30RY 017-080 "B"
Ductable Liquid Chillers with
Integrated Hydronic Module
Nominal cooling capacity 18-79 kW
50 Hz
Installation, operation and maintenance instructions
AQUASNAP
For the operation of the control please refer to
the Pro-Dialog
Control manual for the
30RA/RH - 30RY/RYH "B" series
Carrier is participating in the
Eurovent Certification Programme.
Products are as listed in the
Eurovent Directory of Certified
Products.
Vue de la page 0
1 2 3 4 5 6 ... 31 32

Résumé du contenu

Page 1 - Integrated Hydronic Module

30RY 017-080 "B"Ductable Liquid Chillers withIntegrated Hydronic ModuleNominal cooling capacity 18-79 kW50 HzInstallation, operation and mai

Page 2

104 - PHYSICAL DATA30RY 017 021 026 033 040 050 060 070 080Nominal cooling capacity* kW 18.6 23.1 25.8 31.7 39.4 50.0 58.0 67.0 79.0Operating weight k

Page 3

11Compressor usage and electrical dataCOMPRESSOR 30RYReference code I Nom I Max LRA* Circuit 017 021 026 033 040 050 060 070 080DQ 12 CA 001EE 14.0 19

Page 4

126 - APPLICATION DATA6.1 - Unit operating rangeEvaporator Minimum °C Maximum °CWater entering temp. (at start-up) 7.8 * 30Water leaving temp. (in ope

Page 5

13Legend1 30RY 0172 30RY 0213 30RY 0264 30RY 0335 30RY 0406 30RY 0507 30RY 0608 30RY 0709 30RY 080110100100020001101234567896.7 - Pressure drop in the

Page 6

14347673333L1L3L2L1SAAYX1PE347PE1BBYX 3333685.595L1L2L3S30RY 040-080Control box7 - ELECTRICAL CONNECTION30RY 017-033Control boxLegend1 Main disconnect

Page 7

157.1 - Power supplyThe power supply must conform to the specification on thechiller name plate. The supply voltage must be within the rangespecified

Page 8

169 - WATER CONNECTIONSFor size and position of the unit water inlet and outlet connec-tions refer to the certified dimensional drawings supplied with

Page 9 - 3 - DIMENSIONS/CLEARANCES

179.2 - Hydronic connectionsThe diagram on the next page shows a typical hydronicinstallation.When charging the water circuit use air vents to evacuat

Page 10 - 5 - ELECTRICAL DATA

18Installation components12 Air vent13 Thermometer sleeve14 Flexible connection15 Check valve16 System water drain plug (on connection pipe supplied i

Page 11

19OFFOFFOOFLegendO OpenF ClosedWater inletWater outletPressure gaugeNOTE: Applies to units 040 to 080If the pressure drop has increased, this indicate

Page 12 - Entering air temperature

2The drawings in this document are for illustrative purposes only and is not part of any offer for sale or contract.CONTENTS1 - INTRODUCTION ...

Page 13 - Pressure drop, kPa

2010.3 - Pump pressure/flow rate curvesSingle pumpLegend1 30RY 017-0332 30RY 040-0703 30RY 080Pressure supplied, kPaWater flow rate, l/s50751001251501

Page 14

21Air temperaturesensor positionAccessory filters10.5 - Duct connectionThe 30RY 017-080 can be installed inside a building andconnected to an air duct

Page 15

22Fan data30RY Minimum available Nominal available Maximum availablestatic pressure* static pressure static pressurePressure Flow Pressure Flow Pressu

Page 16

23Depending on the installation and control type, each unit cancontrol its own water pump. If there is only one common pumpfor the two units, the mast

Page 17

24WARNING: To ensure proper operation of 30RY units theremust be at least 12 K of subcooling as the liquid refrigerantenters the expansion valve.The 3

Page 18

2512.6 - UnderchargeIf there is not enough refrigerant in the system, this is indicatedby gas bubbles in the moisture sight glass.If the undercharge i

Page 19

26Characteristics of R407CBar Saturated bubble Saturated dew Bar Saturated bubble Saturated dew Bar Saturated bubble Saturated dew(relative) point tem

Page 20 - Pressure supplied, kPa

2713 - AQUASNAP MAINTENANCE PROGRAMAll maintenance operations must be carried out by technicianswho have been trained on Carrier products, observing a

Page 21

28Service CCarry out the operations listed under Service B.Refrigerant circuit- Check the leak-tightness of the circuit and ensure thatthere is no pip

Page 22 - Additional pressure drop, Pa

2914 - START-UP CHECKLIST FOR 30RY LIQUID CHILLERS (USE FOR JOB FILE)Preliminary informationJob name: ...

Page 23

3CONTENTS (cont’d)12 - MAINTENANCE ...

Page 24 - Pressure

30Unit start-up Chilled water pump starter has been properly interlocked with the chiller Oil level is correct Unit has been leak checked (including f

Page 25

31Carry out the QUICK TEST function (see 30RA/RH - 30RY/RYH «B» Pro-Dialog Plus Control manual):Check and log on to the user menu configurationLoad se

Page 26

Order No.: 13427-76, 09.2003 - Supersedes order No.: 13427-76, 04.2002. Manufactured by: Carrier SA, Montluel, FranceManufacturer reserves the right

Page 27

41 - INTRODUCTIONPrior to the initial start-up of the 30RY units, the peopleinvolved in the on-site installation, start-up, operation, andmaintenance

Page 28

51.3 - Maintenance safety considerationsEngineers working on the electric or refrigeration componentsmust be authorized and fully qualified to do so (

Page 29

6During refrigerant removal and storage operations followapplicable regulations. These regulations, permitting condition-ing and recovery of halogenat

Page 30

72 - PRELIMINARY CHECKS2.1 - Check equipment received• Inspect the unit for damage or missing parts. If damage isdetected, or if shipment is incomplet

Page 31

8Checks before system start-upBefore the start-up of the refrigeration system, the completeinstallation, including the refrigeration system must be ve

Page 32

91372112810682097205882082011000100012058863822.596213516706701100030RY 040-08030RY 017-0333 - DIMENSIONS/CLEARANCESNOTE:A Non-certified drawings.Refe