Installation Instructions
38QRF018---036
Duct Free Heat Pumps
A07532
Fig. 1 -- 38QRF
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1........................
INSTALLATION 2--6.................................
Complete Pre--Installation Checks 2...................
Rig and Mount Unit 5..............................
Complete Refrigerant Piping Connections 5.............
Make Electrical Connections 6........................
START--UP 9........................................
SERVICE 9.........................................
MAINTENANCE 13..................................
TROUBLESHOOTING 14--15..........................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert symbol
!
!
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
Vue de la page 0
1 2 3 4 5 6 ... 15 16

Résumé du contenu

Page 1 - Installation Instructions

Installation Instructions38QRF018---036Duct Free Heat PumpsA07532Fig. 1 -- 38QRFNOTE: Read the entire instruction manual before starting theinstallati

Page 2 - INSTALLATION

10625 ± 50 psig between suction (low side) and discharge (high side)to allow pressure equalization.Internal Current and Temperature Sensitive Overload

Page 3

11Reversing ValveIn heat pumps, changeover between heating and cooling modes isaccomplished with a valve that reverses flow of refrigerant in thesyste

Page 4 - /8 1/8 1/4 1/4 1/4

12Table 3 – Pressure vs. Temperature Chart -- Puron (R--410A) RefrigerantPRESSURE TEMPERATURE PRESSURE TEMPERATURE PRESSURE TEMPERATURE PRESSURE TEMPE

Page 5 - CONNECTIONS

13MAINTENANCE!WARNINGELECTRICAL SHOCK HAZARDFailure to follow this warning could result in personalinjury or death.Before installing, modifying, or se

Page 6 - MAKE ELECTRICAL CONNECTIONS

14TROUBLESHOOTINGLEGENDNOTE: For systems with indoor units equipped with microprocessorcontrol, see separate controls, service, and troubleshooting ma

Page 7 - 38QRF OPERATION SEQUENCE

15TROUBLESHOOTING (CONT.)LEGENDNOTE: For systems with indoor units equipped with microprocessorcontrol, see separate controls, service, and troublesho

Page 8

16Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 10/10Manufacturer reserves the right to c

Page 9 - START--UP

2INSTALLATION!WARNINGUNIT OPERATION AND SAFETY HAZARDFailure to follow this warning could result in personal injuryor equipment damage.Puron refrigera

Page 10

3(FIELD PROVIDED AND INSTALLED)NOTE: Dimensions shown in feet-inches. Dimensions in ( ) are millimeters.UNIT MODELSCHASSISSIZE(Reference)ABCDE FG H JK

Page 11 - TP — Te st Poin t

4Table 1 – 38QRF018--036 Physical DataUNIT 38QRF 018 024 030 035 036NOMINAL CAPACITY Tons 1.5 2.0 2.5 2.9 3.0OPERAT ING WEIGHT lb (kg) 166 (75.3) 176

Page 12

5RIG AND MOUNT UNITMounting on GroundMount unit on a solid, level concrete pad. Position unit so water orice from roof does not fall directly onto uni

Page 13 - MAINTENANCE

6Make Suction Tube Sweat ConnectionRemove plastic caps from liquid and suction service valves. Userefrigerant grade tubing. Service valves are closed

Page 14 - ODT — Outdoor Thermostat

738QRF SCHEMATICLEGENDNOTES:1. Compressor and fan motors are thermally protected.2. Wire in accordance with National Electrical Code (NEC) and local c

Page 15 - TROUBLESHOOTING (CONT.)

8Table 2 – 38QRF Electrical Data38QRFUNITSIZEV --- P H --- H zVOLTAGE RANGE*COMPRESSOR OUTDOOR FAN MOTORMIN CKTAMPSFUSE/HACRBKRAMPSRLA LRA FLA NEC Hp

Page 16 - Catalog No:38QRF---5SI

9START--UPPreliminary Checks1. Check that all internal wiring connections are tight and thatall barriers, covers, and panels are in place.2. Field ele