Carrier 19XL Spécifications Page 260

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 392
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 259
Note:
1. Condenser Freeze Point and Softstop Amps Threshold are only selectable/readable on PSIO Software
Versions 09 and higher.
2. Values in [ ] indicate HFC-134a values.
3. = delta degrees.
Surge/HGBP Delta P2
Full Load Points (T2/P2)
Surge/HGBP Deadband
Surge Delta Percent Amps
Surge Time Period
Demand Limit Source
Select: Amps=0, Load=1
Amps Correction Factor
Motor Rated Load Amps
Motor Rated Line Voltage
Meter Rated Line KW
Line Frequency
Select: 0=60 Hz, 1=50 Hz
Compr Starter Type
Condenser Freeze Point
Soft Stop Amps Threshold
[30-170 (207-1172)]
1-3 (0.6-1.6)
10-50
1-5
0/1
1-8
1-9999
1-9999
1-9999
0/1
REDUCE/FULL
20-35 (–28.9-1.7)
40-100
PSI (kPa)
DEG F (DEG C)
%
MIN
AMPS
VOLTS
kW
HZ
DEG F (DEG C)
%
hgb
dp2
hgb
dp
surge
a
surge
t
dem
src
corfact
a
fs
v
fs
kw
fs
freq
starter
cdfreeze
softstop
170 (1172) [85 (586)]
1 (0.6)
25
2
0
3
200
460
600
0
REDUCE
34 (1)
100
Table 2, Example 7 — Service1 Display Screen (Continued)
Description
Configurable
Range
Units
Reference
Point
Name
Default Value
Vue de la page 259
1 2 ... 255 256 257 258 259 260 261 262 263 264 265 ... 391 392

Commentaires sur ces manuels

Pas de commentaire