Installation Instructions
25HPA
Performancet Series Heat Pump
with Puronr Refr iger a n t
1---1/2 To 5 Nominal Tons (Sizes 18 to 60)
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock, or
other conditions which may cause death, personal injury, or
property damage. Consult a qualified installer, service agency, or
your distributor or branch for information or assistance. The
qualified installer or agency must use factory--authorized kits or
accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes
and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-- alert symbol
!
!
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is
used to identify unsafe practices which may result in minor
personal injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
IMPORTANT: Maximum liquid--line size is 3/8--in. OD for all
residential applications including long line.
IMPORTANT: Always install the factory--supplied liquid--line
filter drier . Obtain replacement filter driers from your distributor
or branch.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced
to gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropri-
ate for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vi-
bration.
5. When passing refrigerant tubes through the wall, seal
opening with RTV or other pliable silicon--based caulk.
(See Fig. 1.)
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs
with a rigid wire or strap which comes in direct contact
with tubing. (See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely
surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. (25.4
mm) wide and conform to shape of tubing insulation. (See
Fig. 1.)
10. Isolate hanger straps from insulation by using metal
sleeves bent to conform to shape of insulation.
INSULATION
VAPOR TUBE
LIQUID TUBE
OUTDOOR WALL INDOOR WALL
LIQUID TUBE
VAPOR TUBE
INSULATION
CAULK
Avoid contact between tubing and structureNOTE:
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
JOIST
1 (25.4 mm)MIN.
SUSPENSION
A94028
Fig. 1 --- Connecting Tubing Installation
When outdoor unit is connected to factory--approved indoor unit,
outdoor unit contains system refrigerant charge for operation with
ARI rated indoor unit when connected by 15 ft/4.57 m. of
field--supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section
of this instruction.
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - Installation Instructions

Installation Instructions25HPAPerformancet Series Heat Pumpwith Puronr Refr iger a n t1---1/2 To 5 Nominal Tons (Sizes 18 to 60)SAFETY CONSIDERATIONSI

Page 2 - INSTALLATION

10TROUBLESHOOTINGSystems Communication FailureIf communication between User Interface (UI), and condensingunit is lost, the outdoor control will flash

Page 3 - ISO 9001:2000

11Status CodesTable 3 shows the status codes flashed by the amber status light.Most system problems can be diagnosed by reading the statuscode as flas

Page 4

1201020304050607080900 (-17.77)20 (-6.67)40 (4.44)60 (15.56)80 (26.67)100 (37.78)120 (48.89)TEMPERATURE °F (°C)RESISTANCE (KOHMS)THERMISTOR CURVEA0805

Page 5

2INSTALLATIONCheck Equipment and Job SiteUnpackUnitMove to final location. Remove carton taking care not to damageunit.Inspect EquipmentFile claim wit

Page 6 - OCT Thermistor

3Outdoor units may be connected to indoor section usingaccessory tubing package or field--supplied refrigerant gradetubing of correct size and conditi

Page 7 - STANDARD THERMOSTAT

4Outdoor Unit Connected to Factory ApprovedIndoor UnitThese outdoor units are carefully evaluated and listed withspecific indoor coils for proper syst

Page 8 - } Outdoor Air Temp (OAT)

5Final Tubing CheckIMPORTANT: Check to be certain factory tubing on both indoorand outdoor unit has not shifted during shipment. Ensure tubesare not r

Page 9

6The Outdoor Coil Temperature (OCT) Thermistor is factoryinstalled on the 3/8” diameter stub tube located on the coilassembly. Check to make sure that

Page 10 - TROUBLESHOOTING

7Check ChargeFactory charge amount and desired subcooling are shown on unitrating plate. Char ging method is shown on information plateinside unit. To

Page 11 - Status Codes

8Outdoor Coil Temp (OCT)} Outdoor Air Temp (OAT)}COMM STATUSA05332Fig. 11 --- Contro l BoardTime DelaysThe unit time delays include:S Five minute time

Page 12 - THERMISTOR CURVE

9Standard Thermostat low ambient cooling mode:A Low Ambient Pressure Switch kit, Evaporator FreezeThermostat and Isolation Relay must be installed for