Carrier 19XR Spécifications Page 76

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 136
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 75
76
TROUBLESHOOTING GUIDE
Overview
The PIC II has many features to help the op-
erator and technician troubleshoot a 19XR chiller.
The CVC shows the chillers actual operating conditions
and can be viewed while the unit is running.
The CVC default screen freezes when an alarm occurs.
The freeze enables the operator to view the chiller condi-
tions at the time of alarm. The STATUS screens continue
to show current information. Once all alarms have been
cleared (by correcting the problems and pressing the
softkey), the CVC default screen returns to nor-
mal operation.
The CONTROL ALGORITHM STATUS screens
(which include the CAPACITY, OVERRIDE,
LL_MAINT,ISM_HIST, LOADSHED, WSMDEFME,
and OCCDEFCM screens) display information that
helps to diagnose problems with chilled water tempera-
ture control, chilled water temperature control overrides,
hot gas bypass, surge algorithm status, and time sched-
ule operation.
The control test feature facilitates the proper operation
and test of temperature sensors, pressure transducers, the
guide vane actuator, oil pump, water pumps, tower con-
trol, and other on/off outputs while the compressor is
stopped. It also has the ability to lock off the compressor
and turn on water pumps for pumpout operation. The
CVC shows the temperatures and pressures required
during these operations.
From other SERVICE tables, the operator/technician can
access configured items, such as chilled water resets,
override set points, etc.
If an operating fault is detected, an alarm message is
generated and displayed on the CVC default screen.
A more detailed message along with a diagnostic
message is also stored into the ALARM HISTORY
table.
Checking Display Messages
The first area to
check when troubleshooting the 19XR is the CVC display. If
the alarm light is flashing, check the primary and secondary
message lines on the CVC default screen (Fig. 14). These mes-
sages will indicate where the fault is occurring. These messag-
es contain the alarm message with a specified code. This code
or state appears with each alarm and alert message. The
ALARM HISTORY table on the CVC SERVICE menu also
contains an alarm message to further expand on the alarm. For
a complete list of possible alarm messages, see Table 11. If the
alarm light starts to flash while accessing a menu screen, press
the softkey to return to the default screen to read the
alarm message. The STATUS screen can also be accessed to
determine where an alarm exists.
Checking Temperature Sensors
All tempera-
ture sensors are thermistor-type sensors. This means that the re-
sistance of the sensor varies with temperature. All sensors have
the same resistance characteristics. If the controls are on, deter-
mine sensor temperature by measuring voltage drop; if the con-
trols are powered off, determine sensor temperature by measur-
ing resistance. Compare the readings to the values listed in
Table 12A or 12B.
RESISTANCE CHECK Turn off the control power and,
from the module, disconnect the terminal plug of the sensor in
question. With a digital ohmmeter, measure sensor resistance
between receptacles as designated by the wiring diagram. The
resistance and corresponding temperature are listed in Table
12A or 12B. Check the resistance of both wires to ground. This
resistance should be infinite.
VOLTAGE DROP The voltage drop across any energized
sensor can be measured with a digital voltmeter while the con-
trol is energized. Table 12A or 12B lists the relationship be-
tween temperature and sensor voltage drop (volts dc measured
across the energized sensor). Exercise care when measuring
voltage to prevent damage to the sensor leads, connector plugs,
and modules. Sensors should also be checked at the sensor
plugs. Check the sensor wire at the sensor for 5 vdc if the con-
trol is powered on.
CHECK SENSOR ACCURACY Place the sensor in a
medium of known temperature and compare that temperature
to the measured reading. The thermometer used to determine
the temperature of the medium should be of laboratory quality
with 0.5
°
F (.25
°
C) graduations. The sensor in question should
be accurate to within 2
°
F (1.2
°
C).
See Fig. 9 for sensor locations. The sensors are immersed
directly in the refrigerant or water circuits. The wiring at each
sensor is easily disconnected by unlatching the connector.
These connectors allow only one-way connection to the sensor.
When installing a new sensor, apply a pipe sealant or thread
sealant to the sensor threads.
DUAL TEMPERATURE SENSORS For servicing con-
venience, there are 2 sensors each on the bearing and motor
temperature sensors. If one of the sensors is damaged, the other
can be used by simply moving a wire. The number 2 terminal
in the sensor terminal box is the common line. To use the sec-
ond sensor, move the wire from the number 1 position to the
number 3 position.
Checking Pressure Transducers
There are 8
pressure transducers on 19XR chillers. They determine cooler,
condenser, oil pressure, and cooler and condenser flow. The
cooler and condenser transducers are also used by the PIC II to
determine the refrigerant temperatures. The oil supply pressure
transducer value and the oil transmission sump pressure trans-
ducer value difference is calculated by the CCM. The CVC
module then displays the differential pressure. In effect, the
CVC reads only one input for oil pressure for a total of 5 pres-
sure inputs: cooler pressure, condenser pressure, oil differential
pressure, cooler waterside differential pressure, and condenser
waterside differential pressure. See the Check Pressure
Transducers section (page 75) under Scheduled Maintenance.
These 5 pressure transducers can be calibrated if necessary.
It is not usually necessary to calibrate at initial start-up.
However, at high altitude locations, it is necessary to calibrate
the transducers to ensure the proper refrigerant temperature/
pressure relationship. Each transducer is supplied with 5 vdc
power from the CCM. If the power supply fails, a transducer
voltage reference alarm occurs. If the transducer reading is
suspected of being faulty, check the supply voltage. It should
be 5 vdc ± .5 v displayed in CONTROL TEST under CCM
Pressure Transducers. If the supply voltage is correct, the trans-
ducer should be recalibrated or replaced.
RESET
EXIT
Relieve all refrigerant pressure or drain the water before
replacing the temperature sensors.
Vue de la page 75
1 2 ... 71 72 73 74 75 76 77 78 79 80 81 ... 135 136

Commentaires sur ces manuels

Pas de commentaire