Carrier 38BK-018 Spécifications

Naviguer en ligne ou télécharger Spécifications pour Climatiseurs à système divisé Carrier 38BK-018. Carrier 38BK-018 Specifications Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 26
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
619E018,024,
40QNB,QNH018,024
High Wall Fan Coil Units
Cancels: II 619E-18-2
Installation, Start-Up
and Service Instructions
II 619E-18-3
9/1/02
CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1
GENERAL ....................................... 1,2
INSTALLATION ................................ 2-13
Step 1 -- Complete Pre-lnstallation
Checks ......................................... 2
UNPACK UNIT
INSPECT SHIPMENT
Step 2 -- Select Location ......................... 2
Step 3 -- Attach Mounting Bracket to Wall ....... 5
Step 4 -- Connect Refrigerant Piping ............ 5
Step 5 -- Connect Condensate Drain Line ....... 11
Step 6 -- Make Electrical Connections .......... 11
Step 7 -- Make Connections to
Outdoor Unit .................................. 13
COOLING-ONLY SYSTEMS
HEAT PUMP SYSTEMS
Step 8 -- Install Fan Coil Unit Onto Mounting
Bracket ....................................... 13
START-UP .................................... 13-16
Control System ................................. 14
After Extended Shutdowns ...................... 14
Seasonal Changeovers .......................... 14
To Turn The Unit On and Off ..................... 14
Adjusting Airflow ................................ 14
Operating Mode Memory ........................ 15
Automatic Operation (Auto) Mode ............... 15
Operating Fault Diagnosis ....................... 15
Microprocessor Control Operation .............. 15
CLEANING AND MAINTENANCE .............. 17,18
Lubrication ...................................... 17
To Install or Replace Remote Controller
Batteries ...................................... 17
To Set the Current Time ......................... 17
To Remove and Clean or Replace Air Filters ..... 17
TO REMOVE AIR FILTERS
TO CLEAN OR REPLACE FILTERS
To Clean Indoor Unit Front Panel ................ 18
To Clean Indoor Coil ............................ 18
To Clean Outdoor Coil (Outdoor Unit) ........... 18
Cleaning Condensate Drains .................... 18
SERVICE ........................................ 19
Diagnostic Codes ............................... 19
System Tests .................................... 19
THERMISTOR TESTS
THERMISTORS
COMPRESSOR FAILURE
REVERSING VALVE FAILURE (Heat Pump Only)
Page
System Safeties and Interlock ................... 19
INDOOR FAN FAILURE
COMPRESSOR SHORT-CYCLING PROTECTION
INDOOR COIL FREEZE PROTECTION
(Cooling or Dehumidification Mode Only)
INDOOR COIL HIGH-TEMPERATURE
PROTECTION (Heat Pump Systems Only)
TROUBLESHOOTING ......................... 19-25
STA RT-UP CHECKLIST ................... CL- 1,CL-2
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install or
service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such
as clemling and replacing tilters. All other operations should be
performed by trained selwice personnel. When working on air-
conditioning equipment, observe precautions in literature and
on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses mid work
gloves. Use quenching cloth for brazing operations. Have fire
extin_isher available. Read these instructions thoroz(,_hl3<
Consult local building codes and National Electrical Code
(NEC) for special installation requirements.
Before installing or servicing system, always turn offmain
power to system. There may be more than one disconnect
switch. Turn offindoor tan coil power if applicable. Electri-
cal shock can cause personal injury.
GENERAL
The heat pump hi_l walt tan coil units (Fig. 1) come with
supplemental electric heat. If your application requires heating,
heat pump units must be used, both outdoors and indoors. See
Table 1 for recommended system combinations.
)
Fig. 1 -- Typical High Wall Fan Coil Unit
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-043 Printed in U.S.A. Form 40QN-6SI Pg 1 9-02 Replaces: 40QN-4SI
Vue de la page 0
1 2 3 4 5 6 ... 25 26

Résumé du contenu

Page 1 - Installation, Start-Up

619E018,024,40QNB,QNH018,024High Wall Fan Coil UnitsCancels: II 619E-18-2Installation, Start-Upand Service InstructionsII 619E-18-39/1/02CONTENTSPageS

Page 2

Table 6 -- Refrigerant ChargeHIGH WALL IADDED CHARGE*SYSTEM INDOOR UNIT OUTDOOR UNIT(Btuh) (over 50 ft tubing)Coolin_ Only18,00024,00040QNB018619ENX01

Page 3 - I ...1

Step 5 -- Connect Condensate Drain Line -- Ob-serve all local sanitary codes when installing condensatedrains.1. Connect the drain line by inserting a

Page 4

LABEL CAUTION- SCREW_ SFRAINRELIEFCLAMPNOTE: This shows item locations only. Front cover of fan coil unitmust be removed to access terminal boards.Fig

Page 5

Step 7 i Make Connections to the OutdoorUnitCOOLING ONLY SYSTEMS To connect the outdoor unitto the tan coil unit so the system will operate correctly:

Page 6 - WALLSLEEVE-- /

ControlSystem --The indoor unit is equipped with amicroprocessor control which operates the system. This controlis located in the control box of the f

Page 7

The swing range shown in Fig. 18is the range that providesmaxilnum occupant comfort in each mode. It is recolmnendedthat the louvers be positioned wit

Page 8

TheindoortZanspeedwillbeatthehighsetting,andtheswinglouverswillbeon(movingupanddo,am).NOTE:Theunitcmmotbecontrolledbytheremotecontrolleruntiltheslides

Page 9

CLEANING AND MAINTENANCETo avoid the possibility of electric shock, before performingaaly cleaning and maintenance operations, always turn offpower to

Page 10 - Table 6 -- Refrigerant Charge

TO CLEAN OR REPLACE FILTERS Filters should bevacuumed and ,a_ashedwith warm water (see Fig. 23). Shakethe tilter to remove any excess ,a_atei; dry it

Page 11 - "/777

SERVICEWhen servicing unit, turn off all electric power to unit toavoid shock hazard or injury tiom rotating parts.Do not vent refrigerant to atmosphe

Page 12 - INDOORoTOooNNECTL

Table 1 -- System Combinations for Indoor andOutdoor UnitsSYSTEM INDOOR UNIT OUTDOOR UNIT40QNB018 38HDC, HDL01840QNB024 38HDL018, 38HDC,HDL024Cooling

Page 13 - --101/4"

Table 12 -- Thermistor Properties*MINIMUM NOMINAL MAXIMUMTEMP MINIMUM NOMINAL MAXIMUM THERMISTOR THERMISTOR THERMISTOR(F) OHMS OHMS OHMS VOLTS -- DC V

Page 14 - 20'

iiAIRFLOW' OUTDOOR ';;'":' UNIT " .: _ ..,2 WIRES(4FUSED DISCONNECTf_ EATHERPROOFFUSED DISCONNECTtPERNEC_ _ "_- 2 W

Page 15

AGING --AS, ASS'Y --CCAPCHCLOCNCOMP --CTEMIFLFMCGNDHAHPSHSHTRIDC Th --IFMJEM-A --KLLPSLPSLSODA Th --ODC Th --OFMLEGEND AND NOTES FOR FIG. 25-27Fo

Page 16 - Fig. 20 -- Slide Switch

Ix3%0RELAY CHARTCOMPRESSOR K13OUTDOOR FAN K12REV. VALVE KllTHERMISTOR EQUIVALENCETEMPERATURE RESISTANCE°F °C o95 35 5,50072 22 11,40032 0 32,500ALL TH

Page 17 - MONTHLYI OUABTEBLYI YEARLY

4_-THERMISTOR EQUIVALENCETEMPERATURE RESISTANCE°F °O a95 35 5,50072 22 11,40032 0 32,500ALL THERMISTORS ARE IDENTICAL018 024 FANCOILBRN CN9IDC ThRA Th

Page 18

TIME GUARO TIMING SEQUENCE3 SEC_ RUN TIME _ _5 M[N.T] T2[__BLACK DENOTES CLOSED CONTACTSTHERMISTOR EQUIVALENCETEMPERATURE RESISTANCE_F _C Q95 35 5,500

Page 19

Copyright 2002 Carrier CorporationManufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and

Page 20 - Table 13 -- Troubleshooting

4. Place the top of the fan coil unit up to 10 ft above floorlevel, making sure the unit is at least 10 in. down fromthe ceiling to permit proper air

Page 21 - TOOPENS*GNT -j/ //

Table4-- High Wall Unit Package ContentsITEM QUANTITYUnit Mounting Template 1Unit Mounting Bracket 11-in. Lag Screws For Unit Mounting 8Hollow Wall An

Page 22

POSSIBLE PIPING DIRECTIONSRIGHT __SIDEKNOCKOUT_"__ LEFTA _ SiDE... II _ KNOCKOUTBOttOM KNOCKOUT ItUPREPUNCHED HOLESFOR RIGHTSIDE PiPiN

Page 23

Use the following instructions to connect piping.1. Install insulation. Insulate all refrigerant lines onheat pumps and multi-split systems to prevent

Page 24 - L R :A PDOAS

Table 5A -- Physical Data -- 38HDC, 538A Condensing UnitsUNIT SIZENOMINAL CAPACITY (Tons)OPERATING WEIGHT (Ib)REFRIGERANT TYPEControl (Cooling)Charge

Page 25 - PCB ASS" Y

Table 5C -- Physical Data -- Multi-Split Condensing UnitsUNIT SIZENOMINAL CAPACITY (Tons)OPERATING WEIGHT (Ib)REFRIGERANT TYPEControl (Cooling)Charge

Page 26

Table 5E -- Physical Data -- Outdoor Heat Pump UnitsUNIT SIZENOMINAL CAPACITY (Tons)OPERATING WEIGHT (Ib)REFRIGERANT TYPEControl (Cooling)Control (Hea

Commentaires sur ces manuels

Pas de commentaire