Carrier 19XR Spécifications Page 37

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 136
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 36
37
Table 4 Capacity Overrides
Spare Safety Alarm Contacts
One set of alarm
contacts is provided in the starter. The contact ratings are pro-
vided in the certified drawings. The contacts are located on ter-
minal strip JP, terminals 15 and 16.
Refrigerant Leak Detector
An input is available
on the CCM module [terminal J5-5 () and J5-6 (+)] for a
refrigerant leak detector. Enabling REFRIGERANT LEAK
OPTION (OPTIONS screen) will allow the PIC II controls to
go into an alarm state at a user configured level (REFRIGER-
ANT LEAK ALARM mA). The input is configured for 4 to
20 mA by setting the DIP switch 1 on SW2 at the ON position,
or configured for 1 to 5 vdc by setting switch 1 at the OFF posi-
tion. The output of the refrigerant leak detector is displayed as
REFRIGERANT LEAK SENSOR on the MAINSTAT screen.
For a 1 to 5 vdc input, 1 vdc input represents 4 mA displayed
and 5 vdc input represents 20 mA displayed.
Kilowatt Output
An output is available on the CCM
module [Terminal J8-1 (+) and J8-2 ()] to represent the power
consumption of the chiller. The 4 to 20 mA signal generated by
the CCM module can be wired to the building automation or
energy management system to monitor the chillers energy
consumption. A 4 mA signal represents the chiller in an off
state and a 20 mA signal represents the chiller operating at its
rated peak kilowatt consumption. The rated peak kilowatt con-
sumption is configured by the user in the RAM_DEM display
screen by the setting the MOTOR RATED KILOWATTS from
the job data sheet.
Remote Reset of Alarms
A standard feature of the
PIC II controls is the ability to reset a chiller in a shutdown
alarm state from a remote location. If the condition which
caused the alarm has cleared the chiller can be placed back into
a normal CCN operating mode when the REMOTE RESET
OPTION (CVC_PSWD menu) is set to ENABLE. A variety of
Carrier Comfort Network software systems including Comfort-
VIEW or Network Service Tool can access the PIC II
controls and reset the displayed alarm. Third party software
from building automation systems (BAS) or energy manage-
ment systems (EMS) can also access the PIC II controls
through a Carrier DataLINK module and reset the fault dis-
played. Both methods would access the CVC_PSWD screen
and force the RESET ALARM ? point to YES to reset the fault
condition. If the PIC II controls have determined that is safe to
start the chiller the CCN MODE ? point (CVC_PSWD screen)
can be forced to YES to place the chiller back into normal
CCN operating mode. The only exceptions are the following
alarms that cannot be reset from a remote location: STATE
#100, 205, 217-220, 223, 233, 234, 247, and 250. To view
alarm codes, refer to Troubleshooting Guide, Checking Dis-
play Messages, page 76. After the alarm has been reset the PIC
II control will increment the Starts in 12 Hours counter by one
upon restart. If the limit of 8 starts in a 12-hour period occurs
the alarm will be required to be reset at the chiller control panel
(CVC).
Condenser Pump Control
The chiller will moni-
tor the condenser pressure (CONDENSER PRESSURE) and
may turn on the condenser pump if the condenser pressure be-
comes too high while the compressor is shut down. The con-
denser pressure override (COND PRESS OVERRIDE) parame-
ter is used to determine this pressure point. COND PRESS
OVERRIDE is found in the SETUP1 display screen, which is
accessed from the EQUIPMENT SERVICE table. The default
value is 125 psig (862 kPa).
If the CONDENSER PRESSURE is greater than or equal to
the COND PRESS OVERRIDE, and the entering condenser
water temperature (ENTERING CONDENSER WATER) is less
than 115 F (46 C), the condenser pump will energize to try to
decrease the pressure. The pump will turn off when the con-
denser pressure is 3.5 psi (24.1 kPa) less than the pressure over-
ride or when the condenser refrigerant temperature (CON-
DENSER REFRIG TEMP) is within 3
°
F (1.7
°
C) of the enter-
ing condenser water temperature (ENTERING CONDENSER
WATER).
OVERRIDE
CAPACITY CONTROL
FIRST STAGE SET POINT
SECOND STAGE SET
POINT
OVERRIDE
TERMINATION
View/Modify
on CVC Screen
Default
Value
Configurable
Range
Value Value
HIGH CONDENSER
PRESSURE
SETUP1
125 psig
(862 kPa)
90 to 165 psig
(620 to 1138 kPa)
>Override
Set Point
+2.4 psid (16.5 kPad)
<Override
Set Point
HIGH MOTOR
TEMPERATURE
SETUP1
>200 F
(93.3 C)
150 to 200 F
(66 to 93 C)
>Override
Set Point
+10° F (6° C)
<Override
Set Point
LOW REFRIGERANT
TEMPERATURE
(Refrigerant
Override Delta
Temperature)
SETUP1 3° F (1.6° C)
2° to 5° F
(1° to 3° C)
Trippoint
+ Override
T 1° F (0.56° C)
>Trippoint
+ Override
T+2° F (1.2° C)
HIGH COMPRESSOR
LIFT
(Surge Prevention)
OPTIONS
Min: T1 1.5° F
(0.8° C)
P1 50 psid
(345 kPad)
Max: T2 10° F
(5.6° C)
P2 85 psid
(586 kPad)
0.5° to 20° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to 1172 kPad)
0.5° to 20° F
(0.3° to 8.3° C)
50 to 170 psid
(348 to 1172 kPad)
None
Within Lift Limits
Plus Surge/HGBP
Deadband Setting
MANUAL GUIDE VANE
TARGET
CAPACITY Automatic 0 to 100% None
Release of
Manual Control
MOTOR LOAD
ACTIVE DEMAND LIMIT
MAINSTAT 100% 40 to 100%
5% of
Set Point
2% Lower
Than Set Point
LOW DISCHARGE
SUPERHEAT
OVERRIDE
Calculated Minimum
Superheat for
Conditions
None
2° F (1.1° C)
Below Calculated
Minimum Superheat
1° F (0.56° C)
Above Calculated
Minimum Superheat
Vue de la page 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 135 136

Commentaires sur ces manuels

Pas de commentaire