Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-80028 Printed in U.S.A. Form 48HG-3SI Pg 1 9-01 Replaces: New
Book 1 4
Ta b 1 a 6 a
Installation Instructions
Part Numbers: CRLPKIT8001A00, CRLPKIT8002A00
SAFETY CONSIDERATIONS
Read these instructions entirely before installing the acces-
sory LP (Liquid Propane) Gas Conversion Kit into the base
rooftop unit. See Table 1 for usage and contents.
Installation, start-up, and servicing of this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roofs). Only trained, qualified installers
and service technicians should install, start up, and service this
equipment.
When working on this equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment. Also observe any other safety precautions that may
apply.
GENERAL
These instructions cover the installation of liquid propane
(LP) conversion kits used to convert units from standard natu-
ral gas input to LP gas input. See Table 1 below for accessory
kit contents and usage.
Table 1 — LP Kit Contents and Usage
Before beginning any modifications, close the main gas
supply shutoff valve, and be certain the main-line electrical
disconnect switch is in the OFF position. Electric shock or
fire could result. TAG DISCONNECT SWITCH AND GAS
VALVE WITH APPROPRIATE WARNING LABELS.
Never use a match or other open flame to check for leaks.
Use a soap and water solution. Fire or serious injury could
result.
This unit is designed to operate at the following manifold
pressures with LP gas: 3.0 ± 0.3 in. wg for vertical supply
units and 2.8 ± 0.3 in. wg for horizontal supply units. Exceed-
ing this pressure will cause explosion or injury.
IMPORTANT: Read these installation instructions thor-
oughly BEFORE starting installation. This instruction
and accessory is for the Centurion 48HGD/E/F units.
These units are equipped with an IGC (Integrated Gas
Unit Controller) board and a direct spark ignition system.
KIT NUMBER UNIT
TYPE OF
SYSTEM
STANDARD UNIT HEAT INPUT (Btuh)
KIT CONTENTS
Vertical/Horizontal
CRLPKIT8001A00
48HGD014-028 5-Cell 250,000/225,000 8 Orifices (LH32RF110)
Instructions
Conversion Label
Warning Label
48HGF014 6-Cell 287,000/266,000
48HGF016-028 8-Cell 372,000/356,000
CRLPKIT8002A00
48HGE016-028 8-Cell 365,000/356,000
8 Orifices (LH32RF102)
Instructions
Conversion Label
Warning Label
48HG014-028
Single-Packaged Large Rooftop Units
Accessory LP (Liquid Propane) Gas Conversion Kit
60 Hz