Carrier COBRA 48/50HJ004-014 Spécifications

Naviguer en ligne ou télécharger Spécifications pour Pompes à chaleur Carrier COBRA 48/50HJ004-014. Carrier COBRA 48/50HJ004-014 Specifications Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 90
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 534-80159 Printed in U.S.A. Form 48/50HJ,62AQ-3SIS Pg 1 4-06 Replaces: 48/50HJ,62AQ-2SIS
Book 1144
Tab 1a1b6a6b
Installation, Start-Up, and Service Supplement
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-42
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . . 2
COBRA UNIT WITH A FULL-PERIMETER ROOF CURB
COBRA UNIT WITH A STANDARD ROOF CURB
Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . . . . . . . . 3
Step 4 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . . . . . . . . 6
POSITIONING
Step 5 — Install Flue Hood (48HJ Rooftop
Sections Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 6 — Install Gas Piping (48HJ Rooftop
Sections Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 7 — Install External Trap for Condensate
Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 8 — Make Electrical Connections . . . . . . . . . . . . . . 11
FIELD POWER SUPPLY
FACTORY-SUPPLIED NON-FUSED DISCONNECT
FIELD CONTROL WIRING
THERMIDISTAT™ DEVICE
PREMIERLINK™ CONTROLLER
HEAT ANTICIPATOR SETTINGS
INDOOR AIR QUALITY AND CO
2
SENSORS
Step 9 — Assemble and Mount Supply-Air Hood . . . . 39
Step 10 — Mount the Barometric Relief Damper. . . . . 39
Step 11 — Set the Outdoor Cooling and
Heating Thermostats. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
LIGHT COMMERCIAL THERMIDISTAT
ACCESSORY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-46
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Dehumidification Equipment and Connections. . . . . . 42
Step 1 — Select Light Commercial
Thermidistat Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Step 2 — Set DIP Switches . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Step 3 — Install Light Commercial Thermidistat
Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Step 4 — Set Light Commercial Thermidistat
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Step 5 — Conduct Light Commercial
Thermidistat Start-Up and Checkout . . . . . . . . . . . . . . 45
Step 6 — Make Final Settings . . . . . . . . . . . . . . . . . . . . . . . 46
OPERATIONAL INFORMATION . . . . . . . . . . . . . . . . . . . 46-69
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70,71
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72-88
ROOFTOP UNIT AND ENERGY RECOVERY UNIT
START-UP CHECKLIST. . . . . . . . . . . . . . . . . . . . CL-1, CL-2
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that apply.
Verify that the power source supplied to the unit matches
the voltages and amperages listed on the unit rating plate.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
GENERAL
Carriers COBRA energy recovery units precondition venti-
lation air for the rooftop unit during winter and summer opera-
tion and recover energy from the building exhaust air. These
units are designed to satisfy the higher ventilation requirements
and other building codes while minimizing energy costs.
Factory installation of the 62AQ Energy$Recycler™ sec-
tion provides the benefit of reduced field-installation time,
single point power connections, and the assurance of a factory
test for the complete COBRA energy recovery unit. The
Energy$Recycler section requires less maintenance than other
energy recovery systems and can be serviced by any qualified
refrigeration technician.
NOTE: The COBRA unit nameplate has been moved to the
opposite end of the rooftop section, on the upper,
right-hand part of the panel due to the location of the 62AQ
Energy$Recycler section.
IMPORTANT: This is a supplemental instruction for the
48/50HJ Start-Up and Service Instructions. It is not
intended to take the place of the instruction or to be a com-
plete piece by itself.
IMPORTANT: Make sure supply voltage matches unit
nameplate voltage.
Disconnect gas piping from unit when leak
testing at pressure greater than
1
/
2
psig. Pres-
sures greater than
1
/
2
psig will cause gas
valve damage resulting in hazardous condi-
tion. If gas valve is subjected to pressure
greater than
1
/
2
psig, it must be replaced
before use. When pressure testing field-
supplied gas piping at pressures of
1
/
2
psig or
less, a unit connected to such piping must be
isolated by manually closing the gas valve.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install a lock-
out tag. Electrical shock could cause personal injury.
COBRA™ Energy Recovery Units
48/50HJ004-014 with 62AQ060-300
Single-Package Rooftop Units
with Energy Recovery Capability
Vue de la page 0
1 2 3 4 5 6 ... 89 90

Résumé du contenu

Page 1 - Single-Package Rooftop Units

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 2 - Step 1 — Inspect Shipment —

10Fig. 5B — Base Unit Dimensions — COBRA™ Energy Recovery Unit — 48/50HJ008-014 with 62AQ200,300 (cont)BOTTOM POWER CHARTTHESE HOLES REQUIRED FOR USEW

Page 3 - APPROVED CURB IS NOT

11Step 5 — Install Flue Hood (48HJ Rooftop Sec-tions Only) — Refer to the 48HJ installation instructions forinformation on installing the flue hood.St

Page 4

12Fig. 6B — Rigging Label — COBRA™ Energy Recovery Unit — Sizes 48/50HJ008-014MAX WEIGHT A B Clb kg in. mm in. mm in. mm48HJ008 w/62AQ200 1310 595 77.

Page 5

13If the 208/230-v unit is to be connected to a 208-v powersupply, the transformer must be rewired by moving the blackwire with the 1/4-in. female spa

Page 6 - SECTION

14PREMIERLINK™ CONTROLLER — The PremierLink digi-tal controller is a Direct Digital Control (DDC) box that mountsin the rooftop unit under the main un

Page 7

15LEGENDFig. 13 — Power Wiring ConnectionsC—ContactorCOMP — CompressorIFC — Indoor-Fan ContactorNEC — National Electrical CodeTB — Terminal Block208/2

Page 8

16PREMIERLINK™ TERMINALBLOCKCONTROL WIRINGTERMINAL BLOCK(TB1)POWER WIRINGOPTIONAL FACTORY - INSTALLEDDISCONNECT(TB2)(TB3)Fig. 14 — Field Wiring Connec

Page 9

17W2RY1Y2W1GCXHMOCT STATUNITW2W1W2W1HMHMRBASE UNITCONNECTIONBOARDROOFTOP SECTIONCONTROL BOXENERGY$RECYCLER™CONTROLBOXTHERMOSTATCONNECTIONBOARDGCY1Y2W1

Page 10

18HUMIDISTATROOFTOP SECTIONCONTROL BOXENERGY$RECYCLER™CONTROL BOXGRAREDBASE UNITCONNECTIONBOARDCONNECTIONBOARDOPEN HOLEFOR WIRESMOUNTING HOLESHMHMW1W2

Page 11

19SPACE TEMPERATURE SENSOR(33ZCT56SPT)W2RY1Y2W1GCXHMOCT STATUNITW2W1W2W1HMHM12345678BLUBRNBLKTB2 TB1PREMIERLINKCONTROLSHMRHUMIDISTAT234561SW1 SENSETC

Page 12

2INSTALLATIONStep 1 — Inspect Shipment — File a claim with theshipping company if shipment is incomplete or damaged. SeeFig. 1 for typical shipping pa

Page 13 - BRASS FITTING

20CGRY1Y2W1W2OCDEHUM*LIGHT COMMERICAL THERMIDISTAT DEVICE HMHMW1W2OCHMW1W2T STATUNITW1W2Y2Y1RGCXTHERMOSTATCONNECTIONBOARDTB1PREMIERLINKCONTROLS1234567

Page 14

21RACEWAY LOW VOLTAGECONNECTIONSINTEGRATED GAS UNITCONTROLLER (IGC)POWERSUPPLYROOF CURBCONDUIT WITHWATERTIGHTCONNECTIONS(FIELD-SUPPLIED)FIELD-SUPPLIED

Page 15

22NOTE: Remove all unused red wires from J4 connector to prevent 24 vac shorting other components or ground. Inputs on J4 are 24 vac; red leads are vo

Page 16 - TERMINAL

23NOTE: Remove red wire from J4-9 to prevent 24 vac shorting out other components or ground.Fig. 22 — PremierLink™ Field-Installed Controller Sensor M

Page 17

24TERMINALBLOCKFig. 23 — Field Wiring Connections(Terminal Block in Energy Recovery Section)a48-6487

Page 18

25Table 1A — Electrical Data (COBRA™ Energy Recovery 48HJ004-007 Units with 62AQ060)LEGEND*The values listed in this table do not include power exhaus

Page 19 - ROOFTOP UNIT

26Table 1B — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ060)UNITSIZENOMINAL V-PH-HzIFMTYPECONV OUTLET62AQ FLAHEATER MODEL NO.

Page 20

27Table 1B — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ060) (cont)LEGEND*The values listed in this table do not include power

Page 21

28Table 1B — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ060) (cont)LEGEND*The values listed in this table do not include power

Page 22

29Table 1C — Electrical Data (COBRA™ Energy Recovery 48HJ004-007 Units with 62AQ100)LEGEND*The values listed in this table do not include power exhaus

Page 23

3COBRA UNIT WITH STANDARD ROOF CURB — If astandard rooftop curb is used (for new or retrofit applications),it is capable of supporting the rooftop un

Page 24

30Table 1D — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ100)UNITSIZENOMINALV-PH-HzIFMTYPECONV OUTLET62AQ FLAHEATER MODEL NO.

Page 25

31Table 1D — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ100) (cont)LEGEND*The values listed in this table do not include powe

Page 26

32Table 1D — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ100) (cont)LEGEND*The values listed in this table do not include power

Page 27

33Table 1E — Electrical Data (COBRA™ Energy Recovery 48HJ008-014 Units with 62AQ200)LEGEND*The values listed in this table do not include power exhaus

Page 28

34Table 1F — Electrical Data (COBRA™ Energy Recovery 50HJ008-014 Units with 62AQ200)UNITSIZENOMINAL V-PH-HzIFMTYPECONV OUTLET62AQ FLAHEATER MODEL NO.

Page 29

35Table 1F — Electrical Data (COBRA™ Energy Recovery 50HJ008-014 Units with 62AQ200) (cont)LEGEND*The values listed in this table do not include power

Page 30

36Table 1G — Electrical Data (COBRA™ Energy Recovery 48HJ008-014 Units with 62AQ300)LEGEND*The values listed in this table do not include power exhaus

Page 31

37Table 1H — Electrical Data (COBRA™ Energy Recovery 50HJ008-014 Units with 62AQ300)UNITSIZENOMINALV-PH-HzIFMTYP CONV OUTLET62AQ FLAHEATER MODEL NO.

Page 32

38Table 1H — Electrical Data (COBRA™ Energy Recovery 50HJ008-014 Units with 62AQ300) (cont)LEGEND*The values listed in this table do not include power

Page 33

39INDOOR AIR QUALITY AND CO2 SENSORS — If a spaceCO2 sensor is desired, a field-installed 25% outdoor-air dampermust be used for proper Demand Control

Page 34

4NOTES:1. Roof curb accessory is shipped disassembled.2. Insulated panels.3. Dimensions in [ ] are in millimeters.4. Roof curb: galvanized steel.5. At

Page 35

408765432133ZCSENCO2CRTWOPOS001A01 or CRTWOPOS002A02TWOPOSITIONDAMPERPLUGR124v Power24v PowerCOMR1R162AQ CONNECTIONBOARDCommercialThermidistatNO(Alarm

Page 36

41HOODSIDEKNOBEND CAPTEMPERATURE SWITCHSHIPPED WITH UNITALUMINUM FILTER SCREENCOOLING SET POINTTHERMOSTAT (WHITE LABEL)HOOD SIDEKNOBDAMPER BLADE STOPS

Page 37

42Step 11 — Set the Outdoor Cooling and Heat-ing ThermostatsCOOLING — During the unoccupied period, the economizermode of operation is used as the fir

Page 38

43Step 2 — Set DIP Switches — There is a 4-sectionDIP (Dual In-line Package) switch within the light commercialThermidistat™ device which must be prop

Page 39 - Damper —

44WHILE IN CONFIGURATION MODE — The upper small(COOL set point) display indicates selected option number andlarge display indicates selection made w

Page 40 - Fig. 26 — CO

45Option 9 — Holiday Heat Set Point — This selection deter-mines the heating set point (40 to 90 minus deadband F) whenthe HOLIDAY function is active.

Page 41

46While in Installer Test mode, clock will display “InSt,” FANbutton will control fan, and MODE button will control heatingand cooling.TO TEST FAN:NOT

Page 42 - ACCESSORY

47Unoccupied Cooling Mode — During unoccupiedperiods the system fans and compression will cycle in responseto the light commercial Thermidistat device

Page 43

48Table 2A — COBRA™ Energy Recovery Unit Sequence of Operation — UnoccupiedLEGEND *Second stage for Y2 call applicable on rooftop units with 2 circuit

Page 44

49Table 3A — Humidi-MiZer™ Adaptive Dehumidification System Rooftop with COBRA™ Energy Recovery UnitSequence of Operation — Unoccupied

Page 45 - — This op

5Fig. 3B — Roof Curb Details (48/50HJ008-014 Section Only)NOTES:1. Roof curb accessory is shipped disassembled.2. Insulated panels: 1-in. thick polyur

Page 46 - OPERATIONAL INFORMATION

50AIRFLOW CONSIDERATIONS — A COBRA™ unit ispotentially capable of allowing up to 100% outdoor air (OA).This application depends specifically on the

Page 47 - ENERGY RECOVERY SECTION

51BAROMETRIC RELIEF DAMPERS — The barometric re-lief damper is located in the exhaust fan section. The damperlimiter can be set for 30, 45, or 60 degr

Page 48

52-0.40-0.30-0.20-0.100.00350 400 450 500 550 600 650 700 750AIRFLOW (CFM)RETURN DUCT STATIC PRESSURE (IN. WG) 350 450 550 650 750AIRFLOW (CFM)50100

Page 49

53-0.40-0.30-0.20-0.100.00400 450 500 550 600 650 700 750AIRFLOW (CFM) RETURN DUCTSTATIC PRESSURE(IN. WG)350 450 550 650 750AIRFLOW (CFM)50100150200

Page 50

54-0.60-0.50-0.40-0.30-0.20-0.100.00500 550 600 650 700 750800850 900 950 1000 1050 1100 AIRFLOW (CFM)RETURN DUCTSTATIC PRESSURE(IN. WG)500 600 700

Page 51

55-0.70-0.60-0.50-0.40-0.30-0.20-0.100.00600 650 700 750 800 850 900 950 1000 1050 1100 AIRFLOW (CFM)RETURN DUCTSTATIC PRESSURE(IN. WG)600 700 800 9

Page 52 - FAN POWER (WATTS)

56-0.70-0.60-0.50-0.40-0.30-0.20-0.101100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100AIRFLOW (CFM)RETURN DUCTSTATIC PRESSURE(IN. WG)1100 1200 13

Page 53

57-0.70-0.60-0.50-0.40-0.30-0.20-0.101100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 AIRFLOW (CFM)RETURN DUCTSTATIC PRESSURE(IN. WG)1100 1200

Page 54

58-0.70-0.60-0.50-0.40-0.30-0.20-0.101100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 AIRFLOW (CFM)RETURN DUCTSTATIC PRESSURE(IN. WG)1100 1200

Page 55 -  — Damper at 45 Degrees Open

59-0.70-0.60-0.50-0.40-0.30-0.20-0.101700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 3100 3200 PULLEY 5 TURNS OPENNO DAMPER ST

Page 56

6Step 4 — Rig and Place Unit — Keep unit uprightand do not drop. Spreader bars are not required if top crating isleft on unit. Rollers may be used to

Page 57

60-0.60-0.50-0.40-0.30-0.20-0.100.000.100.200.300.400.50350 400 450 500 550 600 650 700 750 RETURN DUCTSTATIC PRESSURE(IN. WG)AIRFLOW (CFM)300 400 5

Page 58

61-0.60-0.50-0.40-0.30-0.20-0.100.000.100.200.300.400.50350 450 550 650 750 AIRFLOW (CFM)RETURN DUCTSTATIC PRESSURE(IN. WG)300 400 500 600 700050100

Page 59 - (IN. WG)

62-0.60-0.50-0.40-0.30-0.20-0.100.000.100.200.300.400.500.600.700.80400 500 600 700 800 900 1000 1100 AIRFLOW (CFM)RETURN DUCTSTATIC PRESSURE(IN. WG

Page 60

63-0.60-0.50-0.40-0.30-0.20-0.100.000.100.200.300.400.500.600.700.800.90500 600 700 800 900 1000 1100 AIRFLOW (CFM)RETURN DUCTSTATIC PRESSURE(IN. WG

Page 61

64-0.60-0.50-0.40-0.30-0.20-0.100.000.100.200.300.400.500.600.700.800.901000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 AIRFLOW (CFM)RETURN D

Page 62

651000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000300400500600700800 High Speed - all damper positionsLow Speed - all damper positionsMed Spee

Page 63

661000 1100 1200 1300 1400 1500 1600 1700 1800 1900 20004005006007008009001000 High Speed - all damper positionsLow Speed - all damper positionsMed

Page 64

67-1.00-0.90-0.80-0.70-0.60-0.50-0.40-0.30-0.20-0.100.000.100.200.300.400.500.601900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 RETURN D

Page 65

68-0.90-0.80-0.70-0.60-0.50-0.40-0.30-0.20-0.100.000.100.200.300.400.500.600.700.800.901900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 310

Page 66

69-0.90-0.80-0.70-0.60-0.50-0.40-0.30-0.20-0.100.000.100.200.300.400.500.600.700.800.901900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000AIRF

Page 67 - AIRFLOW (CU FT/MIN)

7RIGHTSIDEREARRIGHT SIDEFRONTLEFT SIDEFRONTLEFTSIDEFig. 5A — Base Unit Dimensions — COBRA™ Energy Recovery Unit — 48/50HJ004-007 with 62AQ060,100a48-6

Page 68

70PRE-START-UPRefer to 48/50HJ Installation Instructions for Pre-Start-Upinformation for the rooftop unit section. Proceed as follows toinspect and pr

Page 69

71Fig. 71 — Fuse Box (48HJ012,014 — 208/230-3-60 Units Only)a48-6463

Page 70

72TROUBLESHOOTINGUse Tables 5 and 6, and Fig. 72-79 when troubleshooting this unit.Fig. 72 — COBRA™ Unit Wiring Schematic (50HJ006 with 62AQ060/100, 2

Page 71

73Fig. 72 — COBRA™ Unit Wiring Schematic (50HJ006 with 62AQ060/100, 208/230-3-60) with Electro-Mechanical Controls (cont)a50-8018

Page 72 - LEGEND FOR FIG. 72-79

74HJ008/009Fig. 73 — COBRA™ Unit Wiring Schematic (48HJ008-012 with 62AQ200, 208/230-3-60) with Electro-Mechanical ControlsNOTES:1. If any of the orig

Page 73

75HJ012Fig. 73 — COBRA™ Unit Wiring Schematic (48HJ008-012 with 62AQ200, 208/230-3-60) with Electro-Mechanical Controls (cont)a48-8166

Page 74 - HJ008/009

76NOTES:1. If any of the original wire furnished must be replaced, it mustbe replaced with Type 90 C wire or its equivalent.2. Three phase motors are

Page 75

77Fig. 74 — COBRA™ Unit Wiring Schematic (50HJ008/009 with 62AQ300, 208/230-3-60) with Electro-Mechanical Controls (cont)a50-8020

Page 76

78Fig. 75 — COBRA™ Unit Wiring Schematic (50HJ014 with 62AQ300, 460-3-60) with Electro-Mechanical ControlsNOTES:1. If any of the original wire furnish

Page 77

79Fig. 75 — COBRA™ Unit Wiring Schematic (50HJ014 with 62AQ300, 460-3-60) with Electro-Mechanical Controls (cont)a50-8022

Page 78

8Fig. 5A — Base Unit Dimensions — COBRA™ Energy Recovery Unit — 48/50HJ004-007 with 62AQ060,100 (cont)BOTTOM POWER CHARTTHESE HOLES REQUIRED FOR USEWI

Page 79

80Fig. 76 — COBRA™ Unit Wiring Schematic (48HJ006/007 with 62AQ060/100, 460-3-60) with Factory-Installed PremierLink™ ControllerNOTES:1. If any of the

Page 80

81Fig. 76 — COBRA™ Unit Wiring Schematic (48HJ006/007 with 62AQ060/100, 460-3-60) with Factory-Installed PremierLink™ Controller (cont)a48-8168

Page 81

82Fig. 77 — COBRA™ Unit Wiring Schematic (50HJ008-014 with 62AQ200, 460-3-60) with Factory-Installed PremierLink™ ControllerNOTES:1. If any of the ori

Page 82

83Fig. 77 — COBRA™ Unit Wiring Schematic (50HJ008-014 with 62AQ200, 460-3-60) with Factory-Installed PremierLink™ Controller (cont)a50-8024

Page 83

84Fig. 78 — COBRA™ Unit Wiring Schematic (50HJ008/009 with 62AQ300, 208/230-3-60) with Factory-Installed PremierLink™ ControllerNOTES:1. If any of the

Page 84

85Fig. 78 — COBRA™ Unit Wiring Schematic (50HJ008/009 with 62AQ300, 208/230-3-60) with Factory-Installed PremierLink™ Controller (cont)a50-8026

Page 85

86Fig. 79 — COBRA™ Unit Wiring Schematic (50HJ008/009 with 62AQ300, 208/230-3-60) with Factory-Installed PremierLink™ ControllerNOTES:1. If any of the

Page 86

87Fig. 79 — COBRA™ Unit Wiring Schematic (50HJ008/009 with 62AQ300, 208/230-3-60) with Factory-Installed PremierLink™ Controller (cont)NOTES:1. If any

Page 87

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 88 - Tab 1a1b6a6b

CL-1ROOFTOP SECTION AND ENERGY$RECYCLER SECTION (62AQ) START-UP CHECKLIST(Remove and Store in Job File) I. PRELIMINARY INFORMATION RTU 62AQII. PRE-STA

Page 89 - III. START-UP

9Fig. 5B — Base Unit Dimensions — COBRA™ Energy Recovery Unit — 48/50HJ008-014 with 62AQ200,300a48-6453

Page 90 - III. START-UP (cont)

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Commentaires sur ces manuels

Pas de commentaire