial clearances are d

Page 89 - COMPRESSOR ASSEMBLY TORQUES

COMPRESSOR ASSEMBLY TORQUESITEM DESCRIPTIONTORQUEft-lb N•m1* Oil Heater Grommet Nut 10 142 Impeller Retaining Bolt 44-46 60-623 Bull Gear Retaining Bo

Page 90

journal bearings within the bearing housing. The oil then drainsinto the oil reservoir at the base of the compressor. The PIC(Product Integrated Contr

Page 91

LEGENDBRG — BearingC—ContactCB — Circuit BreakerCLR — ClearCOM — CommonCOMM — Communication ConnectorEXT — ExternalG.V. — Guide VaneHGBP — Hot Gas Byp

Page 92

Fig. 48 — Electronic PIC Controls Wiring Schematic(For 19XL with No Backlight or with Fluorescent Backlight) (cont)91

Page 93

LEGENDBRG — BearingC—ContactCB — Circuit BreakerCLR — ClearCOM — CommonCOMM — Communication ConnectorEXT — ExternalG.V. — Guide VaneHGBP — Hot Gas Byp

Page 94

Fig. 49 — Electronic PIC Controls Wiring Schematic(For 19XL with Halogen Backlight) (cont)93

Page 95

LEGEND1M — Main Starter ContactorC—ContactorCB — Circuit BoardCR — Control RelayCOMM — Communications ConnectorJ—ConnectorN.C. — Normally ClosedN.O. —

Page 96

Fig. 50 — Chiller Power Panel, Starter Assembly,and Motor Wiring Schematic (cont)95

Page 97

Fig. 51 — Typical Wye-Delta Unit Mounted Starter Wiring SchematicLEGEND1M, 2M — Main Compressor ContactorsCB — Circuit BreakerCR — Control RelayCT — C

Page 98

NOTES:1. Contactors 2M and S are mechanically interlocked.2. Transition resistor fault protector (TRFP) is preset to trip if transition contactor(1A)

Page 99 - INDEX (cont)

INDEXAbbreviations and Explanations, 4Adding Refrigerant, 61Adjusting the Refrigerant Charge, 61After Extended Shutdown, 57After Limited Shutdown, 57A

Page 100

INDEX (cont)Storage Vessel, 5Summary (Lubrication Cycle), 8Surge Prevention Algorithm, 33Surge Protection, 34System Components, 5Temperature Sensors (

Commentaires sur ces manuels

dd 07 Apr 2025 | 00:25:23

dddd