Carrier 48TFD008-014 Spécifications

Naviguer en ligne ou télécharger Spécifications pour Pompes à chaleur Carrier 48TFD008-014. Carrier 48TFD008-014 Specifications Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 48
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 004-816 Printed in U.S.A. Form 48TF-C1SI Pg 1 1-01 Replaces: New
Book 1 4
Ta b 1 a 6 a
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-33
Step 1 — Provide Unit Support
. . . . . . . . . . . . . . . . . . .
1
•ROOF CURB
SLAB MOUNT
Step 2 — Field Fabricate Ductwork
. . . . . . . . . . . . . . .
2
Step 3 — Install External Trap for
Condensate Drain
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 4 — Rig and Place Unit
. . . . . . . . . . . . . . . . . . . . . 2
POSITIONING
Step 5 — Install Flue Hood
. . . . . . . . . . . . . . . . . . . . . . . 8
Step 6 — Install Gas Piping
. . . . . . . . . . . . . . . . . . . . . . 8
Step 7 — Make Electrical Connection
. . . . . . . . . . . . 8
FIELD POWER SUPPLY
FIELD CONTROL WIRING
HEAT ANTICIPATOR SETTINGS
Step 8 — Adjust Factory-Installed Options
. . . . . . 11
APOLLO CONTROL
MANUAL OUTDOOR-AIR DAMPER
OPTIONAL DURABLADE ECONOMIZER
OPTIONAL ECONOMI$ER
Step 9 — Adjust Evaporator-Fan Speed
. . . . . . . . . 20
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36
SERVICE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-41
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . . . . 42-46
START-UP CHECKLIST
. . . . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
INSTALLATION
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the insula-
tion side down. Seals around duct openings must be tight. See
Fig. 1.
Step 1 — Provide Unit Support
ROOF CURB Assemble and install accessory roof curb in
accordance with instructions shipped with curb. See Fig. 2. In-
stall insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to curb. If gas, electric
power or control power is to be routed through the curb, attach
the accessory thru-the-curb service connection plates to the
roof curb in accordance with the accessory installation instruc-
tions. Connection plates must be installed before unit is set in
roof curb.
Curb should be level. Unit leveling tolerances are shown in
Fig. 3. This is necessary for unit drain to function properly. Re-
fer to Accessory Roof Curb Installation Instructions for addi-
tional information as required.
Disconnect gas piping from unit when leak test-
ing at pressure greater than 3.4 kPa (
1
/
2
psig).
Pressures greater than 3.4 kPa (
1
/
2
psig) will
cause gas valve damage resulting in hazardous
condition. If gas valve is ever subjected to pres-
sure greater than 3.4 kPa (
1
/
2
psig), it must be
replaced before use. When pressure testing
field-supplied gas piping at pressures of 3.4 kPa
(
1
/
2
psig) or less, a unit connected to such piping
must be isolated by manually closing the gas
valve(s).
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also result in air leaks and poor unit
performance.
48TFD008-014
48TFE008-014
48TFF008,012
Single-Package Rooftop Heating/Cooling Units
50 Hz
Vue de la page 0
1 2 3 4 5 6 ... 47 48

Résumé du contenu

Page 1 - Service Instructions

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 2 - Drain —

10INTEGRATEDGAS UNITCONTROLLER(IGC)RACEWAYUNIT LOW VOLTAGECONNECTIONBOARDCOMPRESSORNO.1COMPRESSORNO. 2Fig. 9 — Power Wiring Connections

Page 3 - Fig. 2 — Roof Curb Details

11Step 8 — Adjust Factory-Installed OptionsAPOLLO CONTROL — The optional Apollo control is usedto actively monitor all modes of operation as well as i

Page 4 - DIFFERENCE mm (in.)

12OPTIONAL DURABLADE ECONOMIZER — The option-al economizer hood assembly is packaged and shipped in the fil-ter section. Damper blades and control boa

Page 5 - Table 1A — Physical Data (SI)

13ECONOMIZERCONTROL BOARDECONOMIZERPLUGECONOMIZERMOTORTOPSCREWSHIPPINGSCREWECONOMIZER CONTROL BOARDECONOMIZER MOTORPOSITION SETTING BRACKETBLOCK-OFF P

Page 6

144321056789UNITTOPOAT(TERMINALS ARE UP)OUTSIDE AIRSCREENMINIMUMPOSITIONOPEN31TPP1T1425SSODCTRBREV.B198818A%HUM ID ITY9070603010DCBA6065707555508580DA

Page 7 - Fig. 6 — Base Unit Dimensions

15OPTIONAL ECONOMI$ER — See Fig. 28 for EconoMi$ercomponent locations.1. To remove the existing unit filter access panel, raise thepanel and swing the

Page 8 - Step 5 — Install Flue Hood —

165. Slide the outdoor air inlet screens into the screen track onthe hood side panels. While holding the screens in place,fasten the screen retainer t

Page 9

17OUTDOORAIRSENSORTEMPTEMPCOMOUTPWRBROWNVIOLETWHITEREDBROWNTEMPTEMPCOMOUTPWRRETURNAIRSENSORVIOLETWHITEREDOATCOMOAH+15 VRATCOMRAH+15 VECONOMI$ERCONTROL

Page 10

18SUPPLY AIRTEMPERATURESENSORMOUNTINGLOCATIONSUPPLY AIRTEMPERATURESENSOR4-PINCONNECTORPLUGL1L2GREEN11223344GND230 VAC1 PHASEGREEN/YELLOW3215869BA74LT.

Page 11

19CO2 Control Set Up — If a CO2 sensor is not being used, pro-ceed to the next section. If a CO2 sensor is being used, performthe following:1. Determi

Page 12 - FILTER ACCESS

2SLAB MOUNT (Horizontal Units Only) — Provide a levelconcrete slab that extends a minimum of 152 mm (6 in.)beyond unit cabinet. Install a gravel apr

Page 13

20Step 9 — Adjust Evaporator-Fan Speed — Ad-just evaporator-fan speed to meet jobsite requirement.Table 6 shows motor performance. Tables 7 and 8 show

Page 14 - POSITION

21Table 7 — Fan R/s at Motor Pulley Settings (SI)Table 8 — Fan Rpm at Motor Pulley Settings (English)Table 9 — Evaporator-Fan Motor EfficiencyNOTE: Co

Page 15 - PRESSURE DROP (Pa)

22Table 12 — Fan Performance, 48TF008 — Vertical Discharge Units (SI) LEGENDNOTES:1.Boldface indicates field-supplied drive requ

Page 16

23Table 13 — Fan Performance, 48TF012 — Vertical Discharge Units (SI) LEGENDNOTES:1.Boldface indicates field-supplied drive requ

Page 17 - Outdoor-Air Thermostat

24Table 14 — Fan Performance, 48TF014 — Vertical Discharge Units (SI) LEGENDNOTES:1.Boldface indicates field-supplied drive requ

Page 18 - DISCONNECT

25Table 15 — Fan Performance, 48TF008 — Horizontal Discharge Units (SI) LEGENDNOTES:1.Boldface indicates field-supplied drive re

Page 19 - STATIC PRESSURE (IN.WG)

26Table 16 — Fan Performance, 48TF012 — Horizontal Discharge Units (SI)LEGENDNOTES:1.Boldface indicates field-supplied drive required. (See Note 5.)2.

Page 20 - PLATE NUTS

27Table 17 — Fan Performance, 48TF014 — Horizontal Discharge Units (SI)LEGENDNOTES:1.Boldface indicates field-supplied drive required. (See Note 5.)2.

Page 21

28Table 18 — Fan Performance, 48TF008 — Vertical Discharge Units (English) LEGENDNOTES:1.Boldface indicates field-supplied drive

Page 22

29Table 19 — Fan Performance, 48TF012 — Vertical Discharge Units (English)LEGENDNOTES:1.Boldface indicates field-supplied drive required. (See Note 5.

Page 23

3CONNECTORPKG. ACCY.BCD ALT DRAIN HOLEGAS POWER CONTROLCRBTMPWR001A002′-87/16″[827]1′-1015/16″[583]13/4″[44.5]3/4″[19] NPT3/4″ [19] NPT1/2″[12.7]CRBTM

Page 24

30Table 20 — Fan Performance, 48TF014 — Vertical Discharge Units (English)LEGENDNOTES:1.Boldface indicates field-supplied drive required. (See Note 5.

Page 25

31Table 21 — Fan Performance, 48TF008 — Horizontal Discharge Units (English)LEGENDNOTES:1.Boldface indicates field-supplied drive required. (See Note

Page 26

32Table 22 — Fan Performance, 48TF012 — Horizontal Discharge Units (English)LEGENDNOTES:1.Boldface indicates field-supplied drive required. (See Note

Page 27

33Table 23 — Fan Performance, 48TF014 — Horizontal Discharge Units (English)LEGENDNOTES:1.Boldface indicates field-supplied drive required. (See Note

Page 28

34START-UPUnit Preparation — Make sure that unit has been in-stalled in accordance with these installation instructions andapplicable codes. Make sure

Page 29

355. After a call for heating, the main burners should lightwithin 5 seconds. If the burners do not light, then there isa 22-second delay before anoth

Page 30

36If the outdoor air alone cannot satisfy the cooling require-ments of the conditioned space, economizer cooling is integrat-ed with mechanical coolin

Page 31

37LubricationCOMPRESSORS — Each compressor is charged with thecorrect amount of oil at the factory.FAN-MOTOR BEARINGS — Fan-motor bearings are ofthe p

Page 32

38Fig. 49 — Cooling Charging Charts, 48TF008 UnitsFig. 50 — Cooling Charging Charts, 48TF012 Units

Page 33

39Flue Gas Passageways — To inspect the flue collec-tor box and upper areas of the heat exchanger:1. Remove the combustion blower wheel and motor ass

Page 34

4Although unit is weatherproof, guard against water fromhigher level runoff and overhangs.Position unit on roof curb so that the following clearancesa

Page 35 - Operating Sequence

40Main Burners — At the beginning of each heating sea-son, inspect for deterioration, blockage due to corrosion or oth-er causes. Observe the main bur

Page 36 - Cleaning —

41NOTE: Dimensions in ( ) are millimeters.Fig. 54 — Spark Gap Adjustment48TFD00831.4/21.1 kW INPUT (107,000/72,000 BTUH)48TFE008, 48TFD01250.4/31.9 kW

Page 37 - 89 (3.50)

42TROUBLESHOOTINGTable 26 — LED Error Code Service Analysis LEGENDPROBLEM CAUSE REMEDYHardware failure.(LED OFF)Loss of power to control module (IGC).

Page 38

43 Table 27 — Cooling Service TroubleshootingPROBLEM CAUSE REMEDYCompressor andcondenser fanwill not start.Power failure. Call po

Page 39 - Burner Ignition —

44Table 28 — Heating Service TroubleshootingTable 29 — EconoMi$er TroubleshootingLEGENDPROBLEM CAUSE REMEDYBurners will notignite.Misaligned spark ele

Page 40 - Replacement Parts —

45Table 30 — Durablade Economizer Troubleshooting LEGENDPROBLEM CAUSE REMEDYDamper does notopen.Indoor (evaporator) fan is off. 1.

Page 41

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 43

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 44 - Indoor Fan Motor

5Table 1A — Physical Data (SI)LEGEND *Weight of 356 mm (14-in.) roof curb.NOTE: The 48TF units have a loss-of-charge (low pressure) switch located int

Page 45

6Table 1B — Physical Data (English)LEGEND *Weight of 356 mm (14-in.) roof curb.NOTE: The 48TF units have a loss-of-charge (low pressure) switch locate

Page 46 - Ta b 1 a 6 a

7BOTTOM POWER CHART, THESE HOLES REQUIRED FOR USE WITH ACCESSORYPACKAGES — CRBTMPWR002A00 (POWER AND CONTROL) AND CRBTMPWR004A00 (POWER, CONTROL, AND

Page 47

8Step 5 — Install Flue Hood — Flue hood is shippedscrewed to the burner compartment access panel. Removefrom shipping location and, using screws provi

Page 48

9Table 2 — Electrical Data LEGEND*Fuse or HACR circuit breaker.NOTES:1. In compliance with NEC requirements (U.S.A. Standar

Commentaires sur ces manuels

Pas de commentaire