Carrier 48AJ Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Radiateurs Carrier 48AJ. Carrier 48AJ User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 118
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-739 Printed in U.S.A. Form 48A,E-1SI Pg 1 107 11-01 Replaces: 48E-6SI
Book 1
Ta b 1 a
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-58
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
ROOF CURB
ALTERNATE UNIT SUPPORT
Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2
POSITIONING
ROOF MOUNT
Step 3 — Field Fabricate Ductwork. . . . . . . . . . . . . . . 2
Step 4 — Make Unit Duct Connections . . . . . . . . . . . 2
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . 28
Step 6 — Trap Condensate Drain . . . . . . . . . . . . . . . . 28
Step 7 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . 28
Step 8 — Controls Options . . . . . . . . . . . . . . . . . . . . . . 29
STAGED GAS UNIT APPLICATIONS
THERMISTORS
CONSTANT VOLUME APPLICATIONS
VARIABLE AIR VOLUME (VAV) APPLICATIONS
Step 9 — Make Electrical Connections . . . . . . . . . . 33
•POWER WIRING
FIELD POWER SUPPLY
FIELD CONTROL WIRING
Step 10 — Make Outdoor-Air Inlet
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
ECONOMIZER
ECONOMIZER SETTINGS
Step 11 — Position Power Exhaust/Barometric
Relief Damper Hood. . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Step 12 — Install All Accessories . . . . . . . . . . . . . . . 54
Step 13 — Field Modifications. . . . . . . . . . . . . . . . . . . 57
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58-89
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89-102
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . 103-115
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . CL-1,CL-2
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should in-
stall, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
INSTALLATION
Step 1 — Provide Unit Support
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
1. Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, personal
injury, or loss of life. Refer to the Users Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable va-
pors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
3. IMMEDIATELY call your gas supplier from a neigh-
bors phone. Follow the gas suppliers instructions.
4. If you cannot reach your gas supplier, call the fire
department.
Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure
testing field-supplied gas piping at pressures of 0.5 psig or
less, a unit connected to such piping must be isolated by
closing the manual gas valve(s).
1. All panels must be in place when rigging.
2. Unit is not designed for handling by fork truck.
48AJ,AK,AW,AY020-060
with Reciprocating Compressor
48EJ,EK,EW,EY024-068
Single Package Rooftop Units
Electric Cooling/Gas Heating
Vue de la page 0
1 2 3 4 5 6 ... 117 118

Résumé du contenu

Page 1 - Service Instructions

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 1

Page 2

10Fig. 8 — Base Unit Dimensions — 48AW,AY020-030NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units wi

Page 3

100Fig. 81 — Typical 48EJ CV 115-V Control Circuit

Page 4

101Fig. 82 — Label Diagram — Staged Gas Heat — 48AJ,AK,AW,AY020-050 and 48EJ,EK,EW,EY024-048 Units

Page 5

102Fig. 83 — Label Diagram — Staged Gas Heat — 48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY054-068 Units

Page 6

103TROUBLESHOOTINGTypical refrigerant circuiting diagrams are shown in Fig. 84-93. An algorithm diagram of the IGC (Integrated Gas Unit Controller)con

Page 7

1044-Pass4-Pass 4-Pass4-Pass 4-Pass4-Pass 4-Pass4-Pass 4-Pass4-Pass 4-Pass4-Pass 4-Pass4-Pass 4-Pass4-Pass 4-Pass4-Pass 4-Pass4-Pass 4-Pass4-Pass 4-Pa

Page 8

10512-Pass 4-Pass12-Pass 4-Pass12-Pass 4-Pass12-Pass 4-Pass12-Pass 4-Pass12-Pass 4-Pass12-Pass 4-Pass12-Pass 4-Pass12-Pass 4-Pass12-Pass 4-Pass12-Pass

Page 9

106 LEGENDFig. 87 — Typical Refrigerant Circuiting (48EJ,EK,EW,EY038,044)FPS — Freeze Protection SwitchHPS — High-Pressure SwitchLPS

Page 10

1078-Pass 4-Pass8-Pass 4-Pass8-Pass 4-Pass8-Pass 4-Pass8-Pass 4-Pass8-Pass 4-Pass8-Pass 4-Pass8-Pass 4-Pass8-Pass 4-Pass8-Pass 4-Pass8-Pass 4-Pass8-Pa

Page 11

108 LEGENDFig. 89 — Typical Refrigerant Circuiting (48EJ,EK,EW,EY048)FPS — Freeze Protection SwitchHPS — High-Pressure SwitchL

Page 12

109 LEGENDFig. 90 — Typical Refrigerant Circuiting (48EJ,EK,EW,EY054 and 058)HPS — High-Pressure SwitchLPS — Low-Pressure Swit

Page 13

11Fig. 9 — Base Unit Dimensions — 48AW,AY035-050NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units wi

Page 14

1104-Pass6-Pass 4-Pass4-Pass 4-Pass6-Pass 4-Pass6-Pass 4-Pass4-Pass 4-Pass6-Pass 4-Pass6-Pass 4-Pass4-Pass 4-Pass6-Pass 4-Pass6-Pass 4-Pass4-Pass 4-Pa

Page 15

111 LEGENDFig. 92 — Typical Refrigerant Circuiting (48EJ,EK,EW,EY064)HPS — High-Pressure SwitchLPS — Low-Pressure SwitchTXV —

Page 16

112 Fig. 93 — Typical Refrigerant Circuiting (48EJ,EK,EW,EY068) LEGENDHPS — High-Pressure SwitchLPS

Page 17

113 LEGENDNOTE: Thermostat Fan Switch in the “AUTO” position or sensor-equipped unit.Fig. 94 — IGC Control (Heating and Coolin

Page 18

114The alarm codes for the IGC control board are shown inTable 44.Table 44 — IGC Control Board LED AlarmsDiagnostic LEDs — There are 3 LEDs (red, yell

Page 19 - Fig. 17 — Rigging Information

115Tables 46-48 show the input and output channel designations.Table 46 — I/O Channel Designations Base Module — CVTable 47 — I/O Channel Designations

Page 20 - 48EJ,EK,EW,EY UNITS

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 1

Page 21

CL-1START-UP CHECKLISTMODEL NO.: _________________________________ SERIAL NO.: ______________________________________SOFTWARE VERSION (SEE FIG. 27): _

Page 22

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 1

Page 23

12Fig. 10 — Base Unit Dimensions — 48W,AY060NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units with f

Page 24

13Fig. 11 — Base Unit Dimensions — 48EJ,EK024-034NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units w

Page 25

14Fig. 12 — Base Unit Dimensions — 48EJ,EK038-048NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units w

Page 26 - Table 2 — Operating Weights

15Fig. 13 — Base Unit Dimensions — 48EJ,EK054-068NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units w

Page 27

16Fig. 14 — Base Unit Dimensions — 48EW,EY024-034NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units w

Page 28 - Step 5 — Install Flue Hood

17Fig. 15 — Base Unit Dimensions — 48EW,EY038-048NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units w

Page 29

18Fig. 16 — Base Unit Dimensions — 48EW,EY054-068NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units w

Page 30

1948AJ,AK,AW,AY UNITSFig. 17 — Rigging InformationUNITCENTER OF GRAVITYPERCENT OF TOTAL WEIGHTAT EACH CORNER (%)Inches MillimetersABAB1 2 3 448AJ,AKD0

Page 31

2ROOF CURB — For vertical discharge units, assemble or in-stall accessory roof curb in accordance with instructionsshipped with this accessory. See Fi

Page 32 - Field Supplied Wiring

2048EJ,EK,EW,EY UNITSRIGGING WEIGHTS48AJ,AK,AW,AY UNITS*Includes outdoor-air hoods, filters, largest available indoor-fanmotor, modulating power exhau

Page 33

21Table 1A — Physical Data — 48AJ,AK,AW,AY Units LEGEND *Sizes 020-030: Circuit 1 uses the lower portion of condenser coil, Circuit 2

Page 34

22Table 1A — Physical Data — 48AJ,AK,AW,AY Units (cont) LEGEND *Sizes 020-030: Circuit 1 uses the lower portion of condenser coil, Circ

Page 35

23Table 1B — Physical Data — 48EJ,EK,EW,EY Units*Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper portion.

Page 36

24Table 1B — Physical Data — 48EJ,EK,EW,EY Units (cont)*Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper po

Page 37

25Table 1B — Physical Data — 48EJ,EK,EW,EY Units (cont)*Circuit 1 uses the left condenser coil. Circuit 2 the right. All units have intertwined evapor

Page 38

26Table 2 — Operating Weights48AJ,AK,AW,AY Units 48EJ,EK,EW,EY Units LEGEND*Outdoor-air hoods and filters included in base unit weigh

Page 39

27Table 3 — Evaporator Fan Motor DataNOTES:1. Motor shaft speed is 1750 rpm. The fan shaft diameter is 115/16 inches.2. All indoor fan motors meet the

Page 40

28Step 5 — Install Flue Hood48AJ,AK,AW,AY020-050 AND 48EJ,EK,EW,EY024-048UNITS — Flue hood is shipped inside gas section of unit. Toinstall, secure fl

Page 41

29Size gas-supply piping for 0.5-in. wg maximum pressuredrop. Do not use supply pipe smaller than unit gas connection.OPTIONAL STAGED GAS UNITS — The

Page 42

3Fig. 1 — Roof Curb — 48AJ,AK020-030 and 48EJ,EK024-034 Units

Page 43 - TB — Terminal Block

30Table 5 — Controls Options and Configurations (Non-Thermostat Applications) LEGEND*With DIP Switch No. 5 configured to OPEN (Occupied

Page 44 - R Y1 Y2 W1 W2 G C X

31Features with Thermostat Control of Unit• two-stage heating• two-stage cooling• control of unit using Y1, Y2, W1, W2, and G thermostatinputs• contro

Page 45

32An electronic expansion board may be field-installed to pro-vide the following features:• provide discrete inputs for fan status, filter status, fie

Page 46

33• control of one stage of heat to maintain return-air tem-perature at heating set point during occupied periods• provide a variable frequency drive

Page 47

34 LEGEND*Where X is the unit control software version number.Fig. 27 — Control Board DiagramCCN — Carr

Page 48 - BASE BOARD

35Table 7 — Electrical Data — 48AJ,AK,AW,AY Units LEGEND*Fuse or HACR circuit breaker per NEC.NOTES:1. In compliance with N

Page 49

36Table 7 — Electrical Data — 48AJ,AK,AW,AY Units (cont) LEGEND*Fuse or HACR circuit breaker per NEC.NOTES:1. In compliance

Page 50 - GRAY FOAM STRIP

37Table 7 — Electrical Data — 48AJ,AK,AW,AY Units (cont) LEGEND*Fuse or HACR circuit breaker per NEC.NOTES:1. In compliance

Page 51

38Table 7 — Electrical Data — 48AJ,AK,AW,AY Units (cont) LEGEND*Fuse or HACR circuit breaker per NEC.NOTES:1. In compliance

Page 52 - C7400A1004

39Table 8 — Electrical Data — 48EJ,EK,EW,EY UnitsSee Legend and Notes on page 42.UNITSIZE48EJ,EK,EW,EYNOMNALVOLTAGE(3 Ph,60 Hz)VOLTAGERANGECOMPRESSORO

Page 53 - Fig. 49 — Economizer Details

4Fig. 2 — Roof Curb — 48AJ,AK034-050 and 48EJ,EK038-048 Units

Page 54

40Table 8 — Electrical Data — 48EJ,EK,EW,EY Units (cont)See Legend and Notes on page 42.UNITSIZE48EJ,EK,EW,EYNOMNALVOLTAGE(3 Ph,60 Hz)VOLTAGERANGECOMP

Page 55

41Table 8 — Electrical Data — 48EJ,EK,EW,EY Units (cont)See Legend and Notes on page 42.UNITSIZE48EJ,EK,EW,EYNOMNALVOLTAGE(3 Ph,60 Hz)VOLTAGERANGECOMP

Page 56

42Table 8 — Electrical Data — 48EJ,EK,EW,EY Units (cont) LEGEND*Fuse or HACR circuit breaker per NEC.NOTES:1. In compliance

Page 57 - Step 13 — Field Modifications

43Routing Through Bottom of Unit — If wiring is brought inthrough bottom of unit, use field-supplied watertight conduit torun power wiring from basepa

Page 58

44SEE DETAIL ADIP SWITCHES (FAR SIDE)SENSOR CONNECTIONLOCATIONR Y1 Y2 W1 W2 G C XDETAIL A(THERMOSTAT CONNECTIONLOCATION)TB3Fig. 29 — Control Box Diagr

Page 59 - Crankcase Heaters —

45Thermostat Wiring (CV Only) — Install a Carrier-approvedaccessory thermostat assembly (per current price pages)according to the installation instruc

Page 60

46LEGENDC—Compressor/Contactor FU — Fuse OFC — Outdoor-Fan ContactorCB — Circuit Breaker GND — Ground PEC — Power Exhaust ControllerCCB — Control Circ

Page 61

47Conductors and drain wire must be 20 AWG minimumstranded, tinned copper. Individual conductors must be insulat-ed with PVC, PVC/nylon, vinyl, Teflon

Page 62 - Optional Field Wiring

48Step 10 — Make Outdoor-Air Inlet AdjustmentsECONOMIZERNOTE: If accessory power exhaust or barometric relief pack-ages are being added to the unit, i

Page 63

49Perform the following procedure to assemble the economiz-er hood.1. Apply black seal strip (provided in package) to outsidetop-edge of hood sides. W

Page 64

5Fig. 3 — Roof Curb — 48AJ,AK060 and 48EJ,EK054-068 Units

Page 65

50Minimum Damper Position (MDP) Setting — Setting of theoutdoor air damper position is performed in conjunction with ashortened version of the field r

Page 66

51ECONOMIZER SETTINGSAccessory Enthalpy Control (Fig. 46) — The control(HH57AC077) is mounted in the economizer hood. SeeFig. 37. The enthalpy setting

Page 67

527. Route the wires from the enthalpy sensor to the return airenthalpy control through the holes on the inside of thehinged filter access panel. The

Page 68

53 LEGENDRH — Relative HumidityFig. 48 — Psychrometric Chart for Enthalpy ControlNOTE: Partitions shown indicate both side supply (AW,AY,E

Page 69

54Step 12 — Install All Accessories — After all thefactory-installed options have been adjusted, install all field-in-stalled accessories. Refer to t

Page 70

55Install Motormaster® III Controls — Only one MotormasterIII control is required per unit.Motor — One outdoor-fan motor (OFM) must be changed outin t

Page 71

56Fig. 53B — Motormaster® III Sensor Location(48AJ,AK,AW,AY035 and 48EJ,EK,EW,EY038, 044)Fig. 53C — Motormaster III Sensor Location(48AJ,AK,AW,AY040,

Page 72

57Step 13 — Field ModificationsDUCTWORKBottom Return Units (48AJ,AK,EJ,EK) Field-Modified forSide Return — 48AJ,AK and 48EJ,EK units with bottom re-tu

Page 73

58START-UPUse the following information and Start-Up Checklist onpages CL-1 and CL-2 to check out unit PRIOR to start-up.Unit Preparation — Check that

Page 74

59Crankcase Heaters — Crankcase heaters are energizedas long as there is power to the unit, except when the compres-sors are operating.Variable Freque

Page 75

6Fig. 4 — Roof Curb Adapter — (48AJ,AK060 and 48EJ,EK054-068 Units on 48DD,DF054-064 Retrofit, Part No. CRRCADPT005A00)NOTES:1. Unless otherwise speci

Page 76

608. Press “READ/WRITE” key, to enter the new value. Thedesired set point value will alternately flash to indicatethat the new value has been stored.9

Page 77

61Table 13 — Motor Electronic Thermal Protection (tHr) for Toshiba TOSVERT 130-E3 VFD*IFM Letter refers to the 15th digit (Motor Option) of the unit m

Page 78

62Table 14 — Carrier VFD (Toshiba TOSVERT VF-S9) Program Parameter Values*These settings differ from the Toshiba defaults and are required for Carrier

Page 79 - Table 34 — Air Quality Limits

63Power Exhaust — The optional non-modulating powerexhaust (CV only) is a two-stage design where the operation ofthe exhaust fans is linked to economi

Page 80

64• DIP switch 6 configures the Time Guard® override and,when used with the field test function, sets the minimumdamper position• DIP switch 7 configu

Page 81

65Table 18 — DIP Switch Factory Settings*On 48EJ,EW,AJ,AW units equipped with staged gas option, DIP switch 7 should be closed.Table 19 — Fan Performa

Page 82

66Table 20 — Fan Performance, 48AJ,AK035 — Vertical Discharge Units LEGENDBhp — Brake HorsepowerNOTES:1. Fan performance is based on wet coil

Page 83 - CONTROL BOARD

67Table 21 — Fan Performance, 48AJ,AK040,050 — Vertical Discharge Units LEGENDBhp — Brake HorsepowerNOTES:1. Fan performance is based on wet

Page 84

68Table 22 — Fan Performance, 48AJ,AK060 — Vertical Discharge Units LEGENDBhp — Brake HorsepowerNOTES:1. Fan performance is based on wet coil

Page 85 - NAVIGATOR™

69Table 23 — Fan Performance, 48AW,AY020-030 — Horizontal Discharge Units LEGENDBhp — Brake HorsepowerNOTES:1. Fan performance is based on we

Page 86

7Fig. 5 — Base Unit Dimensions — 48AJ,AK020-030NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units wit

Page 87

70Table 24 — Fan Performance, 48AW,AY035 — Horizontal Discharge Units LEGENDBhp — Brake HorsepowerNOTES:1. Fan performance is based on wet co

Page 88

71Table 25 — Fan Performance, 48AW,AY040,050 — Horizontal Discharge Units LEGENDBhp — Brake HorsepowerNOTES:1. Fan performance is based on we

Page 89 - Service Access —

72Table 26 — Fan Performance, 48AW,AY060 — Horizontal Discharge Units LEGENDBhp — Brake HorsepowerNOTES:1. Fan performance is based on wet co

Page 90 - 3. Dimensions are in inches

73Table 27 — Fan Performance, 48EJ,EK024,034 — Vertical Discharge Units(For EW,EY units, reduce net available external static pressure by 0.3 in. wg)

Page 91 - Lubrication

74Table 28 — Fan Performance, 48EJ,EK038,044 — Vertical Discharge Units(For EW,EY units, reduce net available external static pressure by 0.5 in. wg)

Page 92 - Condenser-Fan Adjustment

75Table 29 — Fan Performance, 48EJ,EK048 — Vertical Discharge Units(For EW,EY units, reduce net available external static pressure by 0.5 in. wg)

Page 93 - Gas Valve Adjustment

76Table 30 — Fan Performance, 48EJ,EK054-068 — Vertical Discharge Units LEGENDBhp — Brake HorsepowerNOTES:1. Fan performance is based on dry

Page 94 - CHARGING CHART

77Table 31 — Fan Performance, 48EW,EY054-068 — Horizontal Discharge Units LEGENDBhp — Brake HorsepowerNOTES:1. Fan performance is based on dr

Page 95

78Table 32A — Fan Performance — Power Exhaust, 48AJ,AK,AW,AY020-050 and 48EJ,EK,EW,EY024-048 LEGENDTable 32B — Fan Performanc

Page 96

79Table 33 — Motor Limitations LEGENDBhp — Brake HorsepowerNOTES:1. Extensive motor and electrical testing on the Carrier units hasensured

Page 97

8Fig. 6 — Base Unit Dimensions — 48AJ,AK035-050NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units wit

Page 98

80Return-Air Filters — Check that correct filters are in-stalled in filter tracks (see Tables 1A and 1B). Do not operateunit without return-air filter

Page 99

81Table 35 — User Defined Set Points LEGENDTable 36 — Software Control Link Points LEGENDSET POINTNAMEFORMAT DESCRIPTION LIMITS DEF

Page 100

82The Time Guard® function maintains a minimum offtime of 5 minutes, a minimum ON time of 10 seconds, and aminimum delay before starting the second co

Page 101

83GAS HEATING, VARIABLE AIR VOLUME (VAV)UNITS — All of the gas heating control is performed throughthe integrated gas control (IGC) board. The control

Page 102

84Table 37 — Staged Gas System ComponentsTable 38 — Stage Gas System Inputs/OutputsOperating Modes — The SGC will operate the unit in one ofthe follow

Page 103 - TROUBLESHOOTING

85MORNING WARM-UP (VAV only with PC Accessed/CCNOperation) — Morning warm-up occurs when the control hasbeen programmed to turn on heat prior to the O

Page 104 - LPS — Low-Pressure Switch

86Table 40 — Occupied Heat and Morning Warm-Up Operation and Controlling Factors LEGENDSPACE TEMPERATURE SENSOR CONTROL — If the un

Page 105

87SUPPLY AIR TEMPERATURE RESET — Supply air tem-perature reset is used to reset the supply-air temperature utility.A 4 to 20 mA signal (field-supplie

Page 106 - LEGEND

88Table 41 — Smoke Control Modes LEGENDHEAD PRESSURE CONTROL — Each unit has a fan cy-cling, outdoor thermostat to shut off the out

Page 107

89If a Y2 (or Y2_SPT) call begins while the unit was under“Y1 cooling” control, compressor no. 2 will not be started until“Y1 cooling” control has end

Page 108

9Fig. 7 — Base Unit Dimensions — 48AJ,AK060NOTES:1. Weights include economizer (standard).2. Center of Gravity.3. Do not locate adjacent units with fl

Page 109

90To inspect blower wheel, remove heat exchanger accesspanel. Shine a flashlight into opening to inspect wheel. If clean-ing is required, remove motor

Page 110

91LubricationCOMPRESSORS — Each compressor is charged with thecorrect amount of oil at the factory. The correct oil charge isshown in Tables 1A and 1B

Page 111

925. Be sure that hub flanges, flex members, spacer, and hard-ware are clean and free of oil.6. Place the flanges onto the shafts with the hub facing

Page 112

93Power Failure — The economizer damper motor is aspring return design. In event of power failure, dampers will re-turn to fully closed position until

Page 113 - IDM — Induced-Draft Motor

94Main Burners — For all applications, main burners arefactory set and should require no adjustment.MAIN BURNER REMOVAL (Fig. 76)1. Shut off (field-su

Page 114

95Filter Drier — Replace whenever refrigerant system is ex-posed to atmosphere.Protective DevicesCOMPRESSOR PROTECTIONOvercurrent — Each compressor ha

Page 115 - HV — High Voltage T—Terminal

96Fig. 77 — Typical Power Schematic 48EJ,EK,EW,EY024-034; 208/230-3-60 and 460-3-60NOTES:1. Connect TRAN1 to H4 for 460 v units. Connect toH3 for 230

Page 116 - SERVICE TRAINING

97Fig. 78 — Typical 48EK VAV 24-V Control Circuit

Page 117 - START-UP:

98NOTE: Red wire and violet wire are spliced together at the factory. The brown wire has a wire nut added at the factory.Fig. 79 — Typical CV 24-V Con

Page 118

99Fig. 80 — Typical 48EK VAV 115-V Control Circuit

Commentaires sur ces manuels

Pas de commentaire