Number OneAirconditioningMakerCarrier Parkwav • Syracuse NY 13221Reciprocating Liquid Chillers (60 Hz)All 208/230-volt units have extended-voltage com
Check Unit Safety DevicesSAFETY THERMOSTAT (Fig. 6)The low water temperature cutout (LWTC) protects the unit against freeze-up due to operating
The return water temperature at which the last step of capacity unloads is indicated by the leaving water temperature design set point
6. ANY SAFETY DEVICE TRIPS.If device is low-pressure switch, reset is automatic and unit restart is thru normal timer cycle. In the case of low, o
Tube information:in.(mm)Tube sheet hole diameter... 0.631(16.03)Tube OD... 0.625(15.87)Tube ID after rolling...
TROUBLESHOOTING GUIDESYMPTOMS 1PROBABLE CAUSEREMEDYCompressor does not run !Power line openReset circuit breaker.!Control circuit breaker trippedCheck
TROUBLESHOOTING GUIDE (cont)SYMPTOM 1 PROBABLE CAUSEREMEDYSystem noises | Piping vibrationSupport piping as required.Check for loose pipe connectors.E
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Book
Table 1 — Weight Distribution (ib)UM!T 30( )--APPROXOPERWTHKHLHK HL A I B CD A BCD01516371016142j 201 755539266 26624224202017871136182| 240790 575 29
UNIT AND COMPRESSORTable 2 — Physical DataUNIT 30HK.HL015020 025 030APPROXIMATEHK163717871980 1985OPERATING WT (lb)HL10161136 13101334REFRIGERANT(R-22
3. A specific head pressure must be maintained.Set water regulating valve to maintain design head pressure. Do not adjust to compensate
Refer to Tables 4 and 5 for electrical data on individual compressors and complete units. Compressor usage is given in Tables 2 and 5.
Table 5 — Electrical Data; 3-Phase, 60-HertzCOMPLETE UNITVOLTSNameplate 208/230*460575COMPRESSOR 06E USAGESSupply Ränget 187-253414-508518 632UNIT 30M
The ЗОН К units are shipped with a full refrigerant charge (see Table 2). However, if it is necessary to add refrigerant, operate the unit fo
6. Check leaving chilled water temperature to see that it remains well above freezing.7. Recheck compressor oil level. See Check Oil Charge.Check Re
The electric heater is wired into the 115-volt control circuit thru normally closed contacts of control relay in such a way that it is en