Alarm■file
This file maintains the last 25 time- and date-stamped
alarm and alter messages in memory; this function reduces
troubleshooting time and cost.
Overrides
The control system detects conditions which approach
protective limits and takes self-corrective action prior to
an alarm occurring.
The system automatically reduces chiller capacity when
any of the following parameters are outside their normal
operating range:
- High condenser pressure
- High motor temperature
- Low evaporator refrigerant temperature
- High motor current
During the capacity override period, a pre-alarm (alert)
message is displayed, informing the operator which condi-
tion is causing the capacity override. Once the condition is
again within acceptable limits, the override condition is
terminated and the chiller reverts to normal chiller water
control.
During either condition, if the protective limit is reached,
the chiller shuts down and a message is displayed informing
the operator which condition has caused the shutdown
and alarm. This function increases unit life.

On the19XR base units capacity control is by means of
variable inlet guide vanes located at the impeller inlet. Load
modulation is from 100% to 15% of compressor full load
under nominal ARI conditions without the use of hot gas
bypass. The guide vanes are precisely positioned by a PID
(proportional-integral-derivative) control algorithm to
ensure precise and quick control of desired chilled-water
temperature without hunting or overshooting the set point.
If the machine includes a factory-installed variable-frequency
drive (19XRV), the compressor speed is regulated by the
control of the voltage-frequency values, applied to the
motor. The voltage applied, generated by pulse width
modulation, is proportional to the frequency.
The calculation of the water temperature parameter
deviation measured results in an adjustment of the machine
capacity through a simultaneous and coordinated action
on guide vane opening and compressor speed.

Mechanically cleanable cooler and condenser.
The machine concept allows the refrigerant to be stored
inside the chiller during servicing, reducing refrigerant loss
and eliminating time-consuming transfer procedures.
Easy-access suction and discharge pressure and temperature
information using enhanced display module.