HEATING & COOLING
38AK007
Air-Cooled Condensing Unit
Installation, Start-Up and Service
Instructions
SAFETY COIMSIDERATIONS
Installing and servicing air-conditioning equipment can
be hazardous due to system pressure and electrical compo
nents. Only trained and qualified service personnel should
install or service air-conditioning equipment.
When working on air-conditioning equipment, observe
precautions in literature and on tags and labels attached to
unit.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have
fire extinguisher available. Read these instructions thor
oughly. Consult local building codes and National Electri
cal Code (NEC) for special installation requirements.
A WARNING
Before installing or servicing system, always turn off
main power to system. There may be more than one
disconnect switch. Electrical shock can cause personal
injury.
INSTALLATION
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT Remove unit packaging except for
the top skid assembly and wood bumpers, which should be
left in place until after unit is rigged into place.
INSPECT SHIPMENT File claim with shipping com
pany if shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
Consult local building codes and NEC for special instal
lation requirements.
Allow sufficient space for airflow clearance, wiring,
refrigerant piping, and servicing unit. See Eig. 1 and
Table 1.
Locate unit so that condenser airflow is unrestricted on
all sides and above. Refer to Fig. 1.
Unit may be mounted on a level pad directly on base
rails or mounted on raised pads at support points. See
Table 2 for weight distribution based on recommended
support points.
NOTE: If vibration isolators are required for a particular in
stallation, use data in Table 2 to make proper selection.
Table 1 — Physical Data
UNIT 38AK
007
OPER WEIGHT (lb)
340
REFRIGERANT*
22
COMPRESSOR
on (oz) 65
CONDENSER AIR FAN
Number...Rpm 60 Hz
50 Hz
Diameter (in.)
Motor Hp (NEMA)
Nominal Cfm Total
Propeller; Direct Drive
1.. .850
1.. 708
26
Vs
3800
CONDENSER COIL
Face Area (sq ft)
Storage Capacity (lb)t
12 24
11.264
CONNECTIONS (sweat)
Suction (in.)
Liquid (In.)
1V8
V2
CONTROLS
Pressurestat Settings
High Cutout
Cut-in
Low Cutout
Cut-in
426 ± 7 psig
320 ± 20 psig
7 ± 3 psig
22 ± 5 psig
FUSIBLE PLUG 200 F
‘Unit is factory supplied with holding charge only.
fStorage capacity of condenser coil with coil 80% full of liquid R-22
at 124 F
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 |4 PC 111 Catalog No 633-809 Printed in U.S A Form 38AK-2SI Pg 1 6-92 Replaces: New
Tab 3a 2a
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1

HEATING & COOLING38AK007Air-Cooled Condensing UnitInstallation, Start-Up and ServiceInstructionsSAFETY COIMSIDERATIONSInstalling and servicing

Page 2

Table 2 — Weight DistributionREFRIGERANT PIPING SIZESUNITSTD. UNIT WEIGHTCORNER WEIGHT (A)CORNER WEIGHT (B)lbs.kg.lbs.kg. lbs.kg.38AK0073401548639 532

Page 3

NOTES:1. Dimensions in are in miiiimeters. Center of gravity.Direction of air fiow.34 Minimum ciearance (locai codes or jurisdiction may prevaii):a B

Page 4

FIELD POWER SUPPLY - All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is