STANDBY OPERATION GUIDELINES
For safe, reliable operation in Standby mode, it is important to
follow a few guidelines:
D Never plug the unit in to the power source with the main switch
in the RUN (I) position. The main switch should always be in the
STOP(O) position when connecting the unit to the power
source.
D The circuit breaker and extension cable used for Standby
operation should conform to the following:
Operating Voltage
FLA
Rating
Circuit
Breaker
Capacity
Cable
Requirement
208/230 V
60 hz
3 phase
15.8 A 50 A
8/3 with ground
(upto50ft)
460 V 60 hz
3 phase
13.2 A 30 A
10/3 with ground
(upto75ft)
D When multiple units are in use, each unit must be operated
on its own electrical circuit. You should never operate more
than one unit on a circuit breaker.
Important note: This information is provided as a guideline only.
When preparing a circuit for operation of the refrigeration unit, a
licensed electrician should be contracted. A licensed electrician is
familiar with all local ordinances and special requirements for your
area and can ensure that the circuits are properly designed and
installed, and that connections are correct.